FRAME ANALYSIS

By: Mohammad Soffi bin Md. Noh

BFC 3172

Introduction
In the design of RC structures based on BS 8110 it has to analyse the structure subjected to all probable combinations of loads, considering the ultimate limit state. Once the bending moment, shear force etc. were obtained, reinforcements can be designed according to the standard. Generally, three dimensional wide frame analysis is the most accurate method to analyse the frame building. 3-D frame is complex and need to be carried out using relevant computer software. Clause 3.2.1.1 BS 8110: Part 1: 1997 states that the analysis may be simplified appropriately sub-frame. Hence there are 3 levels sub-frames: Complete sub-frame Simplified sub-frame Simplified sub-frame at point

Reinforced Concrete Design 2

BFC 3172

Method of Frame Analysis


1) Complete sub-frame

Reinforced Concrete Design 2 BFC 3172

The frame consists of all beams at each level with columns top and bottom of beams. Moments at columns and beams are tabulated by analyzing the complete subframe.

Method of Frame Analysis


2) Simplified sub-frame

Reinforced Concrete Design 2

The frame consists of a selected beam with columns and neighbouring beams at both sides of selected beam.

BFC 3172

Method of Frame Analysis


3) Simplified sub-frame at point

Reinforced Concrete Design 2

The frame consists of a selected point or node with columns at top and bottom, and neighbouring beams coming into the point.

BFC 3172

Analysis of Braced Frame


A building is saying as braced frame when the horizontal loadings are resisting by the shear walls or bracing. The analysis of braced frame is only considered for the vertical loads which are dead and imposed load. For the combination of dead load and imposed load, the following loading patterns are considered:
All spans loaded with maximum dead plus imposed loads Alternate spans loaded with maximum dead load and imposed load and all other spans loaded with minimum dead load

Reinforced Concrete Design 2

BFC 3172

Analysis of Braced Frame

1.4Gk + 1.6Qk

1.4Gk + 1.6Qk

1.4Gk + 1.6Qk

1.4Gk + 1.6Qk

Reinforced Concrete Design 2

1.4Gk + 1.6Qk

1.0Gk

1.4Gk + 1.6Qk

1.0Gk

1.0Gk

1.4Gk + 1.6Qk

1.0Gk

1.4Gk + 1.6Qk

BFC 3172

Example 1.1
A four storey braced building is given in Figure P1.1. Perform the analysis for ABCD. Given the following data: All columns = 350 mm x 300 mm Gk = 25 kN/m All beams = 300 mm x 600 mm Qk = 10 kN/m

Reinforced Concrete Design 2

BFC 3172

Example 1.1
Solution Beam Stiffness

Reinforced Concrete Design 2

Column Stiffness

BFC 3172

Example 1.1
Completed Sub-Frame Analysis

Reinforced Concrete Design 2

Max load = 1.4(25) + 1.6(10) = 51 kN/m Min Load = 1.0(25) = 25 kN/m

BFC 3172

Example 1.1
Load Case 1

Reinforced Concrete Design 2

All spans loaded with maximum dead plus imposed loads

BFC 3172 Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Example 1.1

Load Case 2

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Example 1.1
Load Case 3

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Simplified sub-frame Load Case 1

Example 1.1

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Example 1.1

Example 1.1

Load Case 2

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Example 1.1

Example 1.1

Load Case 3

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Simplified Sub-Frame at Point Point A & D

Example 1.1

Example 1.1

BFC 3172

Example 1.1
Point B & C

Reinforced Concrete Design 2 BFC 3172

Example 1.2
Figure P1.2 shows the four spans sub frame. Given: UDL (all spans): Concentrated load (span BC): Gk = 20 kN/m Gk = 30 kN Qk = 15 kN/m Qk = 15 kN Sketch the loadings arrangement.

Reinforced Concrete Design 2

BFC 3172

Example 1.2
Solution UDL Max = 1.4(20) + 1.6(15) = 52 kN/m Concentrated Load Max = 1.4(30) + 1.6(15) = 66 kN Load Case 1

Reinforced Concrete Design 2

Min = 1.0(20) = 20 kN/m Min = 1.0(30) = 30 kN

BFC 3172

Example 1.2
Load Case 2

Reinforced Concrete Design 2

Load Case 3

BFC 3172

Analysis of Unbraced Frame


For unbraced frame, the greatest of the following moments and shearing forces are to be taken for design purposes: Three cases loading arrangements as braced sub-frame (max = 1.4Gk + 1.6Qk, min = 1.0Gk)

Reinforced Concrete Design 2 BFC 3172

Analysis of Unbraced Frame


(i) Vertical loads (1.2Gk + 1.2Qk) for sub-frame + (ii) Wind load (1.2Wk) for complete frame

Reinforced Concrete Design 2

BFC 3172

Analysis of Unbraced Frame


Analysis of Horizontal Load Using Portal Method

Reinforced Concrete Design 2 BFC 3172

The following assumptions have to be made: Loads applied at beam-column junction. Total horizontal shear at any level is carried by columns at the points of contraflexure immediately below the level. The points of contraflexure occur at the mid-heights of columns and at midspans of beams. Each bay acts as a separate portal and the horizontal load is divided between bays in proportion to span.

