Contents
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 1.2 Relationships Between SBLs and MOs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 1.3 A1353-RA Alarm Surveillance Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 1.4 LMT Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 1.5 BTS Alarm Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Class 1: CLK Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 2.1 [1,1] OCXO-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 2.2 [1,3] CLOCK-FREQ-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 2.3 [1,6] MCL-FATAL-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 2.4 [1,7] MCL-TEST-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 2.5 [1,8] MCL-DRV-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 2.6 [1,11] MCLU-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 2.7 [1,12] CLOCK-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 2.8 [1,22] MCLR-EA-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 2.9 [1,23] PCM-SYNC-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 2.10 [1,31] MCL-XCLK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 2.11 [1,234] IOM-DISCONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 2.12 [1,237] HW-DEGRADED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 2.13 [1,240] MISSING-ENTRY-IN-CPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 2.14 [1,241] INCONSIST-ASSHW-ACTHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 2.15 [1,246] CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 2.16 [1,247] RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 2.17 [1,248] RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 2.18 [1,250] NO-ANSWER-DCL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 2.19 [1,255] Q1-RELAY-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Class 2: OMU Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 3.1 [2,1] LOSS OF TWIN CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 3.2 [2,247] RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 3.3 [2,248] RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Class 3: SW-AN Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 4.1 [3,0] UNKNOWN-UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 4.2 [3,1] UNKNOWN-CMD-MSG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 4.3 [3,2] UNKNOWN-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 4.4 [3,11] SW-PROBLEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 4.5 [3,13] TELECOM-CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 4.6 [3,14] WRONG-CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 4.7 [3,246] CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Class 4: FHU Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 5.1 [4,1] DUMMY-BURST-GEN-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 5.2 [4,5] FN-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 5.3 [4,6] INTERNAL-FN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 5.4 [4,10] FATAL-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 5.5 [4,14] FCLK-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 5.6 [4,15] INT-FCLK-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 5.7 [4,16] OBCLK-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 5.8 [4,17] INTERNAL-OBCLK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 5.9 [4,240] MISSING-ENTRY-IN-CPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 5.10 [4,246] CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 5.11 [4,247] RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 5.12 [4,250] NO-ANSWER-DCL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
3 / 584
Contents
5.13 Class 5: 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 6.14 6.15 6.16 6.17 6.18 6.19 6.20 Class 6: 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 7.10 7.11 7.12 7.13 7.14 7.15 7.16 7.17 7.18 7.19 7.20 7.21 7.22 7.23 7.24 7.25 7.26 7.27 7.28 7.29 7.30 7.31 7.32 7.33
[4,255] Q1-RELAY-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ENVIR Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,0] POWER-SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,1] FAN-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,2] FAN-ALARM-U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,3] FAN-ALARM-T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,4] BTS-TEMP-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,5] CPLG-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,6] SU-POWER-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,7] TRX-POWER-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,11] POWER-SUPPLY-U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,12] POWER-SUPPLY-NU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,13] CONTROL-UNIT-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,14] MAINS-POWER-SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,15] BATT-DEEP-DISCHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,20] MAINS-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,23] POWER-SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,24] SUBRACK-POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,31] TEMPERATURE-WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,32] FATAL TEMPERATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,237] HW-DEGRADED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [5,239] HW-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RF alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,1] LNK-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,2] LNK-DBLE-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,5] RX-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,6] RX-DBLE-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,7] RX-SYN-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,8] RX-SYN-DBLE-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,9] VSWR-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,10] TX-POWER-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,11] TEMP-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,13] TX-SYN-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,14] FCLK-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,15] INTERNAL-FCLK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,16] OBCLK-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,17] INTERNAL-OBCLK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,18] REF-FREQ-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,19] INTERNAL-REF-FRQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,34] ANTENNA-VSWR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,35] FRONTEND-RELAY-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,36] FRONTEND-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,37] FATAL-FRONTEND-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,38] BCCH-SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,39] BCCH-SWITCH-FATAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,42] RTMA-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,43] PERU-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,45] TEST-ABORTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,46] ALARM-TEST-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,48] RF-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,49] FRONTEND-AMP-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,50] DATA-INCONSIS-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,51] RTC-OUT-OF-BAND-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,52] RTC-FINE-TUNING-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,53] RTC-PARKING-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,54] RTC-SELFTEST-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
149 151 152 158 159 160 161 163 165 167 169 171 173 175 177 179 181 184 186 190 192 198 203 204 207 210 212 214 216 218 221 223 226 228 231 234 236 238 240 243 245 247 249 251 253 255 257 259 261 264 269 271 273 275 277 279
4 / 584
Contents
10
7.34 7.35 7.36 7.37 7.38 7.39 7.40 7.41 7.42 7.43 Class 7: 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 8.14 8.15 8.16 8.17 8.18 8.19 8.20 8.21 Class 8: 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 9.10 9.11 9.12 9.13 9.14 9.15 9.16 Class 9: 10.1 10.2 10.3 10.4 10.5 10.6
[6,55] RTC-EXT-CONN-LOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,56] RTC-DETECTOR-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,240] MISSING-ENTRY-IN-CPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,241] INCONSIST-ASSHW-ACTHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,246] CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,247] RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,250] NO-ANSWER-DCL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,251] SELF-TEST-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,252] SELF-TEST-DBLE-AL (CU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [6,255] Q1-RELAY-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FU Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,1] AL-LIST-ER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,3] MCL-LINK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,5] BSI-LINK-0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,6] BOTH-BSI-LINKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,7] FHI-LK0-FUL-UNV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,8] FHI-LK1-FUL-UNV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,14] FHU-DUMMY-BURST-GEN-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,31] HW-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,32] NR-SW-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,33] NR-SCP-MP-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,34] BOTH-FHI-LINKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,35] BOTH-CLOCKS-LINKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,36] FU-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,240] MISSING-ENTRY-IN-CPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,241] INCONSIST-ASSHW-ACTHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,242] INCONSIST-actHW-logConfig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,243] INCONSIST-actHW-BTSparam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,245] SW-DLL-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,246] CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,248] RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [7,250] NO-ANSWER-DCL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-BTS Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,3] RESYNCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,4] IGNORE EQUIPMENT OVER 12 TRE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,5] TOO MANY PLUGGED MODULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,6] TB-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,7] Q1-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,8] HW-RESYNCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,26] RACH-CATCHER-LOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,30] BCB-LINK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,31] IOM-LINK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,32] MODULE-INSERTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,246] CONFIG-FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,247] RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,248] RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,250] NO-ANSWER-DCL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,251] SELF-TEST-AL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [8,255] Q1-RELAY-FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BTS-EXTERNAL Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [9,1...56] EXT-ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [9,1] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [9,2] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [9,3] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [9,4] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [9,5] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
281 283 285 289 294 298 300 304 306 308 313 314 317 319 321 323 325 327 329 331 332 333 336 339 340 342 346 348 350 352 354 356 359 360 361 362 363 365 367 368 370 373 376 379 382 386 387 390 393 397 398 400 402 404 407 409
5 / 584
Contents
11
10.7 [9,6] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.8 [9,7] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.9 [9,8] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.10 [9,9] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.11 [9,10] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.12 [9,11] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.13 [9,12] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.14 [9,13] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.15 [9,14] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16 [9,15] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.17 [9,16] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.18 [9,17] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.19 [9,18] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.20 [9,19] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.21 [9,20] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.22 [9,21] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.23 [9,22] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.24 [9,23] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.25 [9,24] EXT-ALARM (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.26 [9,25] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.27 [9,26] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.28 [9,27] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.29 [9,28] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.30 [9,29] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.31 [9,30] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.32 [9,31] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.33 [9,32] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.34 [9,33] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.35 [9,34] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.36 [9,35] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.37 [9,36] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.38 [9,37] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.39 [9,38] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.40 [9,39] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.41 [9,40] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.42 [9,41] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.43 [9,42] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.44 [9,43] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.45 [9,44] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.46 [9,45] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.47 [9,46] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.48 [9,47] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.49 [9,48] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.50 [9,49] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.51 [9,50] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.52 [9,51] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.53 [9,52] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.54 [9,53] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.55 [9,54] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.56 [9,55] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.57 [9,56] EXT-ALARM for A9110-E (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class 10: RX-TX Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.1 [10,1] RSL-LINK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.2 [10,3] RX-CABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.3 [10,10] TRE-VSWR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.4 [10,11] ANTENNA-VSWR-WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.5 [10,12] ANTENNA-VSWR-URGENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
411 413 415 417 419 421 423 425 427 429 431 433 435 437 439 441 443 445 447 449 449 450 450 451 451 452 452 453 453 454 454 455 455 456 456 457 457 458 458 459 459 460 460 461 461 462 462 463 463 464 464 465 466 469 473 476 480
6 / 584
Contents
12
13
11.6 [10,21] MODULE-FRAME-SIGNAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.7 [10,22] MODULE-CLOCK-SIGNAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.8 [10,51] MODULE-NOT-PRESENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.9 [10,234] IOM-DISCONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.10 [10,237] HW-DEGRADED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.11 [10,239] HW-FAILURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.12 [10,248] RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.13 [10,248] RESTART (RA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class 11: BTS-TRANS Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.1 [11,22] LOOP-TO-EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.2 [11,50] LOSS-OF-INCOMING-SIGNAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.3 [11,66] AIS-2M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.4 [11,81] LOSS-OF-FRAME-ALIGNMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.5 [11,86] LOSS-OF-CRC-MULTIFRAME-ALIGNMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.6 [11,99] ERROR-RATE >E-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.7 [11,100] ERROR-RATE >E-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.8 [11,102] ERROR-RATE >E-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.9 [11,176] REMOTE-ALARM-INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BTS Alarm Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.1 BTS Alarms with Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.2 TLV Coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
484 489 494 499 504 511 522 525 527 528 531 534 536 539 542 545 548 551 553 554 556
7 / 584
Figures
Figures
Figure 1: Graphical workflow for corrective actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Figure 2: OCXO-AL: G1/G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Figure 3: CLOCK-FREQ-AL: G1/G2 BTS, Alarm Number 1, 3 & 4, Corrective Actions at OMC-R . . . . . . . . 35 Figure 4: CLOCK-FREQ-AL: G1/G2 BTS, Alarm Number 1, 3 & 4, Corrective Actions On-Site . . . . . . . . . . 36 Figure 5: CLOCK-FREQ-AL: G2 BTS, Alarm Number 2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Figure 6: MCL-FATAL-AL: G1/G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Figure 7: MCL-FATAL-AL: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Figure 8: MCL-FATAL-AL: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Figure 9: MCL-TEST-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Figure 10: MCL-DRV-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Figure 11: MCLU-FAULT: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 12: CLOCK-FAULT: G1/G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 13: CLOCK-FAULT: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Figure 14: CLOCK-FAULT: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Figure 15: MCL-EA-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 16: PCM-SYNC-AL: G1/G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Figure 17: MCL-XCLK: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Figure 18: MCL-XCLK: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Figure 19: HW-DEGRADED: BTS A9100, Alarm Number 1 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . 61 Figure 20: HW-DEGRADED: BTSA9100, Alarm Number 2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . 62 Figure 21: HW-DEGRADED: BTS A9110/A9110-E , Alarm Number 1 Corrective Actions . . . . . . . . . . . . . . . 63 Figure 22: HW-DEGRADED: BTS A9110/A9110-E ,Alarm Number 2 Corrective Actions . . . . . . . . . . . . . . . 64 Figure 23: MISSING-ENTRY-IN-CPF: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Figure 24: INCONSIST-ASSHW-ACTHW, Alarm Number 3: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 68 Figure 25: INCONSIST-ASSHW-ACTHW, Alarm Number 5: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 69 Figure 26: CONFIG-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Figure 27: RESET: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Figure 28: RESET: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Figure 29: RESTART: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Figure 30: RESTART: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Figure 31: NO-ANSWER-DCL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Figure 32: Q1-RELAY-FAILURE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Figure 33: LOSS OF TWIN CONFIGURATION Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Figure 34: RESET: Alarm Number 1,2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Figure 35: RESET: Alarm Number 3 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Figure 36: RESET: Alarm Number 4 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Figure 37: RESET: Alarm Number 5 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Figure 38: RESET: Alarm Number 6 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Figure 39: RESET: Alarm Number 7 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
8 / 584
Figures
Figure 40: UNKNOWN-UNIT: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Figure 41: UNKNOWN-CMD-MSG: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Figure 42: UNKNOWN-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Figure 43: SW-PROBLEM (CLLK): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Figure 44: SW-PROBLEM (CLLK): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Figure 45: SW-PROBLEM (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Figure 46: SW-PROBLEM (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Figure 47: SW-PROBLEM (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Figure 48: TELECOM-CONFIG-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Figure 49: WRONG-CONFIGURATION (TRE): Alarm Number 1, 2, 3, 6, Corrective Actions . . . . . . . . . . . 106 Figure 50: WRONG-CONFIGURATION (TRE): Alarm Number 4, Corrective Actions . . . . . . . . . . . . . . . . . . 107 Figure 51: WRONG-CONFIGURATION (TRE): Alarm Number 5, Corrective Actions . . . . . . . . . . . . . . . . . . 108 Figure 52: WRONG-CONFIGURATION (TRE): Alarm Number 7, 9, Corrective Actions . . . . . . . . . . . . . . . . 109 Figure 53: WRONG-CONFIGURATION (TRE): Alarm Number 8, Corrective Actions . . . . . . . . . . . . . . . . . . 110 Figure 54: WRONG-CONFIGURATION (BTS): Alarm Number 11, Corrective Actions . . . . . . . . . . . . . . . . . 111 Figure 55: WRONG-CONFIGURATION (RA): Alarm Number 2, 7, 10, Corrective Actions . . . . . . . . . . . . . 113 Figure 56: WRONG-CONFIGURATION (RA): Alarm Number 4, Corrective Actions . . . . . . . . . . . . . . . . . . . 114 Figure 57: WRONG-CONFIGURATION (BTS): Alarm Number 12, 14, Corrective Actions . . . . . . . . . . . . . 116 Figure 58: WRONG-CONFIGURATION (BTS): Alarm Number 13, Corrective Actions . . . . . . . . . . . . . . . . . 117 Figure 59: CONFIG-FAIL (CLLK): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 Figure 60: CONFIG-FAIL (CLLK): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . 120 Figure 61: CONFIG-FAIL (RA): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Figure 62: CONFIG-FAIL (RA): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Figure 63: CONFIG-FAIL (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Figure 64: CONFIG-FAIL (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 Figure 65: DUMMY-BURST-GEN-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Figure 66: FN-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Figure 67: INTERNAL-FN: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Figure 68: FATAL-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134 Figure 69: FCLK-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 Figure 70: INT-FCLK-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Figure 71: OBCLK-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Figure 72: INTERNAL-OBCLK: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Figure 73: MISSING-ENTRY-IN-CPF: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Figure 74: CONFIG-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Figure 75: RESET: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 Figure 76: NO-ANSWER-DCL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 Figure 77: Q1-RELAY-FAILURE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 Figure 78: POWER-SUPPLY (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153 Figure 79: POWER-SUPPLY (FU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
9 / 584
Figures
Figure 80: POWER-SUPPLY (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157 Figure 81: FAN-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 Figure 82: FAN-ALARM-U: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 Figure 83: FAN-ALARM-T: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 Figure 84: BTS-TEMP-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162 Figure 85: CPLG-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 Figure 86: SU-POWER-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166 Figure 87: TRX-POWER-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Figure 88: POWER-SUPPLY-U: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170 Figure 89: POWER-SUPPLY-NU: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 Figure 90: CONTROL-UNIT-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174 Figure 91: MAINS-POWER-SUPPLY: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176 Figure 92: BATT-DEEP-DISCHARGE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178 Figure 93: MAINS-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 Figure 94: POWER-SHUTDOWN: Alarm Number 1 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182 Figure 95: POWER-SHUTDOWN: Alarm Number 2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 Figure 96: SUBRACK-POWER: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185 Figure 97: TEMPERATURE-WARNING (BTS): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187 Figure 98: TEMPERATURE-WARNING (TRE): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 Figure 99: FATAL TEMPERATURE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 Figure 100: HW-DEGRADED (BTS): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 Figure 101: HW-DEGRADED (EACB): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Figure 102: HW-DEGRADED (EACB): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 196 Figure 103: HW-DEGRADED (CCF): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 Figure 104: HW-FAILURE (EACB): Alarm Number 2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Figure 105: HW-FAILURE (EACB): Alarm Number 3 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 Figure 106: HW-FAILURE (CCF): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 Figure 107: LNK-AL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 Figure 108: LNK-AL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206 Figure 109: LNK-DBLE-AL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 Figure 110: LNK-DBLE-AL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209 Figure 111: RX-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211 Figure 112: RX-DBLE-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213 Figure 113: RX-SYN-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215 Figure 114: RX-SYN-DBLE-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217 Figure 115: VSWR-AL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 Figure 116: VSWR-AL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 Figure 117: TX-POWER-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222 Figure 118: TEMP-AL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224 Figure 119: TEMP-AL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
10 / 584
Figures
Figure 120: TX-SYN-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227 Figure 121: FCLK-AL (CU): G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229 Figure 122: FCLK-AL (CU): G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 Figure 123: INTERNAL-FCLK (CU): G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232 Figure 124: INTERNAL-FCLK (CU): G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 Figure 125: OBCLK-AL (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 Figure 126: INTERNAL-OBCLK (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237 Figure 127: REF-FREQ-AL (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 Figure 128: INTERNAL-REF-FRQ (CU): G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Figure 129: INTERNAL-REF-FRQ (CU): G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242 Figure 130: ANTENNA-VSWR: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 Figure 131: FRONTEND-RELAY-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246 Figure 132: FRONTEND-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248 Figure 133: FATAL-FRONTEND-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 Figure 134: BCCH-SWITCH: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252 Figure 135: BCCH-SWITCH-FATAL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254 Figure 136: RTMA-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256 Figure 137: PERU-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258 Figure 138: TEST-ABORTED: G1/G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260 Figure 139: ALARM-TEST-FAILURE: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 Figure 140: ALARM-TEST-FAILURE: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263 Figure 141: RF-FAULT (CU): G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 Figure 142: RF-FAULT (CU): G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266 Figure 143: RF-FAULT (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 Figure 144: FRONTEND-AMP-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 Figure 145: DATA-INCONSIS-AL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272 Figure 146: RTC-OUT-OF-BAND-ALARM: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274 Figure 147: RTC-FINE-TUNING-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Figure 148: RTC-PARKING-FAILURE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278 Figure 149: RTC-SELFTEST-FAILURE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280 Figure 150: RTC-EXT-CONN-LOST: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282 Figure 151: RTC-DETECTOR-FAILURE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284 Figure 152: MISSING-ENTRY-IN-CPF: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286 Figure 153: MISSING-ENTRY-IN-CPF: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288 Figure 154: INCONSIST-ASSHW-ACTHW: Alarm Number 2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 290 Figure 155: INCONSIST-ASSHW-ACTHW: Alarm Number 4 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 291 Figure 156: INCONSIST-ASSHW-ACTHW: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293 Figure 157: CONFIG-FAIL (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295 Figure 158: CONFIG-FAIL (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297 Figure 159: RESET (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
11 / 584
Figures
Figure 160: NO-ANSWER-DCL (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301 Figure 161: NO-ANSWER-DCL (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 Figure 162: SELF-TEST-AL (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305 Figure 163: SELF-TEST-DBLE-AL (CU): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307 Figure 164: Q1-RELAY-FAULT (CU): G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309 Figure 165: Q1-RELAY-FAULT (CU): G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Figure 166: Q1-RELAY-FAULT (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312 Figure 167: AL-LIST-ER: DRFU Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 Figure 168: AL-LIST-ER: OMU Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 Figure 169: MCL-LINK: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318 Figure 170: BSI-LINK-0: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 Figure 171: BOTH-BSI-LINKS: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322 Figure 172: FHI-LK0-FUL-UNV: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324 Figure 173: FHI-LK1-FUL-UNV: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326 Figure 174: FHU-DUMMY-BURST-GEN-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328 Figure 175: HW-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330 Figure 176: BOTH-FHI-LINKS: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334 Figure 177: BOTH-FHI-LINKS: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335 Figure 178: BOTH-CLOCK-LINKS: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337 Figure 179: BOTH-CLOCK-LINKS: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338 Figure 180: FU-FAULT: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339 Figure 181: MISSING-ENTRY-IN-CPF: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341 Figure 182: INCONSIST-ASSHW-ACTHW: Alarm Number 1 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 343 Figure 183: INCONSIST-ASSHW-ACTHW: Alarm Number 8 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 344 Figure 184: INCONSIST-ASSHW-ACTHW: Alarm Number 9 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 345 Figure 185: INCONSIST-actHW-logConfig: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347 Figure 186: INCONSIST-actHW-BTSparam: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349 Figure 187: SW-DLL-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 351 Figure 188: CONFIG-FAIL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 Figure 189: RESTART: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 Figure 190: NO-ANSWER-DCL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 Figure 191: IGNORE EQUIPMENT OVER 12 TRE: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361 Figure 192: TOO MANY PLUGGED MODULES: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 362 Figure 193: TB-FAILURE: G1/G2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 Figure 194: Q1-FAILURE: G1/G2 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366 Figure 195: RACH-CATCHER-LOST: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 Figure 196: BCB-LINK: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 Figure 197: BCB-LINK: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 Figure 198: IOM-LINK: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 Figure 199: IOM-LINK: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375
12 / 584
Figures
Figure 200: MODULE-INSERTED: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377 Figure 201: MODULE-INSERTED: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . 378 Figure 202: CONFIG-FAIL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380 Figure 203: CONFIG-FAIL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 Figure 204: RESET (EACB): G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384 Figure 205: RESET (EACB): G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 Figure 206: NO-ANSWER-DCL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 Figure 207: NO-ANSWER-DCL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 Figure 208: SELF-TEST-AL: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391 Figure 209: SELF-TEST-AL: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392 Figure 210: Q1-RELAY-FAULT: G1 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394 Figure 211: Q1-RELAY-FAULT: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395 Figure 212: EXT-ALARM [9,1...56] : Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399 Figure 213: [9,1] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . 401 Figure 214: [9,2] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403 Figure 215: [9,3] EXT-ALARM: BTS G2 and A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 405 Figure 216: [9,3] EXT-ALARM: BTS A9110/A9110-E Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 406 Figure 217: [9,4] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408 Figure 218: [9,5] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . 410 Figure 219: [9,6] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . 412 Figure 220: [9,7] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . 414 Figure 221: [9,8] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . 416 Figure 222: [9,9] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 418 Figure 223: [9,10] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420 Figure 224: [9,11] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422 Figure 225: [9,12] EXT-ALARM: G2 BTS Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424 Figure 226: [9,13] EXT-ALARM: BTS G2 and A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . 426 Figure 227: [9,14] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . 428 Figure 228: [9,15] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . 430 Figure 229: [9,16] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . 432 Figure 230: [9,17] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434 Figure 231: [9,18] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436 Figure 232: [9,19] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438 Figure 233: [9,20] EXT-ALARM: BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440 Figure 234: [9,21] EXT-ALARM: BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442 Figure 235: [9,22] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444 Figure 236: [9,23] EXT-ALARM: Default Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446 Figure 237: [9,24] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions . . . . . . . . . . . . . . . . . 448 Figure 238: RSL-LINK: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 467 Figure 239: RSL-LINK: G2 BTS Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
13 / 584
Figures
Figure 240: RX-CABLE (TRE):Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470 Figure 241: RX-CABLE (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472 Figure 242: TRE-VSWR: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474 Figure 243: TRE-VSWR: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475 Figure 244: ANTENNA-VSWR-WARNING: Corrective Actions for A9100 BTS . . . . . . . . . . . . . . . . . . . . . . . . 478 Figure 245: ANTENNA-VSWR-WARNING: Corrective Actions for A9110-E BTS . . . . . . . . . . . . . . . . . . . . . . 479 Figure 246: ANTENNA-VSWR-URGENT: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481 Figure 247: ANTENNA-VSWR-URGENT: Corrective Actions, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 482 Figure 248: ANTENNA-VSWR-URGENT: Corrective Actions, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 483 Figure 249: MODULE-FRAME-SIGNAL (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 485 Figure 250: MODULE-FRAME-SIGNAL (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . 486 Figure 251: MODULE-FRAME-SIGNAL (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 488 Figure 252: MODULE-CLOCK-SIGNAL (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 490 Figure 253: MODULE-CLOCK-SIGNAL (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . 491 Figure 254: MODULE-CLOCK-SIGNAL: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493 Figure 255: MODULE-NOT-PRESENT (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . 495 Figure 256: MODULE-NOT-PRESENT (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . 496 Figure 257: MODULE-NOT-PRESENT (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 498 Figure 258: IOM-DISCONNECTION (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . 500 Figure 259: IOM-DISCONNECTION (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . 501 Figure 260: IOM-DISCONNECTION (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 503 Figure 261: HW-DEGRADED (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505 Figure 262: HW-DEGRADED (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 506 Figure 263: HW-DEGRADED (RA): BTS A9100, Alarm Number 3 Corrective Actions . . . . . . . . . . . . . . . . . 508 Figure 264: HW-DEGRADED (RA): BTS A9100, Alarm Number 4...11 Corrective Actions . . . . . . . . . . . . 509 Figure 265: HW-DEGRADED (RA): BTS A9100, Alarm Number 3 Corrective Actions . . . . . . . . . . . . . . . . . 510 Figure 266: HW-FAILURE (TRE): BTS A9100, Alarm Number 1, 12 and 13 Corrective Actions . . . . . . . . 513 Figure 267: HW-FAILURE (TRE): BTS A9100, Alarm Number 1, 3...11 and 15 Corrective Actions . . . . . . 514 Figure 268: HW-FAILURE (TRE): BTS A9100, Alarm Number 14 Corrective Actions . . . . . . . . . . . . . . . . . . 515 Figure 269: HW-FAILURE (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . 516 Figure 270: HW-FAILURE (RA): BTS A9100, Alarm Number 2 and 12 Corrective Actions . . . . . . . . . . . . . 518 Figure 271: HW-FAILURE (RA): BTS A9100, Alarm Number 10 Corrective Actions . . . . . . . . . . . . . . . . . . . 519 Figure 272: HW-FAILURE (RA): BTS A9100, Alarm Number 14 Corrective Actions . . . . . . . . . . . . . . . . . . . 520 Figure 273: HW-FAILURE (RA): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 Figure 274: RESTART (TRE): BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523 Figure 275: RESTART (TRE): BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524 Figure 276: RESTART (RA): Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526 Figure 277: LOOP-TO-EQUIPMENT: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529 Figure 278: LOOP-TO-EQUIPMENT: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . 530 Figure 279: LOSS-OF-INCOMING-SIGNAL: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . 532
14 / 584
Figures
Figure 280: LOSS-OF-INCOMING-SIGNAL: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . 533 Figure 281: AIS-2M: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535 Figure 282: LOSS-OF-FRAME-ALIGNMENT: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . 537 Figure 283: LOSS-OF-FRAME-ALIGNMENT: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . 538 Figure 284: LOSS-OF-CRC-MULTIFRAME-ALIGNMENT: BTS A9100 Corrective Actions . . . . . . . . . . . . . 540 Figure 285: LOSS-OF-CRC-MULTIFRAME-ALIGNMENT: BTS A9110/A9110-E Corrective Actions . . . . 541 Figure 286: ERROR-RATE>E-3: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543 Figure 287: ERROR-RATE>E-3: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544 Figure 288: ERROR-RATE>E-4: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 546 Figure 289: ERROR-RATE>E-4: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547 Figure 290: ERROR-RATE>E-6: BTS A9100 Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 549 Figure 291: ERROR-RATE>E-6: BTS A9110/A9110-E Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 550 Figure 292: REMOTE-ALARM-INDICATION: Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552 Figure 293: G1, Mark I, TLV53 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561 Figure 294: G1, Mark II, TLV53 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561 Figure 295: G2, FU2, TLV53 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 562 Figure 296: G1, FU3, TLV53 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 562 Figure 297: G1, Mark I TLV59 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 570
15 / 584
Tables
Tables
Table 1: SBL state to MO state translation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Table 2: OMC-R to LMT state change commands translation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Table 3: Event Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Table 4: Alarm Severity Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Table 5: Alarm [2,247] TLV Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554 Table 6: Alarm [2,248] TLV Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554 Table 7: Alarms [7,3], [7,5] to [7,8] and [7,31] to [7,35] TLV Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 555 Table 8: Alarm [7,245] TLV Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 555 Table 9: Alarm [7,248] TLV Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 555 Table 10: NACK Types for TLV35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 556 Table 11: Error Numbers for TLV35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559 Table 12: Field Definitions for Fourth and Fifth Bytes of TLV53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 563 Table 13: FU Alarms and Alarm Type for TLV53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565 Table 14: Bit value description (6th and 7th byte) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565 Table 15: 8th byte description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 566 Table 16: TLV57 Coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 567 Table 17: TLV57 Error Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 567 Table 18: TLV58 Coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568 Table 19: TLV58 Software Identity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568 Table 20: TLV58 Board Identity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 569 Table 21: TLV58 DSP Identity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 569 Table 22: TLV59 FU Alarm Type 20 Alarms for G1/G2 and Micro-BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571 Table 23: TLV59 for TRE faults of Evolium BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 573 Table 24: TLV59 for AN faults of Evolium BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 574 Table 25: TLV59 for TRANS&CLOCK faults of Evolium A9100 BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 575 Table 26: TLV61 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576 Table 27: TLV61 Board Identification Bytes for G1/G2 and Micro-BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 577 Table 28: TLV61 Board Identification Bytes for Evolium BTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 577 Table 29: TLV82 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 579 Table 30: TLV83 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 581 Table 31: TLV84 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 581 Table 32: TLV120 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582 Table 33: TLV243 Bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 583
16 / 584
Preface
Preface
Purpose
The purpose of the alarm dictionary is to provide the operator with a structured method for handling alarm messages generated by the BTS. This document contains a list of all BTS alarms, and the actions required to remove them. Alarms are displayed at the OMC-R terminal and at the LMT to inform the operator of system faults.
When a fault occurs, a number of alarms can be generated simultaneously. These alarms must be analyzed as a group to determine the precise fault.
In Edition 10
Corrective action for alarm [10,239] HW-FAILURE (Section 11.11) number 1, 12 and 13 was updated.
In Edition 09
Alarm name was corrected for [8,5] TOO MANY PLUGGED MODULES (Section 9.3).
In Edition 08
The following alarms were added: [2,1] LOSS OF TWIN CONFIGURATION (Section 3.1) [8,4] IGNORE EQUIPMENT OVER 12 TRE (Section 9.2) [8,5] TOO MANY PLUGGED MODULES (Section 9.3).
In Edition 07
Description improvement for the alarms: [5,11] POWER-SUPPLY-U (Section 6.9) [5,12] POWER-SUPPLY-NU (Section 6.10) [5,20] MAINS-AL (Section 6.14).
In Edition 06
Description improvement for alarm [10,248] RESTART (Section 11.12)
17 / 584
Preface
In Edition 05
Description improvement for alarm [10,11] ANTENNA-VSWR-WARNING (Section 11.4).
In Edition 04
Description improvement for alarm [5,1] FAN-ALARM (Section 6.2).
In Edition 03
Description improvement for alarm [3,14] WRONG-CONFIGURATION (RA) (Section 4.6.2).
In Edition 02
Description improvement for alarm [10,1] RSL-LINK (Section 11.1).
In Edition 01
Creation in B9.
This document is aimed at telecommunications operators responsible for performing O&M fault handling and troubleshooting tasks. The operator must be familiar with the following: Alcatel O&M concepts for the BSS Fault management Use of OMC-R and BTS terminals SBL hierarchies of the BTS Telecommunications techniques including line transmission and switching.
18 / 584
1 Introduction
1 Introduction
This section describes the structure of the BTS alarm messages.
19 / 584
1 Introduction
1.1 Overview
This alarm dictionary provides additional information that is not displayed in the alarm messages sent to the OMC-R, BSC or TSS terminals. The dictionary contains alarm definitions for each alarm type produced by the BSS. Each definition describes the: Alarm description Impact on System Methods for further fault isolation Corrective actions. The descriptions of the alarms in this document is MO based for OMC -R terminal purpose. For BTS LMT purpose, the SBL related information is added in brackets if applicable.