Example 1.3
Draw the bending moment diagram of the 5 storey building frame subjected to 3 kN/m wind load as shown in Figure P1.3.

Reinforced Concrete Design 2

BFC 3172

Example 1.3
Solution

Reinforced Concrete Design 2 BFC 3172

Example 1.3
Analysis of horizontal load Roof floor = (1.2 x 3) x (3.5/2) = 6.30 kN rd and 4th Floor 3 = (1.2 x 3) x [(3.5/2) +(3.5/2)] = 12.6 kN 2nd Floor = (1.2 x 3) x [(3.5/2) + (4/2)] = 13.5 kN 1st Floor = (1.2 x 3) x [(4/2) + (4/2)] = 14.4 kN Ground Floor = (1.2 x 3) x (4/2) = 7.2 kN Ratio of axial force in column Axial Force of external column : Axial force of internal column N1 : N2 8 : 2 4P : 1P

Reinforced Concrete Design 2

BFC 3172

Example 1.3 (Roof Floor)

Reinforced Concrete Design 2

Axial Force in column:

Shear force in beam

BFC 3172

Example 1.3 (Roof Floor)


Horizontal Force in Column: MF1 = 0

MF2 = 0

H1 (1.75) 0.65(3) = 0 1.95 H1 = = 1.11kN 1.75

( H1 + H 2 )(1.75) 0.65(8) 0.16(2) = 0 H 2 = 3.15 1.11 = 2.04kN

Reinforced Concrete Design 2

BFC 3172

Example 1.3 (Roof Floor)

Reinforced Concrete Design 2 BFC 3172

Example 1.3 (4th Floor)

Reinforced Concrete Design 2

Axial force in Column:

N1 = 4 P = 3.24kN = N 4 N 2 = P = 0.81kN = N 3

BFC 3172

Example 1.3 (4th Floor)


Shear force in beam Fy = 0 F1 + 0.65 3.24 = 0 F1 = 3.24 0.65 = 2.59kN Fy = 0 F2 + 0.65 + 0.16 3.24 0.81 = 0 F2 = 3.24 + 0.81 0.65 0.16 = 3.24kN

Reinforced Concrete Design 2 BFC 3172

Example 1.3 (4th Floor)


Horizontal force in column MF1 = 0 H1 (1.75) + 1.11(1.75) + 0.65(3) 3.24(3) = 0 H1 = 3.33kN MF2 = 0 ( H1 + H 2 )(1.75) + (1.11 + 2.04)(1.75) (3.24 0.65)(8) (0.81 0.16)(2) = 0
( H1 + H 2 ) = 9.43kN H 2 = 9.43 3.33 = 6.10kN

Reinforced Concrete Design 2

BFC 3172

Example 1.3 (4th Floor)

Reinforced Concrete Design 2 BFC 3172

Example 1.3 (3rd Floor)

Reinforced Concrete Design 2

Axial force in Column: Ms = 0 P(6) P(10) 4P(16) + 6.3(8.75) + 12.6(5.25) + 12.6(1.75) = 0 P = 2.11 kN N1 = 4P = 8.44 kN = N4 N2 = 1P = 2.11 kN = N3

BFC 3172

Example 1.3 (3rd Floor)


Shear force in beam Fy = 0
F1 + 3.24 8.44 = 0 F1 = 8.44 3.24 = 5.20kN

Reinforced Concrete Design 2

Fy = 0 F2 + 3.24 + 0.81 8.44 2.11 = 0 F2 = 8.44 + 2.11 3.24 0.81 = 6.5kN

BFC 3172

Example 1.3 (3rd Floor)


Horizontal force in column MF1 = 0 H1 (1.75) + 3.33(1.75) + 3.24(3) 8.44(3) = 0 H1 = 5.58kN MF2 = 0 ( H1 + H 2 )(1.75) + (3.33 + 6.10)(1.75) (8.44 3.24)(8) (2.11 0.81)(2) = 0
( H1 + H 2 ) = 15.83kN H 2 = 15.83 5.58 = 10.25kN

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Example 1.3 (2nd Floor)

Example 1.3 (3rd Floor)

BFC 3172

Reinforced Concrete Design 2

BFC 3172

Reinforced Concrete Design 2

Example 1.3 (1st Floor)

BFC 3172

Simplified Approach
1.4Gk + 1.6Qk 1.4(25) + 1.6(10) = 51 kN/m

Reinforced Concrete Design 2 BFC 3172

Simplified Approach
1.2Gk + 1.2Qk 1.2(25) + 1.2(10) = 42 kN/m

Reinforced Concrete Design 2

BFC 3172

Result of Portal Analysis at 3rd Floor

Reinforced Concrete Design 2 BFC 3172

Vertical Load + Horizontal Load


1.2Gk + 1.2Qk

Reinforced Concrete Design 2

27.03

31.53 16.07

13.67

13.67 16.07 31.53

27.03

1.2Wk

BFC 3172

Reinforced Concrete Design 2