20 / 584
1 Introduction
Table 2: OMC-R to LMT state change commands translation See document A1353-RA Surveillance Handbook for use of the OMC-R commands, see document BTS Terminal User Guide for the use of the BTS LMT commands.
21 / 584
1 Introduction
22 / 584
1 Introduction
Indicates... a serious fault condition which requires immediate corrections. Example: a managed object goes out of service. a fault condition which requires urgent correction action. Example: severe degradation in the operation of a managed object. a fault condition which does not affect service but corrective action should be taken to avoid a more serious fault. detection of a potential fault condition. Action should be taken to diagnose and correct the problem to avoid a more serious fault condition. the severity level cannot be defined by the resource which raised the alarm. the alarm was cleared by the resource which raised the alarm.
Major
Minor
Warning
In addition the Object Identification and Alarm Type information, all alarms always give the date and time of the alarm. An alarm may also contain optional information, such as the notification id. Refer to the AS on-line help for more detailed information on AS.
23 / 584
1 Introduction
1.4.1.3 Classification
The characteristics of the alarm, consisting of: Alarm Class name and number - as shown in the Alarm Dictionary Alarm Type name and number - as shown in the Alarm Dictionary Alarm Number - dependent on the Alarm Class and Type. See the appropriate dictionary entry for the valid alarm numbers for a particular alarm Alarm Condition - has one of the following values: begin - alarm on. For fatal failures, the affected SBL changes state to FLT or FOS. For non-fatal failures, the affected SBL changes state to FIT end - alarm off. Indicates the successful recovery of the system. The affected SBL may not change state if other alarms related to the SBL are on event - occurrence of anomaly. No action is required unless it occurs frequently. Event alarms are of short duration and the affected SBL does not change state. The system retry/recovery mechanism has cleared the fault.
1.4.1.4 Location
The origin of the alarm, consisting of: Unit type Unit number SBL type SBL number and subnumber, if appropriate.
24 / 584
1 Introduction
25 / 584
1 Introduction
26 / 584
1 Introduction
1.5.1.2 eventType
The eventType attribute identifies the basic type of the alarm. It provides a list of standard types: Communication: associated with the procedures and/or processes required to convey information from one point to another. Quality of Service: associated with a degradation of the quality of service. Processing Error: associated with a software or processing fault. Equipment: associated with an equipment fault. Environmental: associated with a condition relating to an enclosure in which the equipment resides.
27 / 584
1 Introduction
Warning: indicates a potential or impending fault, before any significant effect have been felt. Action(s) should be taken to further diagnose (if necessary) and correct the problem in order to prevent it from becoming a more serious service affecting fault. Indeterminate: indicates that the severity level cannot be defined by the resource raising the alarm. Cleared: indicates the clearing of one or more previously alarms for this managed object with the same Alarm type, Probable Cause and Specific problems (if given).
28 / 584
1 Introduction
[1,1] OCXOAL
Clock operational?
yes
Alarm solved
no
Onsite
Onsite
Onsite
OR
OR
Clock operational?
yes
Alarm solved
End fields
Figure 1: Graphical workflow for corrective actions This figure shows an example of a graphical workflow and describes the different flowchart fields. Useful hints for safety and required tools are added as appropriate.
29 / 584
1 Introduction
30 / 584
31 / 584
If the CLLK is redundant on this BTS, the telecom functions are not affected. If, however, no redundancy is available, the cell(s) fed by the reporting CLLK are lost. (X) Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
32 / 584
Clock operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite OR
G2: Replace STSE, STSP, STSR
OR
Clock operational?
yes
Alarm solved
33 / 584
Alarm Number
If the CLLK is redundant on this BTS, the telecom functions are not affected. If, however, no redundancy is available, the clock system is not reliable. Thus the telecom functions on the cell(s) fed by the indicated MFG can be affected. Degradation in transmission quality can arise on these cell(s), e.g., BER increasing, interference and handover problems. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.)
Required tools and materials: Thermometer Replacement tools, see appropriate replacement procedure.
34 / 584
Clock operational?
yes
Alarm solved
no
yes
no
Replace modules
Figure 3: CLOCK-FREQ-AL: G1/G2 BTS, Alarm Number 1, 3 & 4, Corrective Actions at OMC-R
35 / 584
Replace modules
Onsite
Check BTS status (logical configurations)
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
Clock operational?
yes
Alarm solved
Figure 4: CLOCK-FREQ-AL: G1/G2 BTS, Alarm Number 1, 3 & 4, Corrective Actions On-Site
36 / 584
no
Clock operational?
yes
Alarm solved
no
yes
Onsite
Check ambient temperature
Onsite
Ambient temperature outside permitted limits? yes Reduce ambient temperature
Recheck alarm
no yes
Alarm solved
Clock operational?
37 / 584
If the CLLK is redundant on this BTS, the telecom functions are not affected. If no redundancy is available however, the cell(s) fed by the reporting CLLK are lost. BTS A9100: There is no clock redundancy available, so the cells fed by the reporting CLLK are lost, thus the BTS is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
38 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Check BTS status (logical configuration)
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
Clock operational?
yes
Alarm solved
39 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Replace SUMP, SUMA
Clock operational?
yes
Alarm solved
40 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
41 / 584
If the CLLK is redundant on this BTS the telecom functions are not affected. If, however, no redundancy is available, the cell(s) fed by the reporting CLLK are lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
42 / 584
Clock operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite OR
G2: Replace STSE, STSP, STSR
OR
Clock operational?
yes
Alarm solved
43 / 584
If the CLLK is redundant on this BTS the telecom functions are not affected. If, however, no redundancy is available, the cell(s) fed by the reporting CLLK are lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
44 / 584
Clock operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite OR
G2: Replace STSE, STSP, STSR
OR
Clock operational?
yes
Alarm solved
45 / 584
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
46 / 584
Lock Function RA
Unlock Function RA
yes
no
RA operational?
yes
Alarm solved
no
Onsite Onsite
Onsite
Onsite
If not all possible TREs are equipped, check for missing dummy load on ANY.
Onsite
RA operational?
yes
Alarm solved
47 / 584
If the clock system is redundant on this BTS, the telecom functions are not affected. If, however, no redundancy is available, the channels supported by the CLLK/CLDB are lost. BTS A9100: There is no clock redundancy available, so the cells fed by the reporting CLLK are lost, thus the BTS is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
48 / 584
Onsite
Clock operational? no Check cables amd connectors to cabinet
Onsite
Check CLDBs of cabinet
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
Clock operational?
yes
Alarm solved
49 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Replace SUMP, SUMA
Clock operational?
yes
Alarm solved
50 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
51 / 584
If the CLLK is redundant on this BTS the telecom functions are not affected. If, however, no redundancy is available, the cell(s) fed by the reporting CLLK are lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
52 / 584
yes
no
Clock operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
Clock operational?
yes
Alarm solved
53 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
54 / 584
no
yes Solve that alarm(s) first PCM Clock operational? yes Alarm solved
no
Onsite
G1:Check cables/connectors transmission system to MFGP
Onsite
G2: Check cables/connectors transmission system to STSP
OR
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
yes
Alarm solved
55 / 584
If the CLLK is redundant on this BTS the telecom functions are not affected. If, however, no redundancy is available, the cell(s) fed by the reporting CLLK are lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
56 / 584
no
Clock operational?
no Onsite Check cables/connectors between clock unit on master BTS and reporting clock unit
Onsite
Replace SUMP, SUMA
Clock operational?
yes
Alarm solved
57 / 584
no
Onsite
Reset Function BTS Disconnect mains power from ACCO to Basic Unit
Onsite
yes Solve that alarm(s) first Clock operational? no Check cables/connectors between clock unit on master BTS and reporting clock unit
OR Onsite
Switch off Battery Backup Switch and Main Power switch in Side Support Cabinet
OR Onsite
Switch off mains power fuse for tower mounted BTS
Onsite
After 30 s repower the BTS
Onsite
Replace BTS A910 no BTS operational?
58 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
59 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Required tools and materials: PCM test tools GPS test tools Replacement tools, see appropriate replacement procedure.
60 / 584
no
yes
Onsite
no Check BTS status (logical configurations)
Clock operational?
yes
Alarm solved
no
Onsite
After 30 s switch BTS on
Onsite
Onsite
Clock operational? yes no Replace SUMP, SUMA
Alarm solved
Clock operational?
yes
Alarm solved
61 / 584
Onsite
no Check BTS status (logical configurations)
Clock operational?
Clock operational?
yes
Alarm solved
no
Onsite
After 30 s switch BTS on
Onsite
Onsite
Clock operational? yes no Replace SUMP, SUMA
Alarm solved
Clock operational?
yes
Alarm solved
62 / 584
no
Onsite
Reset Function BTS Disconnect mains power from ACCO to Basic Unit
Onsite
yes Solve that alarm(s) first no Check logical configuration & PCM clock input
OR Onsite
Switch off Battery Backup Switch and Main Power switch in Side Support Cabinet
Clock operational?
OR Onsite
Switch off mains power fuse for tower mounted BTS
Onsite
After 30 s repower the BTS
Onsite
Replace BTS A910 no BTS operational?
63 / 584
Onsite
Reset Function BTS Disconnect mains power from ACCO to Basic Unit
Onsite
OR Onsite
Switch off Battery Backup Switch and Main Power switch in Side Support Cabinet
Clock operational?
no
OR Onsite
Switch off mains power fuse for tower mounted BTS
Onsite
After 30 s repower the BTS
Onsite
Replace BTS A910 no BTS operational?
64 / 584
If the BTS clock system has redundancy, telecom functions are not affected. If there is no redundancy, the cell is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
65 / 584
Check existing hardware against populated hardware in the OMU CPF for wrong BTS family, characteristic and parameter entries. Use:
Choose the correct CPF settings by selecting the appropriate BTS characteristics. Use:
Clock operational?
yes
Alarm solved
66 / 584
Alarm Number
If the BTS clock system has redundancy, telecom functions are not affected. If there is no redundancy, the cell is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
67 / 584
[1,241] INCONSISTASSHWACTHW
Check assumed BTS hardware master/slave capability against the clock units in the BTS. Use:
Onsite Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity, as descibed in the CMA
OR
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite OR
G2: Replace STSE, STSP, STSR
OR
Clock operational?
yes
Alarm solved
68 / 584
[1,241] INCONSISTASSHWACTHW
Onsite
OR
Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity, as descibed in the CMA
Onsite
G2: Replace STSE, STSP, STSR
Clock operational?
yes
Alarm solved
69 / 584
If the clock system is redundant on this BTS and only one Clock Unit configuration failed, the telecom functions are not affected. If, however, no redundancy is available or the configuration of both Clock Units on the BTS failed, the cell(s) fed by the clock system are lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
70 / 584
If both Clock Units in BTS report this alarm, there is a problem with the parameters (List of Clock Unit delays). If alarm is reported at powerup, there is also a Q1 failure, which provoked the configuration failure.
Check validity of parameters (BTS hardware configuration) on Clock Unit delays. Use Check Cell with Hardware
Restart OMU
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
Clock operational?
yes
Alarm solved
71 / 584
If the clock system is redundant on this BTS the telecom functions are not affected. If, however, no redundancy is available, the call(s) on that BTS are lost due to the lack of clock signals and are not resumed later. Signaling is resumed as soon as the Clock Unit is available again. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
72 / 584
Clock operational?
yes
no
no
Alarm solved
yes
Onsite
Replace SUMP, SUMA
Clock operational?
yes
Alarm solved
73 / 584
Clock operational?
yes
no
Alarm solved
no
yes
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
Clock operational? no Replace BTS A910 BTS operational? yes Alarm solved
74 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
75 / 584
Clock operational?
yes
no
no
Alarm solved
yes
Onsite
Replace SUMP, SUMA
Clock operational?
yes
Alarm solved
76 / 584
Clock operational?
yes
no
Alarm solved
no
yes
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
Clock operational? no Replace BTS A910 BTS operational? yes Alarm solved
77 / 584
Major (PMA): If the clock system is redundant on this BTS, the telecom functions are not affected. If, however, no redundancy is available, the cell will be lost because no configuration can be set. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
Minor (DMA): In case of Q1 malfunction there is no disturbance of the telecom applications. In case of clock malfunction and the clock system is redundant on this BTS, there is no disturbance of the telecom application. If, however, no redundancy is available, the result depends on the clock fault, the clocks can eventually go on with the previous configuration. If the fault is fatal, others alarms will appear on other equipment (ex FU on Token bus). Impact Loss Degradation BSS X Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
78 / 584
Onsite
no Check Q1 bus cable and connectors between OMU and Clock Unit
Clock operational?
yes
Alarm solved
Clock operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite
G2: Replace STSE, STSP, STSR
OR
OR
Clock operational?
yes
Alarm solved
79 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
80 / 584
Clock operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite OR
G2: Replace STSE, STSP, STSR
OR
Clock operational?
yes
Alarm solved
81 / 584
82 / 584
83 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Alarm solved
84 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
85 / 584
Poweron reset?
yes
no
Alarm solved
no
Onsite
OMU operational?
yes
Alarm solved
86 / 584
Onsite
G1: Replace OMUA
Onsite
G2: Replace SCFE
Onsite OR
A9100: Replace SUMP, SUMA
Onsite
A910: Replace BTS A910
OR
OR
OMU operational?
yes
Alarm solved
Onsite
OMU operational?
yes
Alarm solved
87 / 584
88 / 584
Onsite
A9100: Replace SUMP, SUMA
Onsite
A910: Replace BTS A910
OR
OMU operational?
yes
Alarm solved
89 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
90 / 584
91 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Unit operational?
yes
Alarm solved
92 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
no
Alarm solved
Figure 41: UNKNOWN-CMD-MSG: Corrective Actions If this alarm quickly recurs for more than one OMU, or for more than one FU of the same version, there can be a problem with the software or firmware of any BTS unit.
93 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Alarm persists?
no
Alarm solved
Figure 42: UNKNOWN-ALARM: Corrective Actions If this alarm is sent frequently or by more than one OMU within a short period of time, there can be a problem with the software.
94 / 584
If the CLLK is redundant on this BTS, the telecom functions are not affected. For the BTS A9100: there is no clock redundancy available, so the cells fed by the reporting CLLK are lost, thus the BTS is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
95 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Replace SUMP, SUMA
Clock operational?
yes
Alarm solved
96 / 584
Clock operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
97 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality. (*). If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
98 / 584
TRE operational?
yes
Alarm solved
no
yes
no Onsite
Replace TRE
TRE operational?
yes
Alarm solved
99 / 584
BTS operational?
no Alarm is reported from more than one BTS? yes Contact System Support
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
100 / 584
The transmission quality is degraded. Impact Loss Degradation BSS Cell(s) Signaling X Calls X
101 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
yes
no
Onsite
RA operational?
yes
Alarm solved
102 / 584
Telecom functions are not affected. The old configuration is still running. Impact Loss Degradation BSS Cell(s) Signaling Calls -
103 / 584
Alarm persists?
no
Alarm solved
104 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality, calls are lost. (*) If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
105 / 584
yes
Alarm persists?
no
Alarm solved
106 / 584
Other TRE alarms event? no Download the masterfile and the application file
yes
Alarm persists?
no
Alarm solved
107 / 584
yes
Alarm persists?
no
Alarm solved
108 / 584
yes
Alarm persists?
no
Alarm solved
109 / 584
yes
Initialize TRE
Alarm persists?
no
Alarm solved
110 / 584
Correct parameter values with correct Abis configuration according to BTS capability
Alarm persists?
no
Alarm solved
111 / 584
Alarm number 2, 4 and 7: The transmission quality is degraded. Alarm number 10: No disturbance of the telecom applications. Impact Loss Degradation BSS Cell(s) Signaling X(not Nb.10) Calls X(not Nb.10)
112 / 584
Reset effected RA
Alarm persists?
no
Alarm solved
113 / 584
Replace masterfile
Reset effected RA
Alarm persists?
no
Alarm solved
114 / 584
115 / 584
Alarm persists?
no
Alarm solved
Figure 57: WRONG-CONFIGURATION (BTS): Alarm Number 12, 14, Corrective Actions
116 / 584
Alarm persists?
no
Alarm solved
117 / 584
If the CLLK is redundant on this BTS, the telecom functions are not affected. For the BTS A9100: there is no clock redundancy available, so the cells fed by the reporting CLLK are lost, thus the BTS is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
118 / 584
Alarm persists?
no
Alarm solved
Alarm persists?
no
Alarm solved
119 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
Replace BTS A910 no BTS operational?
120 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
121 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Replace ANX, ANY, ANC
RA operational?
yes
Alarm solved
122 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
123 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality, calls are lost. (*). If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
124 / 584
TRE operational?
yes
Alarm solved
no
Onsite
Replace TRE
TRE operational?
yes
Alarm solved
125 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
126 / 584
127 / 584
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#). If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
128 / 584
FHU operational?
yes
Alarm solved
no
Onsite
G1: Replace FQHU
Onsite OR
G2: Replace STSE/STSP/STSR
FHU operational?
yes
Alarm solved
129 / 584
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
FHU operational?
yes
Alarm solved
130 / 584
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. ( X) Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
131 / 584
FHU operational?
yes
Alarm solved
no Onsite Check cables and connectors between Clock Unit and FHU
FHU operational?
yes
Alarm solved
no
Onsite
Replace FQHU
FHU operational?
yes
Alarm solved
132 / 584
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. ( X) Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
133 / 584
FHU operational?
yes
Alarm solved
no
Onsite
G1: Replace FQHU
Onsite
G2: Replace STSE/STSP/STSR
FHU operational?
yes
Alarm solved
134 / 584
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
135 / 584
FHU operational?
yes
Alarm solved
no Onsite Check cables and connectors between Clock Unit and FHU
FHU operational?
yes
Alarm solved
no
Onsite
Replace FQHU
FHU operational?
yes
Alarm solved
136 / 584
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
137 / 584
FHU operational?
yes
Alarm solved
no Onsite Check cables and connectors between Clock Unit and FHU
FHU operational?
yes
Alarm solved
no
Onsite
Replace FQHU
FHU operational?
yes
Alarm solved
138 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
139 / 584
FHU operational?
yes
Alarm solved
no Onsite Check cables and connectors between Clock Unit and FHU
FHU operational?
yes
Alarm solved
no
Onsite
Replace FQHU
FHU operational?
yes
Alarm solved
140 / 584
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. ( X) Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
FHU operational?
yes
Alarm solved
no
Onsite
Replace FQHU
FHU operational?
yes
Alarm solved
141 / 584
If the FHU has redundancy, telecom functions are not affected. If there is no redundancy, the cell is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
142 / 584
Check existing hardware against populated hardware in the OMU CPF for wrong BTS family, characteristic and parameter entries. Use:
Choose the correct CPF settings by selecting the appropriate BTS characteristics. Use:
FHU operational?
yes
Alarm solved
143 / 584
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
144 / 584
FHU operational?
yes
Alarm solved
no
Restart OMU
no
Onsite
Check parameters at BTS Terminal
Onsite
FHU operational?
yes
Alarm solved
145 / 584
If there is antenna diversity, the antenna diversity function is lost for a short time and there is a loss of call quality. If there is no antenna diversity, there is a loss of calls. The cell and BCCH signaling is lost for around one minute. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
FHU operational?
yes
Alarm solved
no
Onsite
G1: Replace FQHU
Onsite
G2: Replace STSE/STSP/STSR
FHU operational?
yes
Alarm solved
146 / 584
Major (PMA): The fault is detected during initialization or reconfiguration in all cases (Q1 malfunction). If the BTS is equipped and configured for antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity (hardware does not support it or the configuration parameters indicate no antenna diversity usage), the cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
Minor (DMA): In case of Q1 malfunction there is no disturbance of the telecom applications. In case of FHU malfunction, the result depends on the FHU fault, the FHU can eventually go on with the previous configuration. If the fault is fatal, others alarms will appear on other equipment (ex FU on Token bus). Impact Loss Degradation BSS Cell(s) Signaling Calls -
147 / 584
FHU operational?
yes
Alarm solved
FHU operational?
yes
Alarm solved
no
Onsite
G1: Replace FQHU
Onsite
G2: Replace STSE/STSP/STSR
FHU operational?
yes
Alarm solved
148 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
149 / 584
FHU operational?
yes
Alarm solved
no
Onsite
G1: Replace FQHU
Onsite
G2: Replace STSE/STSP/STSR
FHU operational?
yes
Alarm solved
150 / 584
151 / 584
The CU is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the CU supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#) If the CU supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality. (*) If the CU supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
152 / 584
yes
no
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
yes Alarm solved CU operational? Check cables/connectors to mains, batteries, power supplies and EACB
Onsite
Check power supply is switched on
no
Onsite
G1: Replace CPSU
Onsite OR
G2: Replace FCPS
CU operational?
yes
Alarm solved
153 / 584
The FU is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the FU supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#) If the FU supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality. (*) If the FU supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
154 / 584
yes
no
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
yes Alarm solved FU operational? Check cables/connectors to mains, batteries, power supplies, EACB, OMU and FU
Onsite
Check power supply is switched on
no
Onsite
G1: Replace FUPS, TCPS
Onsite OR
G2: Replace FCPS
FU operational?
yes
Alarm solved
155 / 584
Major (PMA): The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
156 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
G1: Replace CUPS
Onsite OR
G2: Replace FCPS
RA operational?
yes
Alarm solved
157 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Onsite
G1: Replace CFSR; CFSU; TBCF; TCFB; TCFU G2: OR Replace CFU1, CFUA, CFUT
Onsite
A9100: OR Replace FANU; FACB
Onsite
A9110E: Replace Fan Cassete
OR
Fan operational?
yes
Alarm solved
158 / 584
Temperature problems are expected to occur. This can lead to a general degradation of the transmitted signal quality. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X
Onsite
G1: Replace CFSR; CFSU; TBCF; TCFB; TCFU G2: OR Replace CFU1, CFUA, CFUT
Onsite
A9100: OR Replace FANU; FACB
Onsite
A9110E: Replace Fan Cassete
OR
Fan operational?
yes
Alarm solved
159 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Onsite
G1: Replace CFSR; CFSU; TBCF; TCFB; TCFU G2: OR Replace CFU1, CFUA, CFUT
Onsite
A9100: OR Replace FANU; FACB
Onsite
A9110E: Replace Fan Cassete
OR
Fan operational?
yes
Alarm solved
160 / 584
Temperature problems are expected to occur. This can lead to a general degradation of the transmitted signal quality. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X
161 / 584
no Alarm persists?
Alarm solved
no Alarm persists?
Alarm solved
162 / 584
Minor (DMA): The CU is no longer usable. The associated eight channels are lost. The BSC reduces the number of channels supported by the cell. If the CU supported the BCCH, redundancy mechanisms regain the cells functionality, calls are lost. If there is no BCCH redundancy, the complete cell is lost. Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) Signaling X(no red.) Calls X(no red.) -
163 / 584
[5,5] CPLGALARM
Onsite
G1: Replace CBC2; CBC4; CEC2; CEC4; FBC2; FCAV; FEC2
Onsite OR
G2: Replace CRBG; CREG; FRBG; FREG; RC4D; RC8D
Onsite OR
G2: DUPD; DUPG; WB2G; WB2D
CU operational?
yes
Alarm solved
164 / 584
If there are two SUPSs, there is no impact on the telecom capabilities. In the case of a single SUPS, the OMU, FHU and CLLK are no longer available and the cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
165 / 584
Onsite
Check Power Supplies are switched on
Onsite
Check cables/connectors to EACB and SUPS
SU operational?
yes
Alarm solved
no
Onsite
G1: Replace SUPS
Onsite OR
G2: Replace ADPS in MCO2/MCO4
Onsite OR
G2: Replace ADPS in MCI2
Onsite OR
G2: Replace MBPS
SU operational?
yes
Alarm solved
166 / 584
Alarm Number
The affected equipment (CU, FU) is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the FU or CU supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the FU or CU supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality, calls are lost. (*) If the FU or CU supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
167 / 584
Onsite
Check Power Supplies are switched on
Onsite
Check cables/connectors to AC/DC and EACB
CU/FU operational?
yes
Alarm solved
no
Onsite
G1: Replace SUPS
Onsite OR
G2: Replace ADPS in MCO2/MCO4
Onsite OR
G2: Replace ADPS in MCI2
Onsite OR
G2: Replace MBPS
CU/FU operational?
yes
Alarm solved
168 / 584
During a defined delay, the configuration is kept, the Telecom functions are not affected. After the end of the previous delay, a minimal configuration is selected with the TRE supporting the BCCH. (#). If the battery is empty, the cells are lost. (X). Impact Loss Degradation BSS #X Cell(s) X # Signaling X Calls #X -
169 / 584
Onsite
Check Power Supplies are switched on
Onsite
Check cables/connectors to control unit, power module and EACB
no Alarm persists?
Alarm solved
yes
Onsite
G2: Replace ADPS in MCO2/MCO4
Onsite
G2: Replace ADPS in MCI2
Onsite
A9100: Replace OR PM08, which LED is off or red *
Onsite
A9100: Replace PM11, which LED is off or red *
Onsite
A9100: Replace PM12, which LED is off or red *
Onsite
A9100: Replace PM18, which LED is off or red *
OR
OR
OR
OR
yes
Alarm solved
* If RIT location is A,0,0, the RIT is located in A9100 COMI/CODI outdoor side compartment
170 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
171 / 584
Onsite
Check Power Supplies are switched on
Onsite
Check cables/connectors to control unit, power module and EACB
no Alarm persists?
Alarm solved
yes
Onsite
G2: Replace ADPS in MCO2/MCO4
Onsite
G2: Replace ADPS in MCI2
Onsite
A9100: Replace OR PM08, which LED is off or red *
Onsite
A9100: Replace PM11, which LED is off or red *
Onsite
A9100: Replace PM12, which LED is off or red *
Onsite
A9100: Replace PM18, which LED is off or red *
OR
OR
OR
OR
yes
Alarm solved
* If RIT location is A,0,0, the RIT is located in A9100 COMI/CODI outdoor side compartment
172 / 584
The battery is empty and is not used: the Telecom functions are not affected. The battery is empty and is used: the cells are lost. (X) Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
173 / 584
Onsite
Check Power Supplies are switched on
Onsite
Battery OK? no G2: Replace BBU2/BU60
Onsite
A9100 OR BCU1/BCU2, PM12: Replace BU41/BU100
Onsite OR
A9100: Replace BATS
Onsite OR
A9100: Replace BU101
yes
yes
Alarm solved
Onsite
Check cables/connectors to control unit and EACB no Contact System Support
Onsite
G2: Replace BHPS
Onsite
G2: Replace PM06
Onsite
A9100: Replace OR BCU1, which LED is off or red *
Onsite
A9100: Replace OR BCU2, which LED is off or red *
Onsite OR
A9100: Replace PM12, which LED is off or red *
OR
yes
Alarm solved
* If RIT location is A,0,0, the RIT is located in A9100 COMI/CODI outdoor side compartment
174 / 584
There is no disturbance of the telecom applications as long as the battery is still working. If the battery is empty, the cells are lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
175 / 584
Onsite
Check cables/connectors to control unit, power module and EACB
Onsite
G1: Replace SUPS
Onsite
G2 in MCO2/MCO4: Replace ADPS
Onsite
G2 in MCI2: Replace ADPS
Onsite OR
G2: Replace MBPS
OR
OR
yes
Alarm solved
176 / 584
There is no disturbance of the telecom applications as long as the battery is still working. If there is no mains power supply and the battery is empty, the cells are lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
177 / 584
Onsite
Check the battery BBU2
Onsite
Check the Battery BU60
OR
Onsite
Battery OK? yes G2: Replace SACE/SCFE
no
Onsite
G2: Replace BBU2
Onsite OR
G2: Replace BU60
Battery OK?
yes
Alarm solved
Battery OK?
yes
Alarm solved
178 / 584
During a defined delay, the configuration is kept, the Telecom functions are not affected. After the end of the previous delay, a minimal configuration is selected with the TRE supporting the BCCH. (#) If the battery is empty, the cells are lost. (X). Impact Loss Degradation BSS #X Cell(s) X # Signaling X Calls #X -
179 / 584
Onsite
Check cables/connectors to control unit and BTS
Onsite
Check external BTS mains supply and fuses. Setup supply and replace fuses if required
no Alarm persists?
Alarm solved
yes
Onsite
A9100: Replace PM08, which LED is off or red *
Onsite OR
A9100: Replace PM11, which LED is off or red *
Onsite
A9100: Replace PM12, which LED is off or red *
Onsite
A9100: Replace PM18, which LED is off or red *
OR
OR
yes
Alarm solved
* If RIT location is A,0,0, the RIT is located in A9100 COMI/CODI outdoor side compartment
180 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality. (*). If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
181 / 584
Onsite
Check cables/connectors to control unit and BTS
Onsite
Check external BTS mains supply and fuses. Setup supply and replace fuses if required
no Alarm persists?
Alarm solved
yes
Onsite
A9100: Replace PM08, which LED is off or red *
Onsite OR
A9100: Replace PM11, which LED is off or red *
Onsite
A9100: Replace OR PM12, which LED is off or red *
yes
Alarm solved
* If RIT location is A,0,0, the RIT is located in A9100 COMI/CODI outdoor side compartment
182 / 584
Onsite
Onsite
Disable TRE(s)
Onsite
Init TRE(s)
no Alarm persists?
Alarm solved
183 / 584
There is impact through the HW_FAILURE of class 10 alarms. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
184 / 584
Onsite
no Alarm persists?
Alarm solved
yes Check for faulty RITs in class 10 HW_Failure alarms on this BTS. Solve that alarm(s) before repowering the subrack.
yes
Alarm solved
185 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
186 / 584
no Onsite
Onsite
Is ambient temperature out of permitted limits? no Onsite Check and clean heat exchanger air intake
yes
yes
Alarm solved
yes
Alarm solved
187 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
188 / 584
yes
Onsite
yes
yes
Alarm solved
Onsite
yes
yes
Alarm solved
no
Onsite
yes
Alarm solved
189 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality, calls are lost. (*) If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) Calls X(no red.)#* -
190 / 584
no Onsite
Is ambient temperature out of permitted limits? no Onsite Check and clean heat exchanger air intake
Onsite
yes
yes
Alarm solved
yes
Alarm solved
191 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
192 / 584
yes
Alarm solved
no
Onsite
Replace SUMP, SUMA
yes
Alarm solved
193 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
194 / 584
EACB operational?
yes
Alarm solved
no
Onsite
A9100: Replace XIOB
Onsite
For RIT OUTC replacement contact system support
OR
EACB operational?
yes
Alarm solved
195 / 584
MicroBTS operational?
yes
Alarm solved
no
Onsite
Switch MicroBTS off
Onsite
Switch MicroBTS on
MicroBTS operational?
yes
Alarm solved
no
Replace MicroBTS
MicroBTS operational?
yes
Alarm solved
196 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Onsite
Onsite
Replace FACB
OR
Replace FANU
Fan operational?
yes
Alarm solved
no
197 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
198 / 584
Check for previously reported alarms o this function (SBL EACB). Solve that alarm(s) first.
EACB operational?
yes
Alarm solved
no
Onsite
EACB operational?
yes
Alarm solved
199 / 584
Onsite
EACB operational?
yes
Alarm solved
200 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
201 / 584
yes
FAN operational?
yes
Alarm solved
no
Check for previously reported alarms on this function (SBL CCF). Solve that alarm(s).
FAN operational?
yes
Alarm solved
no
Onsite
Replace FACB
FAN operational?
yes
Alarm solved
202 / 584
7 Class 6: RF alarms
7 Class 6: RF alarms
This section defines the alarms for the Class 6: RF alarm class.
203 / 584
7 Class 6: RF alarms
If there is antenna diversity, the antenna diversity function is lost and there is a loss of call quality. (#) If there is no antenna diversity, the 8 channels supported by the CU are lost. The BCCH is regained through recovery. (X). Impact Loss Degradation BSS Cell(s) #X Signaling #X Calls X #
204 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite
Onsite
Replace Receiver
OR
Replace Transmitter
CU operational?
yes
Alarm solved
205 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite
Replace Receiver
OR
Replace Transmitter
CU operational?
yes
Alarm solved
206 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
207 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite
Replace Receiver
OR
Replace Transmitter
CU operational?
yes
Alarm solved
208 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite
Replace Receiver
OR
Replace Transmitter
CU operational?
yes
Alarm solved
209 / 584
7 Class 6: RF alarms
If the BTS is equipped and configured for antenna diversity, then the antenna diversity function is lost. There is also a loss of call quality. (#). If there is no antenna diversity (hardware does not support it, or the configuration parameters indicate no antenna diversity usage) then the eight channels supported by the CU are lost. The BCCH is regained through recovery. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
210 / 584
7 Class 6: RF alarms
[6,5] RXAL
yes
Onsite
Modify actual Antenna diversity Choose correct CPF capability by OR by selecting replacing the appropriate BTS appropriate antenna characteristics. entity
Lock Function CU
Unlock Function CU
no
Onsite
Replace G1 Receiver
Onsite
Replace G2 Receiver
OR
CU operational?
yes
Alarm solved
Figure 111: RX-AL: Corrective Actions The fault can be due to external interference.
211 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
212 / 584
7 Class 6: RF alarms
[6,6] RXDBLEAL
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite Onsite
Replace both G2 Receivers
Onsite
Replace both G1 Receivers
OR
CU operational?
yes
Alarm solved
213 / 584
7 Class 6: RF alarms
If the BTS is equipped and configured for antenna diversity, then the antenna diversity function is lost. There is also a loss of call quality. (#). If there is no antenna diversity (hardware does not support it, or the configuration parameters indicate no antenna diversity usage) then the eight channels supported by the CU are lost. The BCCH is regained through recovery. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
214 / 584
7 Class 6: RF alarms
[6,7] RXSYNAL
yes
Onsite
Modify actual Antenna diversity Choose correct CPF OR capability by by selecting replacing the appropriate BTS appropriate antenna characteristics. entity
Lock Function CU
Unlock Function CU
no
Onsite
Replace G1 Receiver
Onsite
Replace G2 Receiver
OR
CU operational?
yes
Alarm solved
215 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
216 / 584
7 Class 6: RF alarms
[6,8] RXSYNDBLEAL
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite Onsite
Replace both G2 Receivers
Onsite
Replace both G1 Receivers
OR
CU operational?
yes
Alarm solved
217 / 584
7 Class 6: RF alarms
The eight channels supported by the offending carrier are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
218 / 584
7 Class 6: RF alarms
[6,9] VSWRAL
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
yes Alarm solved CU operational? Check cables/connectors to transmitter antenna visually for damage and for electric function. If required, reconnect/replace cable
no
CU operational?
yes
Alarm solved
no
Onsite
Replace Combiner
Onsite
Replace Transmitter
OR
CU operational?
yes
Alarm solved
219 / 584
7 Class 6: RF alarms
[6,9] VSWRAL
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
Onsite
Check cables/connectors to transmitter antenna visually for damage and for electric function. If required, reconnect/replace cable
no
CU operational?
yes
Alarm solved
no
Onsite
Replace RTC
Onsite
Replace WBC
Onsite
Replace Transmitter
OR
OR
CU operational?
yes
Alarm solved
220 / 584
7 Class 6: RF alarms
The affected equipment (TX) is no longer usable. The associated eight channels are lost. If the TX supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TX supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the BCCH. (*). If the TX supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.)# * Cell(s) X(no red.) #* Signaling X(no red.) * Calls X(no red.)# * -
221 / 584
7 Class 6: RF alarms
[6,10] TXPOWERAL
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
Onsite
yes Alarm solved CU operational? Check cables/connectors to CU and combiner downlink. If required, reconnect/replace cable
no
no
Onsite
Replace G1 Transmitter
Onsite
Replace G2 Transmitter
OR
CU operational?
yes
Alarm solved
no
Onsite
Replace G1 Combiner
Onsite
Onsite
OR
Replace G2 RTC
OR
Replace G2 WBC
CU operational?
yes
Alarm solved
222 / 584
7 Class 6: RF alarms
Major (PMA): If the transmitter supporting the BCCH is not concerned, the transmitter cannot be used and the eight channels are lost. (#). If the transmitter supporting the BCCH is concerned and there is BCCH redundancy: the transmitter cannot be used and the eight channels are lost recovery mechanisms regain the BCCH. (*). If the TX supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X(no red.) Cell(s) X(no red.) #* Signaling X(no red.) * Calls X(no red.)#* -
223 / 584
7 Class 6: RF alarms
yes
Onsite
Is ambient temperature out of permitted limits? yes The ambient temperature must be reduced. Transmitter Temperature OK? yes Alarm solved
Onsite
OR Onsite
Replace Transmitter
yes
Alarm solved
224 / 584
7 Class 6: RF alarms
yes
Onsite
Is ambient temperature out of permitted limits? yes The ambient temperature must be reduced. Transmitter Temperature OK? yes Alarm solved
Onsite
OR Onsite
Replace Transmitter
yes
Alarm solved
225 / 584
7 Class 6: RF alarms
Transmission quality is degraded. Depending on the level of degradation, the eight channels supported by the transmitter may be lost. The BCCH is regained through recovery. Impact Impact Loss Degradation BSS BSS X Cell(s) Cell(s) X Signaling Signaling X Calls Calls X -
226 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
G1: Replace Transmitter
Onsite
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
227 / 584
7 Class 6: RF alarms
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
228 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Replace MCLU, MCLR
Onsite
Onsite OR
OR
Replace MFG
Replace Transmitter
CU operational?
yes
Alarm solved
229 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Replace STSE, STSP, STSR
Onsite
OR
Replace Transmitter
CU operational?
yes
Alarm solved
230 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
231 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
Replace MCLU, MCLR
Onsite
Onsite
OR
Replace MFG
OR
Replace Transmitter
CU operational?
yes
Alarm solved
232 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
Replace STSE, STSP, STSR
Onsite
OR
Replace Transmitter
CU operational?
yes
Alarm solved
233 / 584
7 Class 6: RF alarms
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
234 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
G1: Replace Transmitter
Onsite
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
235 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
236 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
G1: Replace Transmitter
Onsite
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
237 / 584
7 Class 6: RF alarms
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
238 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
G1: Replace MCLU, MCLR
Onsite
G1: Replace MFG
Onsite OR
G2: Replace STSE,STSP,STSR
OR
CU operational?
yes
Alarm solved
239 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
240 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
Replace MCLU, MCLR
Onsite
Onsite
OR
Replace MFG
OR
Replace Transmitter
CU operational?
yes
Alarm solved
241 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Check cables/connectors to clock link and CU
CU operational?
yes
Alarm solved
no
Onsite
Replace STSE, STSP, STSR
Onsite
OR
Replace Transmitter
CU operational?
yes
Alarm solved
242 / 584
7 Class 6: RF alarms
Major (PMA): The complete cell is lost. (X) Minor (DMA): The transmission quality is degraded. (#). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
243 / 584
7 Class 6: RF alarms
[6,34] ANTENNAVSWR
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
temporarily
Check cable/connectors to transmitter antenna for damage and electric function. Check VSWR threshold switch setting to 1.7 on combiner front panel Check BTS status Reduce transmit power, so cell might come back in traffic. Solve problem as soon as possible
RA operational?
yes
Alarm solved
no
yes
no
yes
no
RA operational?
yes
Alarm solved
Figure 130: ANTENNA-VSWR: Corrective Actions Reduced TX Power If the transmit power was reduced, set transmit power settings back to previous values when the problem is solved.
244 / 584
7 Class 6: RF alarms
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
245 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors from receiver antenna visually and eletrically. Replace cable if required.
Onsite
G1: Replace RFE
Onsite
G2: Replace RFE
OR
RA operational?
yes
Alarm solved
246 / 584
7 Class 6: RF alarms
If the BTS is equipped and configured for antenna diversity, the antenna diversity function is lost. There is a loss of call quality. (#) If there is no antenna diversity, the cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
247 / 584
7 Class 6: RF alarms
[6,36] FRONTENDAL
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors from receiver antenna visually and eletrically. Replace cable if required.
Onsite
G1: Replace RFE
Onsite
G2: Replace RFE
OR
RA operational?
yes
Alarm solved
248 / 584
7 Class 6: RF alarms
The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
249 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors from receiver antenna visually and eletrically. Replace cable if required.
Onsite
G1: Replace RFE
Onsite
G2: Replace RFE
OR
RA operational?
yes
Alarm solved
250 / 584
7 Class 6: RF alarms
If failure of supervision functions causes the alarm, this has no impact on the telecom functions. If the alarm is due to failure of the switch then the BCCH (and therefore the cell) is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
251 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between switch and EACB visually and electrically. Replace cable if required.
Onsite
G1: Replace EACB, EAIB
Onsite
G2: Replace SACE, SCFE
OR
RA operational?
yes
Alarm solved
252 / 584
7 Class 6: RF alarms
The BCCH and therefore the cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
253 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between switch and EACB visually and electrically. Replace cable if required.
Onsite
G1: Replace EACB, EAIB
Onsite
G2: Replace SACE, SCFE
OR
RA operational?
yes
Alarm solved
254 / 584
7 Class 6: RF alarms
Major (PMA): The complete cell is lost. Minor (DMA): No impact on the telecom functions. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
255 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check antenna (DCS1800 only). Replace antenna if required.
Onsite
Check cables/connectors to RTMA, amplifier, antenna, rack unit and tower mounted unit visually and electrically. Replace cable if required.
Onsite
G1: Replace RTMA
Onsite OR
G2: Replace TMA
Onsite OR
G2: Replace RMC
RA operational?
yes
Alarm solved
256 / 584
7 Class 6: RF alarms
Major (PMA): The complete cell is lost. Minor (DMA): No impact on the telecom functions. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
257 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check antenna (DCS1800 only). Replace antenna if required.
Onsite
Check cables/connectors to RTMA, amplifier, antenna, rack unit and tower mounted unit visually and electrically. Replace cable if required.
Onsite
G1: Replace RTMA
Onsite OR
G2: Replace TMA
Onsite OR
G2: Replace RMC
RA operational?
yes
Alarm solved
258 / 584
7 Class 6: RF alarms
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
259 / 584
7 Class 6: RF alarms
[6,45] TESTABORTED
Lock Function RA
Unlock Function RA
yes
no
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between switch and EACB visually and electrically. Replace cable if required.
Onsite
G1: Replace EACB, EAIB
Onsite
G2: Replace SACE, SCFE
OR
RA operational?
yes
Alarm solved
260 / 584
7 Class 6: RF alarms
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
261 / 584
7 Class 6: RF alarms
[6,46] ALARMTESTFAILURE
Lock Function RA
Unlock Function RA
yes
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between switch and EACB visually and electrically. Replace cable if required.
Onsite
Replace RFE
Onsite
Replace EACB, EAIB
Onsite
Replace Combiner
OR
OR
RA operational?
yes
Alarm solved
262 / 584
7 Class 6: RF alarms
[6,46] ALARMTESTFAILURE
Lock Function RA
Unlock Function RA
yes
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between switch and EACB visually and electrically. Replace cable if required.
Onsite
Replace RFE
Onsite
Replace SACE, SCFE Replace RTC
Onsite
Replace WBC
Onsite
OR
OR
OR
RA operational?
yes
Alarm solved
263 / 584
7 Class 6: RF alarms
No further impact on the telecom functions, as the CU is isolated already. Impact Loss Degradation BSS Cell(s) X Signaling Calls -
264 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite OR
Replace Receiver
Replace Transmitter
CU operational?
yes
Alarm solved
265 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite OR
Replace Receiver
Replace Transmitter
CU operational?
yes
Alarm solved
266 / 584
7 Class 6: RF alarms
No further impact on the telecom functions, as the RA is isolated already. Impact Loss Degradation BSS Cell(s) X Signaling Calls -
267 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
268 / 584
7 Class 6: RF alarms
There is some disturbance to the telecom functions. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X
269 / 584
7 Class 6: RF alarms
[6,49] FRONTENDAMPAL
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
G1: Replace RFE
Onsite OR
G2: Replace RFE
RA operational?
yes
Alarm solved
270 / 584
7 Class 6: RF alarms
The BTS is unable to handle telecom traffic. The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
271 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Check OMU CPF against BTS BCCH switch configuration parameters, use:
OR
Choose the correct CPF settings by selecting the appropriate BTS characteristics. Use:
OR
RA operational?
yes
Alarm solved
272 / 584
7 Class 6: RF alarms
Minor (DMA): The eight channels supported by the failing cavity are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
Warning (MI): If frequency hopping is used, during the re-tuning period for the RTCs, the quality of the calls routed through the modified cavity can be degraded (#). If non-hopping, then eight calls are lost during this period. After re-tuning, all channels are available. (X). Impact Loss Degradation BSS Cell(s) X Signaling X Calls X #
273 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
274 / 584
7 Class 6: RF alarms
Minor (DMA): The eight channels supported by the failing cavity are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
Warning (MI): If frequency hopping is used, during the re-tuning period for the RTCs, the quality of the calls routed through the modified cavity can be degraded (#). If non-hopping, then eight calls are lost during this period. After re-tuning, all channels are available. (X). Impact Loss Degradation BSS Cell(s) X Signaling X Calls X #
275 / 584
7 Class 6: RF alarms
Restart OMU
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
276 / 584
7 Class 6: RF alarms
The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
277 / 584
7 Class 6: RF alarms
[6,53] RTCPARKINGFAILURE
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
278 / 584
7 Class 6: RF alarms
The BTS is unable to handle telecom traffic. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
279 / 584
7 Class 6: RF alarms
[6,54] RTCSELFTESTFAILURE
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between basic and extension unit
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
280 / 584
7 Class 6: RF alarms
The channels supported by the RTC extension unit are lost (CU 5 - 8). The BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
281 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check cables/connectors between basic and extension unit
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
282 / 584
7 Class 6: RF alarms
If the alarm number is 1, the channels supported by the reported RTC (CU 1 - 4) are lost. The BCCH is lost if the basic unit is lost. (#). If the alarm number is 2, the channels supported by the extension unit are lost (CU 5 - 8). (X). Impact Loss Degradation BSS X# Cell(s) X# Signaling X# Calls X# -
283 / 584
7 Class 6: RF alarms
[6,56] RTCDETECTORFAILURE
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Onsite
Onsite
Onsite
OR
OR
RA operational?
yes
Alarm solved
284 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X -
285 / 584
7 Class 6: RF alarms
Choose the correct CPF settings by selecting the appropriate BTS characteristics. Use:
Reset BTS
CU operational?
yes
Alarm solved
286 / 584
7 Class 6: RF alarms
All cavities supported by the RTC are lost. The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
287 / 584
7 Class 6: RF alarms
Choose the correct CPF settings by selecting the appropriate BTS characteristics. Use:
Reset BTS
RA operational?
yes
Alarm solved
288 / 584
7 Class 6: RF alarms
Alarm Number
The eight channels supported by the CU are lost. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X -
289 / 584
7 Class 6: RF alarms
[6,241] INCONSISTASSHWACTHW
Onsite Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity, as descibed in the CMA
OR
Onsite
G1: Replace Receiver
Onsite
G1: OR Replace Transmitter
Onsite
G2: Replace Receiver
Onsite OR
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
290 / 584
7 Class 6: RF alarms
[6,241] INCONSISTASSHWACTHW
Onsite
OR
Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity, as descibed in the CMA
Onsite
G1: Replace Receiver
Onsite
G1: OR Replace Transmitter
Onsite
G2: Replace Receiver
Onsite OR
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
291 / 584
7 Class 6: RF alarms
All cavities supported by the RTC are lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
292 / 584
7 Class 6: RF alarms
Onsite Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity, as descibed in the CMA
OR
Onsite
G1: Replace Receiver
Onsite
G1: OR Replace Transmitter
Onsite
G2: Replace Receiver
Onsite OR
G2: Replace Transmitter
OR
RA operational?
yes
Alarm solved
293 / 584
7 Class 6: RF alarms
The eight time slots supported by the reporting CU are lost. Through recovery, the BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
294 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
yes
no
CU operational?
yes
Alarm solved
no
yes
Onsite
G1: Replace Receiver
Onsite
G1: OR Replace Transmitter
Onsite
G2: Replace Receiver
Onsite OR
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
CU operational?
yes
Alarm solved
295 / 584
7 Class 6: RF alarms
The BTS is unable to handle telecom traffic, the cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
296 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Restart OMU
RA operational?
yes
Alarm solved
no
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
297 / 584
7 Class 6: RF alarms
If redundancy is used, there is no disturbance of the telecom applications. If redundancy is not used there is a loss of calls, and the cell and BCCH signaling is lost for a short period (0.5 - 1 minute). (X). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
298 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
299 / 584
7 Class 6: RF alarms
Major (PMA): The fault is detected during initialization or reconfiguration in all the cases (Q1 or CU malfunction). Eight channels which were to be supported by the CU are lost. (X). Minor (DMA): In case of Q1 malfunction, there is no disturbance of telecom applications. In case of CU malfunction, the result depends on the fault: the CU can eventually go on with the previous configuration. If the fault is fatal, other alarms will appear on other equipment. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
300 / 584
7 Class 6: RF alarms
Lock Function CU
Restart OMU
Unlock Function CU
CU operational?
yes
Alarm solved
no
yes
no
Onsite
G1: Replace EACB/EAIB
Onsite
G1: Replace Receiver
Onsite
G1: OR Replace Transmitter
Onsite
G2: Replace Receiver
Onsite OR
G2: Replace Transmitter
OR
CU operational?
yes
Alarm solved
CU operational?
yes
Alarm solved
301 / 584
7 Class 6: RF alarms
Major (PMA): The fault is detected during initialization or reconfiguration in all the cases (Q1 or RTC malfunction). The BTS is lost. (X). Minor (DMA): In case of Q1 malfunction, there is no disturbance of telecom applications. In case of RTC malfunction, the result depends on the fault: the RTC can eventually go on with the previous configuration. If the fault is fatal, other alarms will appear on other equipment. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
302 / 584
7 Class 6: RF alarms
Lock Function RA
Restart OMU
Unlock Function RA
RA operational?
yes
Alarm solved
no
yes
no
Onsite
G1: Replace EACB/EAIB
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
RA operational?
yes
Alarm solved
303 / 584
7 Class 6: RF alarms
Major (PMA): The eight channels supported by the CU are lost. The BCCH is regained through recovery. ( X). Minor (DMA): The antenna diversity functionality is lost, there is a loss of quality of calls. (#). Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X #
304 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
G1: Replace Receiver
Onsite OR
G2: Replace Receiver
CU operational?
yes
Alarm solved
305 / 584
7 Class 6: RF alarms
The eight channels supported by the CU are lost. The BCCH is regained through recovery. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
306 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
G1: Replace Receiver
Onsite OR
G2: Replace Receiver
CU operational?
yes
Alarm solved
307 / 584
7 Class 6: RF alarms
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
308 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite
Replace Receiver
OR
Replace Transmitter
CU operational?
yes
Alarm solved
309 / 584
7 Class 6: RF alarms
Lock Function CU
Unlock Function CU
CU operational?
yes
Alarm solved
no
Onsite
Onsite
Replace Receiver
OR
Replace Transmitter
CU operational?
yes
Alarm solved
310 / 584
7 Class 6: RF alarms
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
311 / 584
7 Class 6: RF alarms
Lock Function RA
Unlock Function RA
Onsite
G1: Replace Combiner
Onsite OR
G2: Replace RTC
Onsite OR
G2: Replace WBC
RA operational?
yes
Alarm solved
312 / 584
8 Class 7: FU Alarms
8 Class 7: FU Alarms
This section defines the alarms for the Class 7: FU alarm class.
313 / 584
8 Class 7: FU Alarms
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
314 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
yes
315 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
yes
Check for OMU alarm(s) (for example 6,247 RESET) to detemine if the OMU was not busy so the FU could not be polled (FU alarm not ready by OMU). Solve this alarm.
316 / 584
8 Class 7: FU Alarms
Alarm Number
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
317 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G1: Replace Frame Unit
Onsite
G2: Replace Frame Unit
OR
FU operational?
yes
Alarm solved
318 / 584
8 Class 7: FU Alarms
Telecom functions can be affected. Disturbances are dependent of telecom mechanism (timers, protocol,...) and duration of the fault (maximum is fixed by BSI_TIMER). For example, calls will be released if this fault lasts more than T_SYNC (FU timer) due to remote transcoder alarm. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X
319 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G1: Replace Frame Unit
Onsite
G2: Replace Frame Unit
OR
FU operational?
yes
Alarm solved
320 / 584
8 Class 7: FU Alarms
The FU is lost, and the eight time slots supported by the FU are lost. The BCCH of the cell is maintained through recovery mechanisms. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
321 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G1: Replace Frame Unit
Onsite
G2: Replace Frame Unit
OR
FU operational?
yes
Alarm solved
322 / 584
8 Class 7: FU Alarms
The antenna diversity capability is lost, the quality of calls are degraded. Impact Loss Degradation BSS Cell(s) Signaling X Calls X
323 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G1: Replace Frame Unit
Onsite
G2: Replace Frame Unit
Onsite
G2: Replace SACE, SCFE
OR
OR
FU operational?
yes
Alarm solved
324 / 584
8 Class 7: FU Alarms
The antenna diversity capability is lost, the quality of calls are degraded. Impact Loss Degradation BSS Cell(s) Signaling X Calls X
325 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G1: Replace Frame Unit
Onsite
G2: Replace Frame Unit
Onsite
G2: Replace SACE, SCFE
OR
OR
FU operational?
yes
Alarm solved
326 / 584
8 Class 7: FU Alarms
The eight time slots supported by the reporting FU are lost. Through reconfiguration, the BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
327 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
yes
328 / 584
8 Class 7: FU Alarms
Major (PMA): If there is a FU state change, the eight channels supported by the FU are lost. The BCCH is regained through recovery. (X). Warning (MI): If there is no FU state change, there is no impact on the telecom capabilities. During the auto-test, the calls ongoing were lost. (#). Impact Loss Degradation BSS X Cell(s) X Signaling X# Calls X# -
329 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
yes
no
FU operational?
yes
Alarm solved
Onsite
Check clock cables/connectors visually and elctrically. Relace cable if required.
FU operational?
yes
Alarm solved
no
Onsite
G1: Replace Frame Unit
no
Onsite
OR
FU operational?
yes
Alarm solved
330 / 584
8 Class 7: FU Alarms
Major (PMA): If there is a FU state change, the eight channels supported by the FU are lost. The BCCH is regained through recovery (X). Warning (MI): No impact on the telecom capabilities. The calls ongoing were lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
331 / 584
8 Class 7: FU Alarms
Major (PMA): If there is a FU state change, the eight channels supported by the FU are lost. The BCCH is regained through recovery (X). Warning (MI): No impact on the telecom capabilities. The calls ongoing were lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
332 / 584
8 Class 7: FU Alarms
The eight time slots supported by the reporting FU are lost. Through recovery, the BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
333 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G1: Replace Frame Unit
Onsite
G1: Replace FQHU
OR
FU operational?
yes
Alarm solved
334 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Onsite
G2: Replace Frame Unit
Onsite
G2: Replace STSE, STSP, STSR
OR
FU operational?
yes
Alarm solved
335 / 584
8 Class 7: FU Alarms
The eight time slots supported by the reporting FU are lost. Through recovery, the BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
336 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Check cables between clock system and FU
Onsite
G1: Replace Frame Unit
Onsite
G1: Replace FQHU
OR
FU operational?
yes
Alarm solved
337 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite
Check cables between clock system and FU
Onsite
G2: Replace Frame Unit
Onsite
G2: Replace STSE, STSP, STSR
OR
FU operational?
yes
Alarm solved
338 / 584
8 Class 7: FU Alarms
There is no further impact on the telecom capability. Impact Loss Degradation BSS Cell(s) X Signaling X Calls -
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
339 / 584
8 Class 7: FU Alarms
The eight time slots supported by the FU are lost. The BCCH is maintained through reconfiguration. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X -
340 / 584
8 Class 7: FU Alarms
Choose the correct CPF settings by selecting the appropriate BTS characteristics. Use:
Reset BTS
FU operational?
yes
Alarm solved
341 / 584
8 Class 7: FU Alarms
Alarm number 1 or 9: The eight time slots supported by the FU are lost. The BCCH is maintained through reconfiguration. Alarm number 8: The FU cannot perform telecom functions as the configuration is incomplete. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X -
342 / 584
8 Class 7: FU Alarms
[7,241] INCONSISTASSHWACTHW
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity.
OR
Onsite
G1: Replace Frame Unit
Onsite OR
G2: Replace Frame Unit
FU operational?
yes
Alarm solved
343 / 584
8 Class 7: FU Alarms
[7,241] INCONSISTASSHWACTHW
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no Onsite Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity.
yes
no
Onsite
G1: Replace Frame Unit
Onsite OR
G2: Replace Frame Unit
FU operational?
yes
Alarm solved
FU operational?
yes
Alarm solved
344 / 584
8 Class 7: FU Alarms
[7,241] INCONSISTASSHWACTHW
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
Onsite Modify actual BTS hardware capability by replacing existing BTS entity by appropriate BTS hardware entity.
OR
Onsite
G1: Replace Frame Unit
Onsite OR
G2: Replace Frame Unit
FU operational?
yes
Alarm solved
345 / 584
8 Class 7: FU Alarms
The eight time slots supported by the FU are lost. The BCCH is maintained through reconfiguration. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X -
346 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
FU operational?
yes
Alarm solved
347 / 584
8 Class 7: FU Alarms
The eight time slots supported by the reporting FU are lost. Through recovery, the BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling Calls X -
348 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
FU operational?
yes
Alarm solved
349 / 584
8 Class 7: FU Alarms
There is no further impact on the telecom capability of the system (the FU was not in service before the fault occurred). The FU remains isolated until the down-load and initialization is completed. Impact Loss Degradation BSS Cell(s) X Signaling X Calls -
350 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
FU operational?
yes
Alarm solved
351 / 584
8 Class 7: FU Alarms
The eight time slots supported by the reporting FU are lost. Through recovery, the BCCH is maintained. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
352 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
yes
FU operational?
yes
Alarm solved
no There is a severe problem with the configuration parameters. Check the parameter validity of cell information elemtent 1/2, BSS parameters, channel configuration, BTS hardware configuration.
no
Onsite
G1: Replace Frame Unit
Onsite OR
G2: Replace Frame Unit
FU operational?
yes
yes
Alarm solved
353 / 584
8 Class 7: FU Alarms
Alarm Number
If the FU supporting the BCCH is not concerned, during the restart the FU loses all calls. After the successful restart the FU is usable. If the FU supporting the BCCH is concerned, during the restart the FU loses all calls. After the successful restart the FU is usable. The BCCH is regained through recovery. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
354 / 584
8 Class 7: FU Alarms
Lock Function FU
Unlock Function FU
FU operational?
yes
Alarm solved
no
FU operational?
yes
Alarm solved
Figure 189: RESTART: Corrective Actions If the FU restarts repeatedly in a short period of time, there can be a hardware problem, wrong configuration parameters sent, or the FU software can be corrupt.
355 / 584
8 Class 7: FU Alarms
Major (PMA): If detected during initialization or re-configuration of the unit, the unit is isolated. Thus the eight time slots supported by the reported FU are lost. Through recovery, the BCCH is maintained. Minor (DMA): In case of a Token Bus malfunction. There is no impact on the telecom capabilities. In case of FU malfunction, the result depends on the fault. The FU can eventually go on with the previous configuration. If the fault is fatal, other alarms will appear on other equipment. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
356 / 584
8 Class 7: FU Alarms
Lock Function FU
Restart OMU
Unlock Function FU
FU operational?
yes
Alarm solved
no
yes
RIT is a DRFU?
no
Onsite
G1: Replace DRFU and DRFE
Onsite
G1: Replace Frame Unit
Onsite
G2: Replace Frame Unit
OR
FU operational?
yes
Alarm solved
FU operational?
yes
Alarm solved
357 / 584
8 Class 7: FU Alarms
358 / 584
359 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
360 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Alarm solved
361 / 584
There is no disturbance of the telecom applications. Impact Loss Degradation BSS Cell(s) Signaling Calls -
Alam cleared?
yes
Alarm solved
362 / 584
Telecom functions are not affected as long as no recovery is needed. If recovery is needed, the cell is lost temporarily and all calls are lost. Impact Loss Degradation BSS Cell(s) Signaling Calls -
363 / 584
Reset BTS
BTS operational?
yes
Alarm solved
no
Onsite
G1: Replace OMUA
Onsite
G2: Replace SACE/SCFE
OR
BTS operational?
yes
Alarm solved
364 / 584
Telecom functions are not affected as long as no recovery is needed. If recovery is needed, the cell is lost temporarily and all calls are lost. Impact Loss Degradation BSS Cell(s) Signaling Calls -
365 / 584
Reset BTS
BTS operational?
yes
Alarm solved
no
Onsite
G1: Replace OMUA
Onsite
G2: Replace SACE/SCFE
OR
BTS operational?
yes
Alarm solved
366 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
367 / 584
Alarm Number
Outgoing calls are not possible for Mobile Stations in the inner cell that camp on the outer cell BCCH frequency. Active calls are not affected. Impact Loss Degradation BSS Cell(s) X (Inner Cell) Signaling X (Inner Cell) Calls -
368 / 584
BTS operational?
yes
Alarm solved
no
yes
no
BTS operational?
yes
Alarm solved
369 / 584
The is no communication on the BCB. Impact Loss Degradation BSS Cell(s) Signaling Calls -
370 / 584
[8,30] BCBLINK
BTS operational?
yes
Alarm solved
no
Onsite
Onsite
Replace SUMP/SUMA
BTS operational?
yes
Alarm solved
371 / 584
[8,30] BCBLINK
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
372 / 584
There is no disturbance of the telecom applications. Impact Loss Degradation BSS Cell(s) Signaling Calls -
373 / 584
[8,31] IOMLINK
BTS operational?
yes
Alarm solved
no
Onsite
Onsite
Replace SUMP/SUMA
BTS operational?
yes
Alarm solved
374 / 584
[8,31] IOMLINK
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
375 / 584
There is no disturbance of the telecom applications. Impact Loss Degradation BSS Cell(s) Signaling Calls -
376 / 584
[8,32] MODULEINSERTED
BTS operational?
yes
Alarm solved
no
Onsite
Onsite
Check RF cables and connectors to TRE and ANX/ANY/ANC visually and electrcally. Replace cable, if required.
If the module has been extracted previously and the same module inserted (without operator action), the connection of the module could be faulty
BTS operational?
yes
Alarm solved
no
Onsite
Replace ANX,ANY,ANC
Onsite
OR
Replace TRE
BTS operational?
yes
Alarm solved
377 / 584
[8,32] MODULEINSERTED
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
378 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
379 / 584
EACB operational?
yes
Alarm solved
no
Onsite
Replace EACB
EACB operational?
yes
Alarm solved
380 / 584
EACB operational?
yes
Alarm solved
no
Onsite
Replace SACE/SAFE
EACB operational?
yes
Alarm solved
381 / 584
There is no disturbance of the telecom applications, because the BTS was powered down before. Impact Loss Degradation BSS Cell(s) Signaling Calls -
382 / 584
Telecom functions are not affected Impact Loss Degradation BSS Cell(s) Signaling Calls -
383 / 584
EACB operational?
yes
Alarm solved
no Onsite
EACB operational?
yes
Alarm solved
no Onsite
Replace FQHU
EACB operational?
yes
Alarm solved
384 / 584
EACB operational?
yes
Alarm solved
no Onsite
EACB operational?
yes
Alarm solved
no Onsite
Replace STSE,STSP,STSR
EACB operational?
yes
Alarm solved
385 / 584
After the previous call interrupt, the BTS is now in service. Impact Loss Degradation BSS Cell(s) Signaling Calls -
386 / 584
Major (PMA): During initialization units supported by this EACB are not switched properly, and therefore the telecom functions may be lost. (X). Minor (DMA): In case of Q1 malfunction, the telecom functions are not affected. In case of EACB malfunction, the result depends on the CU fault, the CU can go on with the previous configuration. If the fault is fatal, other alarms will appear on other equipment. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X
387 / 584
EACB operational?
yes
Alarm solved
EACB operational?
yes
Alarm solved
no
Onsite
Replace EACB
EACB operational?
yes
Alarm solved
388 / 584
EACB operational?
yes
Alarm solved
EACB operational?
yes
Alarm solved
no
Onsite
Replace SACE/SCFE
EACB operational?
yes
Alarm solved
389 / 584
The units supported by this EACB are not switched properly, and therefore the telecom capabilities may be lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
390 / 584
EACB operational?
yes
Alarm solved
no
Onsite
Replace EACB
EACB operational?
yes
Alarm solved
391 / 584
EACB operational?
yes
Alarm solved
no
Onsite
Replace SACE/SAFE
EACB operational?
yes
Alarm solved
392 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
393 / 584
EACB operational?
yes
Alarm solved
EACB operational?
yes
Alarm solved
no
Onsite
Replace EACB
EACB operational?
yes
Alarm solved
394 / 584
EACB operational?
yes
Alarm solved
EACB operational?
yes
Alarm solved
no
Onsite
Replace SACE/SCFE
EACB operational?
yes
Alarm solved
395 / 584
396 / 584
397 / 584
Telecom functions are not directly affected, if the detected problem is not disturbing the BTS function. (#) VSWR and LNA alarms (if equipped), indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
398 / 584
Onsite
yes
Onsite
Trigger customer specific action according to reported alarm (e.g. call fire brogade)
Onsite
no
Alarm solved
399 / 584
Telecom functions are not directly affected, if the detected problem is not disturbing the BTS function. Telecom functions are not directly affected, as long as the BTS is battery powered. Impact Loss Degradation BSS Cell(s) Signaling Calls -
400 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
Figure 213: [9,1] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
401 / 584
Telecom functions are not directly affected, as long as the BTS is battery powered. Immediate intervention is necessary, if not the BTS will go down. Impact Loss Degradation BSS Cell(s) Signaling Calls -
402 / 584
Onsite
yes
Onsite Onsite
Onsite
no
Alarm solved
no
Alarm solved
403 / 584
Telecom functions are not affected . Impact Loss Degradation BSS Cell(s) Signaling Calls -
404 / 584
Onsite
yes
Onsite
Trigger customer specific action according to reported alarm (e.g. call fire brogade)
Onsite
no
Alarm solved
Figure 215: [9,3] EXT-ALARM: BTS G2 and A9100 Default Corrective Actions
405 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check AC power supply fuses, breakers, cabl%s, connectors Check cabling to sensor, replace cabling if required.
Onsite Onsite
Check sensor function, replace sensor if required.
Onsite
External alarm persists? no Alarm solved
Replace SSCPS
Alarm solved
406 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
407 / 584
Onsite
yes
Onsite
Trigger customer specific action according to an open door or window alarm when allowance key is used onsite.
Onsite
no
Alarm solved
408 / 584
Telecom functions are not directly affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
409 / 584
Onsite
yes
Onsite
Trigger customer specific action according to reported alarm (e.g. call fire brogade)
Onsite
no
Alarm solved
Figure 218: [9,5] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
410 / 584
Telecom functions are not directly affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
411 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
Figure 219: [9,6] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
412 / 584
Telecom functions are not directly affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
413 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
G2: Replace HEAT
Onsite
A9100: Replace HEAT2 Check cabling to sensor, replace cabling if required.
OR
Onsite
Check sensor function, replace sensor if required. External alarm persists? no Alarm solved
no
Alarm solved
Figure 220: [9,7] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
414 / 584
Telecom functions are not directly affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
415 / 584
Onsite
yes
Onsite
Trigger customer specific action according to a hot equipment room alarm (e.g. check air condition unit)
Onsite
no
Alarm solved
Figure 221: [9,8] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
416 / 584
Telecom functions are not directly affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
417 / 584
Onsite
yes
Onsite
Trigger customer specific action according to a hot equipment room alarm (e.g. check air condition unit)
Onsite
no
Alarm solved
418 / 584
Telecom functions are not directly affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
419 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
no
Alarm solved
420 / 584
Telecom functions are not directly affected, as long as the BTS is battery powered, but the BTS will be switched off after 30 - 60 s. Impact Loss Degradation BSS Cell(s) Signaling Calls -
421 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite
Check cabling to sensor, replace cabling if required.
Onsite
Check sensor function, replace sensor if required.
yes
no
Alarm solved
yes
Onsit e
Check battery
Onsite
Onsite
Onsite
Onsite
Onsite
Onsite
OR
OR
OR
OR
OR
no
Alarm solved
422 / 584
Telecom functions are not directly affected, as long as the BTS is battery powered. Impact Loss Degradation BSS Cell(s) Signaling Calls -
423 / 584
Onsite
Onsite
Onsite
no
Alarm solved
424 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
425 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
no
Alarm solved
Figure 226: [9,13] EXT-ALARM: BTS G2 and A9100 Default Corrective Actions
426 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
427 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
no
Alarm solved
Figure 227: [9,14] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
428 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
429 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
Figure 228: [9,15] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
430 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
431 / 584
Onsite
yes
Onsite
Onsite
no
Alarm solved
Figure 229: [9,16] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
432 / 584
(#) VSWR alarm indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
433 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check TRX to antenna cables visually and electrically Check cabling to sensor, replace cabling if required.
Onsite
Onsite
Check sensor function, replace sensor if required.
Check antenna
Onsite
External alarm persists? no Alarm solved
Alarm solved
434 / 584
(#) VSWR alarm indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
435 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check TRX to antenna cables visually and electrically Check cabling to sensor, replace cabling if required.
Onsite
Onsite
Check sensor function, replace sensor if required.
Check antenna
Onsite
External alarm persists? no Alarm solved
Alarm solved
436 / 584
(#) VSWR alarm indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
437 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check TRX to antenna cables visually and electrically Check cabling to sensor, replace cabling if required.
Onsite
Onsite
Check sensor function, replace sensor if required.
Check antenna
Onsite
External alarm persists? no Alarm solved
Alarm solved
438 / 584
(#) VSWR alarm indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
439 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check TRX to antenna cables visually and electrically Check cabling to sensor, replace cabling if required.
Onsite
Onsite
Check sensor function, replace sensor if required.
Check antenna
Onsite
External alarm persists? no Alarm solved
Alarm solved
440 / 584
(#) VSWR alarm indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
441 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check TRX to antenna cables visually and electrically Check cabling to sensor, replace cabling if required.
Onsite
Onsite
Check sensor function, replace sensor if required.
Check antenna
Onsite
External alarm persists? no Alarm solved
Alarm solved
442 / 584
(#) VSWR alarm indicates a problem on the antenna output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
443 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
Check TRX to antenna cables visually and electrically Check cabling to sensor, replace cabling if required.
Onsite
Onsite
Check sensor function, replace sensor if required.
Check antenna
Onsite
External alarm persists? no Alarm solved
Alarm solved
444 / 584
(#) PDU/LNA alarm indicates a problem on the antenna amplifier output, and degradation may occur. Impact Loss Degradation BSS Cell(s) X# Signaling Calls X#
445 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite
Check cabling to sensor, replace cabling if required.
Onsite
Check all PDUs for flashing TRX MAB LEDs
Onsite
Check sensor function, replace sensor if required.
Onsite
Replace the MAB corresponding to the lashing TRX MAB LED External alarm persists? no Alarm solved
Alarm solved
446 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
447 / 584
Onsite
Alarm was sent without cause? no yes Check sensor connection to BTS.
Onsite Onsite
G2: Replace HEAT
Onsite
A9100: Replace HEAT2 Check cabling to sensor, replace cabling if required.
OR
Onsite
Check sensor function, replace sensor if required. External alarm persists? no Alarm solved
no
Alarm solved
Figure 237: [9,24] EXT-ALARM: G2 BTS and BTS A9100 Default Corrective Actions
448 / 584
449 / 584
450 / 584
451 / 584
452 / 584
453 / 584
454 / 584
455 / 584
456 / 584
457 / 584
458 / 584
459 / 584
460 / 584
461 / 584
462 / 584
463 / 584
464 / 584
465 / 584
The concerned TRE does not carry traffic as long as the Lapd RSL is not reestablished. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X
466 / 584
[10,1] RSLLINK
BTS operational?
yes
Alarm solved
no
Onsite
Onsite
Check RSL cables and connectors to TRE and SUM visually and electrcally. Replace cable, if required.
BTS operational?
yes
Alarm solved
no
Onsite
Replace SUMP/SUMA
BTS operational?
yes
Alarm solved
467 / 584
[10,1] RSLLINK
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
468 / 584
The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
469 / 584
yes
no
TRE operational?
yes
Alarm solved
no
Onsite
Check RX cables to TRE and ANX/ANY/ANC visually and electrically
Onsite
Onsite
Replace TRE
TRE operational?
yes
Alarm solved
470 / 584
The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
471 / 584
Lock Function RA
Unlock Function RA
yes
no
RA operational?
yes
Alarm solved
no
Onsite
Check RX cables to TRE and ANX/ANY/ANC visually and electrically
Onsite
Onsite
Replace ANX/ANY/ANC
RA operational?
yes
Alarm solved
472 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality. (*). If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X #* Signaling X Calls X#* -
473 / 584
[10,10] TREVSWR
yes
no
TRE operational?
yes
Alarm solved
no
Onsite
Check TX cables to TRE and ANX/ANY/ANC visually and electrically
Onsite
Onsite
Replace TRE
TRE operational?
yes
Alarm solved
474 / 584
[10,10] TREVSWR
BTS operational?
yes
Alarm solved
no
Onsite
Check cables to transmitter antenna visually and electrically.
Onsite
Check for antenna problems (e.g. damage, position, reflection). Solve antenna problem.
Onsite
Replace VSWR detector
Onsite
BTS operational? no Replace BTS A910
475 / 584
Required tools and materials Antenna Test Tools Antenna Dummy Load
specific Problems event Type probable Cause perceived Severity Alarm Description Alarm Number
ANTENNA-VSWR-WARNING Equipment Transmitter Failure Minor (DMA), Warning (MI) A fault has been detected concerning VSWR antenna supervision. 1 (only for A9100 BTS): The LOW (first) threshold of antenna 1 VSWR has been exceeded. 2 (only for A9100 BTS): The LOW (first) threshold of antenna 2 VSWR has been exceeded. 3 (only for A9100 BTS): The LOW (first) thresholds on both antenna 1 and 2 have been exceeded. 4 (only for A9110-E BTS): VSWR 1 alarm for Master. 5 (only for A9110-E BTS): VSWR 2 alarm for Master. 6 (only for A9110-E BTS): VSWR 1 alarm for Slave 1. 7 (only for A9110-E BTS): VSWR 2 alarm for Slave 1. 8 (only for A9110-E BTS): VSWR 1 alarm for Slave 2. 9 (only for A9110-E BTS): VSWR 2 alarm for Slave 2. 10 (only for A9110-E BTS): VSWR 1 alarm for Slave 11. 11 (only for A9110-E BTS): VSWR 2 alarm for Slave 11. 12 (only for A9110-E BTS): VSWR 1 alarm for Slave 12. 13 (only for A9110-E BTS): VSWR 2 alarm for Slave 12. 14 (only for A9110-E BTS): VSWR 1 alarm for Slave 21. 15 (only for A9110-E BTS): VSWR 2 alarm for Slave 21. 16 (only for A9110-E BTS): VSWR 1 alarm for Slave 22. 17 (only for A9110-E BTS): VSWR 2 alarm for Slave 22.
476 / 584
Impact
BSS
Cell(s)
Signaling
Calls
477 / 584
Lock Function RA
Unlock Function RA
yes
no
RA operational?
yes
Alarm solved
no
Onsite Onsite
Onsite
Onsite
If not all possible TREs are equipped, check for missing dummy load on ANY.
Onsite
RA operational?
yes
Alarm solved
478 / 584
Lock Function RA
Unlock Function RA
yes
no
RA operational?
yes
Alarm solved
no
Onsite
Onsite
Onsite
Onsite
RA operational?
yes
Alarm solved
479 / 584
The cell is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
480 / 584
Required tools and materials: Antenna Test Tools Antenna Dummy Load.
Lock RA
Unlock RA
Alarm disappears?
Yes
Alarm solved
No
REK used?
Yes
OMCR
No REK alarm(s)? Yes Solve REK alarm(s)
No
TREAl arms
No
VSWRAlarm disappears?
Yes
Alarm solved
481 / 584
TREAl arms
ANTENNAVSWRURGENT (continued)
Yes
OR
Temporary:
OR
OMCR OMCR
OMCR
No
VSWRAlarm disappears?
482 / 584
On site
ANTENNAVSWRURGENT (continued)
Onsite
Onsite
Onsite
Onsite
If not all possible TREs are equipped, check for missing dummy load on ANY.
Onsite
RA operational?
yes
Alarm solved
Figure 248: ANTENNA-VSWR-URGENT: Corrective Actions, continued Reduced TX Power If the transmit power was reduced, set transmit power settings back to previous values when the problem is solved.
483 / 584
Transmission quality is degraded. Impact Loss Degradation BSS Cell(s) Signaling X Calls X
484 / 584
yes
no
yes
yes
no
no
Onsite
Check cables to TRE visually and electrically.
Onsite
Check SUM cables/connectors
Onsite
Replace TRE
Onsite
Replace SUM
yes
Alarm solved
485 / 584
no
yes
Alarm solved
Check cables between master BTS and reporting slave BTS visually and electrically.
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910 BTS operational? yes Alarm solved
no
486 / 584
Transmission quality is degraded. Impact Loss Degradation BSS Cell(s) Signaling X Calls X
487 / 584
Lock Function RA
Unlock Function RA
yes
no
Onsite
Check SUM cables/connectors
Onsite
Check cables to TRE and antenna visually and electrically.
Onsite
Replace ANX,ANY,ANC
488 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality. (*). If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X #* Signaling X Calls X#* -
489 / 584
yes
no
yes
yes
no
no
Onsite
Check cables to TRE visually and electrically.
Onsite
Check SUM cables/connectors
Onsite
Replace TRE
Onsite
Replace SUM
yes
Alarm solved
490 / 584
no
yes
Alarm solved
Check cables between master BTS and reporting slave BTS visually and electrically.
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910 BTS operational? yes Alarm solved
no
491 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
492 / 584
Lock Function RA
Unlock Function RA
yes
no
Onsite
Check SUM cables/connectors
Onsite
Check cables to TRE and antenna visually and electrically.
Onsite
Replace ANX,ANY,ANC
493 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality, calls are lost. (*) If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X #* Signaling X Calls X#* -
494 / 584
TRE operational?
yes
Alarm solved
no
Onsite
Insert missing TRE module
Onsite
TRE operational?
yes
Alarm solved
495 / 584
[10,51] MODULENOTPRESENT
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
496 / 584
The sector is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
497 / 584
Lock Function RA
Unlock Function RA
TRE operational?
yes
Alarm solved
no
Onsite
Insert missing ANX,ANY,ANC module
Onsite
TRE operational?
yes
Alarm solved
498 / 584
Telecom functions are not affected, as long as no commands on the Managed Objects (SBLs) TRE or RA are executed. Impact Loss Degradation BSS Cell(s) Signaling Calls -
499 / 584
TRE operational?
yes
Alarm solved
no
Onsite
Replace TRE
TRE operational?
yes
Alarm solved
500 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
OR
Switch off Battery Switch off mains power Backup Switch and OR fuse for tower mounted Main Power switch in BTS Side Support Cabinet
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
501 / 584
Telecom functions are not affected, as long as no commands on the Managed Objects (SBLs) TRE or RA are executed. Impact Loss Degradation BSS Cell(s) Signaling Calls -
502 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Replace ANX/ANY/ANC
RA operational?
yes
Alarm solved
503 / 584
The antenna diversity is lost and the quality of reception is degraded. Impact Loss Degradation BSS Cell(s) Signaling Calls X
504 / 584
Onsite
yes Alarm solved TRE operational? no Check BCB cables/connectors
Onsite
Disengage TRE
Onsite
Onsite
Disengage, RIT by RIT, all TREs, ANYs, ANXs, the SUM and the XIOB
Onsite
yes Reengage TRE Alarm persists?
Reengage RIT
no
Onsite
yes Alarm persists? Replace TRE
no Onsite
TRE operational?
yes
Alarm solved
Onsite
yes Alarm persists? Replace BCB flat cable
TRE operational?
Alarm solved
505 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
506 / 584
Alarm Numbers 3, 4, 5, 6, 9, 11: There is no disturbance of the telecom application. Alarm Numbers 7, 8: The antenna diversity is lost and the quality of reception is degraded. Impact Loss Degradation BSS Cell(s) Signaling Calls X
507 / 584
Alarm Number 3
Onsite
yes Alarm solved TRE operational? no Check BCB cables/connectors
Onsite
Disengage TRE
Onsite
Onsite
Disengage, RIT by RIT, all TREs, ANYs, ANXs, the SUM and the XIOB
Onsite
yes Reengage TRE Alarm persists?
Reengage RIT
no
Onsite
yes Alarm persists? Replace TRE
no Onsite
TRE operational?
yes
Alarm solved
Onsite
yes Alarm persists? Replace BCB flat cable
TRE operational?
Alarm solved
Figure 263: HW-DEGRADED (RA): BTS A9100, Alarm Number 3 Corrective Actions
508 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Replace ANX/ANY/ANC
RA operational?
yes
Alarm solved
Figure 264: HW-DEGRADED (RA): BTS A9100, Alarm Number 4...11 Corrective Actions
509 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Check cables to transmitter antenna visually and electrically.
Onsite
Check for antenna problems (e.g. damage, position, reflection). Solve antenna problem.
Onsite
Replace VSWR detector
Onsite
BTS operational? no Replace BTS A910
Alarm solved
Figure 265: HW-DEGRADED (RA): BTS A9100, Alarm Number 3 Corrective Actions
510 / 584
511 / 584
The TRE is no longer usable. The associated eight channels are lost. Independent of frequency hopping or not, the BSC reduces the number of channels supported by the cell. If the TRE supporting the BCCH is not concerned, the cell is degraded, calls are lost. (#). If the TRE supporting the BCCH is concerned and there is BCCH redundancy, recovery mechanisms regain the cells functionality, calls are lost. (*) If the TRE supporting the BCCH is concerned and there is no BCCH redundancy, the complete cell is lost. (X). Impact Loss Degradation BSS X Cell(s) X #* Signaling X Calls X#* -
512 / 584
yes
no
yes
Alarm persists?
no
Alarm solved
Onsite
Check power supply. Ensure BTS is powered correctly.
Onsite
yes Alarm persists? Replace TRE
no
Alarm solved
TRE operational?
yes
Alarm solved
no
Figure 266: HW-FAILURE (TRE): BTS A9100, Alarm Number 1, 12 and 13 Corrective Actions
513 / 584
TRE operational?
yes
Alarm solved
no
yes
no
Onsite
Onsite
yes Alarm persists?
Replace TRE
TRE operational?
Alarm solved
Figure 267: HW-FAILURE (TRE): BTS A9100, Alarm Number 1, 3...11 and 15 Corrective Actions
514 / 584
Alarm Number 14
TRE operational?
yes
Alarm solved
no
yes
no
TRE operational?
yes
Alarm solved
Figure 268: HW-FAILURE (TRE): BTS A9100, Alarm Number 14 Corrective Actions
515 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Onsite
Switch off mains power fuse for tower mounted BTS
Switch off Battery OR Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Check cables between indicated clock unit on master BTS and reporting clock unit.
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
516 / 584
The sector is lost. Impact Loss Degradation BSS X Cell(s) X Signaling X Calls X -
517 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
yes
no
Onsite
Check power supply. Ensure ANX/ANC is powered correctly.
Onsite
yes Alarm persists? Replace ANX/ANY/ANC
RA operational?
Alarm solved
Figure 270: HW-FAILURE (RA): BTS A9100, Alarm Number 2 and 12 Corrective Actions
518 / 584
Alarm Number 10
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
yes
no
Onsite
Onsite
yes Alarm persists? Replace ANX/ANY/ANC
RA operational?
Alarm solved
Figure 271: HW-FAILURE (RA): BTS A9100, Alarm Number 10 Corrective Actions
519 / 584
Alarm Number 14
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
yes
no
RA operational?
yes
Alarm solved
Figure 272: HW-FAILURE (RA): BTS A9100, Alarm Number 14 Corrective Actions
520 / 584
If an alarm on the feeding clock unit of the master BTS is still outstanding, the failure is due to external reasons.
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
521 / 584
During the restart, the TRE looses all its calls, but after the restart, the TRE is again usable. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
522 / 584
TRE operational?
yes
Alarm solved
no
TRE operational?
yes
Alarm solved
no Onsite
Replace TRE
TRE operational?
yes
Alarm solved
523 / 584
BTS operational?
yes
Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
BTS operational? no Replace BTS A910
Alarm solved
524 / 584
Telecom functions are not affected. Impact Loss Degradation BSS Cell(s) Signaling Calls -
525 / 584
Lock Function RA
Unlock Function RA
RA operational?
yes
Alarm solved
no
Onsite
Check configuration parameters.
Onsite
yes Alarm persists? Replace ANX/ANY/ANC
RA operational?
Alarm solved
526 / 584
527 / 584
Alarm Number
As long as the loop is closed, the concerned channels are not available. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
528 / 584
Onsite
Release external loop
BTS operational?
yes
Alarm solved
no
Reset BTS
BTS operational?
yes
Alarm solved
no
Onsite
Replace SUMP/SUMA
BTS operational?
yes
Alarm solved
529 / 584
Onsite
Release external test loop BTS operational? yes Alarm solved
no
Onsite
BTS operational? yes Alarm solved
no
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Replace BTS A910 no BTS operational?
530 / 584
LMT: The corresponding Abis link is lost. If the link towards the BSC is concerned, the BTS is lost (if no redundancy). OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS was lost. The Abis link is reestablished and allows the alarm reception (otherwise, without Abis link, no alarms are reported to the OMC). Case 2, link in other direction is concerned: The other BTS in the chain are lost. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
531 / 584
yes
no
yes
Onsite
Reset BTS
yes
Alarm solved
no
Onsite
Replace SUMP/SUMA no
yes
Alarm solved
532 / 584
Onsite
Abis link is re established? no Reset Function BTS
yes Check/solve alarms of AIFL Abis link is re established? no yes Alarm solved
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Abis link is re established? no Replace BTS A910 Abis link is re established? no Contact System Support yes Alarm solved
533 / 584
LMT: The corresponding Abis link is lost. If the link towards the BSC is concerned, the BTS is lost (if no redundancy). OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS was lost. The Abis link is reestablished and allows the alarm reception (otherwise, without Abis link, no alarms are reported to the OMC). Case 2, link in other direction is concerned: The other BTS in the chain are lost. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
534 / 584
yes
yes
Alarm solved
535 / 584
LMT: The corresponding Abis link is lost. If the link towards the BSC is concerned, the BTS is lost (if no redundancy). OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS was lost. The Abis link is reestablished and allows the alarm reception (otherwise, without Abis link, no alarms are reported to the OMC). Case 2, link in other direction is concerned: The other BTS in the chain are lost. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
536 / 584
yes
no
yes
Onsite
Check Abis cables/connectors
yes
Alarm solved
yes
Alarm solved
537 / 584
Onsite
Abis link is re established? no Reset Function BTS
yes Check/solve alarms of AIFL Abis link is re established? no yes Alarm solved
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Abis link is re established? no Replace BTS A910 Abis link is re established? no Contact System Support yes Alarm solved
538 / 584
LMT: The corresponding Abis link is lost. If the link towards the BSC is concerned, the BTS is lost (if no redundancy). OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS was lost. The Abis link is reestablished and allows the alarm reception (otherwise, without Abis link, no alarms are reported to the OMC). Case 2, link in other direction is concerned: The other BTS in the chain are lost. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
539 / 584
yes
no
CRC enabled?
no
yes
Onsite
Check Abis cables/connectors no BTS operational? yes Alarm solved
Onsite
Check Abis equipment
Onsite
Check transmission equipment up to next node in Abis chain
yes
Alarm solved
Replace SUMP/SUMA
BTS operational?
yes
Alarm solved
540 / 584
Onsite
Abis link is re established? no Reset Function BTS
yes Check/solve alarms of AIFL Abis link is re established? no yes Alarm solved
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Check transmission equipment up to next node in Abis chain
no
yes
Alarm solved
Onsite
Replace BTS A910 Abis link is re established? no Contact System Support yes Alarm solved
541 / 584
LMT: The corresponding Abis link is lost. If the link towards the BSC is concerned, the BTS is lost (if no redundancy). OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS was lost. The Abis link is reestablished and allows the alarm reception (otherwise, without Abis link, no alarms are reported to the OMC). Case 2, link in other direction is concerned: The other BTS in the chain are lost. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
542 / 584
yes
no
no
yes
Alarm solved
Onsite
Check Abis cables/connectors
Onsite
Abis link quality OK? yes Alarm solved
Reset BTS
no
Onsite
Replace SUMP/SUMA
yes
Alarm solved
543 / 584
Onsite
Abis link quality OK? no Reset Function BTS
yes Check/solve alarms of AIFL Abis link quality OK? no yes Alarm solved
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Abis link quality OK? no Replace BTS A910 Abis link quality OK? no Contact System Support yes Alarm solved
544 / 584
LMT: The corresponding Abis link is degraded. OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS is degraded. Case 2, link in other direction is concerned: The link to the other BTS in the chain is degraded. Impact Loss Degradation BSS Cell(s) Signaling X Calls X
545 / 584
yes
no
no
yes
Alarm solved
Onsite
Check Abis cables/connectors
Onsite
Abis link quality OK? yes Alarm solved
Reset BTS
no
Onsite
Replace SUMP/SUMA
yes
Alarm solved
546 / 584
Onsite
Abis link quality OK? no Reset Function BTS
yes Check/solve alarms of AIFL Abis link quality OK? no yes Alarm solved
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Abis link quality OK? no Replace BTS A910 Abis link quality OK? no Contact System Support yes Alarm solved
547 / 584
LMT: The corresponding Abis link is possibly degraded. OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS is possibly degraded. Case 2, link in other direction is concerned: The link to the other BTS in the chain is possibly degraded. Impact Loss Degradation BSS Cell(s) Signaling (X) Calls (X)
548 / 584
yes
no
no
yes
Alarm solved
Onsite
Check Abis cables/connectors
Onsite
Abis link quality OK? yes Alarm solved
Reset BTS
no
Onsite
Replace SUMP/SUMA
yes
Alarm solved
549 / 584
Onsite
Abis link quality OK? no Reset Function BTS
yes Check/solve alarms of AIFL Abis link quality OK? no yes Alarm solved
Onsite
Disconnect mains power from ACCO to Basic Unit
Onsite
Switch off Battery Backup Switch and OR Main Power switch in Side Support Cabinet
Onsite
Switch off mains power fuse for tower mounted BTS
OR
Onsite
After 30 s repower the BTS
Onsite
Abis link quality OK? no Replace BTS A910 Abis link quality OK? no Contact System Support yes Alarm solved
550 / 584
LMT: The corresponding Abis link is lost. If the link towards the BSC is concerned, the BTS is lost (if no redundancy). OMC: Case 1, the link towards the BSC is concerned: The Abis link to the BTS was lost. The Abis link is reestablished and allows the alarm reception (otherwise, without Abis link, no alarms are reported to the OMC). Case 2, link in other direction is concerned: The other BTS in the chain are lost. Impact Loss Degradation BSS Cell(s) X Signaling X Calls X -
551 / 584
yes
yes
Alarm solved
552 / 584
553 / 584
[2,247]
The coding of the additional information for this alarm depends on the alarm number, as shown in Table 5. This information is only provided if the OMU has battery backup for its RAM. Alarm Number 4 Bytes 1-5 6 - 24 5 1-5 6 - 37 6 1-5 6 - 24 7 1-5 6 - 176 Table 5: Alarm [2,247] TLV Codes Coding TLV120 TLV83 TLV120 TLV84 TLV120 TLV83 TLV120 TLV82
[2,248]
The coding of the additional information for this alarm depends on the alarm number, as shown in Table 6. Alarm Number 1 Bytes 1-5 6 - 37 3 1-5 6 - 24 4 1-5 6 - 176 Table 6: Alarm [2,248] TLV Codes Coding TLV120 TLV84 TLV120 TLV83 TLV120 TLV82
[7,1]
554 / 584
The additional information for these alarms are TLV53 and TLV61 coded, as shown in Table 7. Byte Number 1 10 Several TLV61s can follow Table 7: Alarms [7,3], [7,5] to [7,8] and [7,31] to [7,35] TLV Codes Coding Start of TLV53 Start of TLV61
[7,30] [7,245]
The additional information for this alarms is TLV53 coded. The additional information for this alarms is TLV35 coded, or TLV 57 and TLV 58 coded, depending on the value of Byte 2. Byte 2 Value 23 (hex) 39 (hex) Byte Numbers 1-6 1-4 5 - 10 Table 8: Alarm [7,245] TLV Codes Coding TLV35 TLV57 TLV58
[7,246] [7,248]
The additional information for these alarms is TLV35 coded. The additional information for this alarms is TLV59 and TLV61 coded, as shown in Table 9. Byte Number 1 11 Several TLV61s can follow Table 9: Alarm [7,248] TLV Codes Coding Start of TLV59 Start of TLV61
555 / 584
NACK Reason
The NACK Reason field provides more information concerning the message rejection. When messages are received from the OMU, the FU uses the two-byte NACK Reason field as follows: The first byte defines the NACK Type, as shown in Table 10 The second byte defines the Error Number, as shown in Table 11.
NACK Type 1 2 3 4 5 6 7
Description An unknown message was received. The FU was not in a convenient substate when the message was received. Error during software downloading. Error during configuration file downloading or configuration messages sequencing error. Wrong parameter in the configuration file. Wrong parameter in the CONFIGURATION DATA message. Wrong parameter in the FUIF LINK SELECT message.
556 / 584
NACK Type 1 2 3
Error Number
1 2 3 4 5 6 7 8 9 10
Record sequence number error. File header error. Record type error. Sequence error. Software checksum error. Time out error at the beginning of the SCP downloading. Block sequence number error. File length error. Record length error. Time out error from an FU entity. Record sequence number error. File header error. Record type error. Sequence error. File length error.
1 2 3 4 8
557 / 584
NACK Type 5
Error Number
Maximum number of PAGING REQUEST messages out of range (PG_FULL). Polling period of FUIF is zero (FUISUP_PR). Time out for FUIF response is zero (FUISUP_TO). Polling period of MFP is zero (MFPSUP_PR). Time out for MFP response is zero (MFPSUP_TO). I_LAPD_MAX_RX out of range. AG_FULL out of range. I_LAPD_MAX_TX out of range. UI_LAPD_MAX_TX out of range. Wrong checking for T_MEAS. Wrong checking for T_Sync. BSI_TIMER = 0. The name of the wrong parameter is given in brackets.
2 3 4 5 6 7 8 9 10 11 12 6 1 2 3 6 4 5 6 7
Interference band value out of range (INTFBDi). Wrong order between two interference band values (INTFBDi). Channel configuration value out of range (CHCCONFi). Channel configuration value not allowed. Too many SDCCH channels (the whole set of CHCCONFi). TEI out of range. CCCH slots do not belong to an allowed distribution (i.e., TS0 only, TS0 & TS2, TS0 & TS2 & TS4, TS0 & TS2 & TS4& TS6). NETWORK_TYPE out of range. BTS ciphering capabilities cannot be supported by the FU. Wrong value for at least one of T310x_y_STOP parameter (x = 5 or 6; y = F or D). All parameters have been checked and are correct, but B_parameter cannot be changed in this state.
8 9 10
11
558 / 584
NACK Type 7
Error Number
Antenna diversity not allowed (ANTENN_DIV). Note, antenna diversity is always available in a G2 with two FU boards. All parameters have been checked and are correct, but B_parameter cannot be changed in this state.
559 / 584
560 / 584
G1, Mark I
The TLV53 byte definitions for G1, Mark l are shown in the following figure.
Element Identifier (=53) 1st Byte Element Identifier (=53) 2nd Byte
*
DMDT 2
AD DMDT 0 BSI
Length (=6) HWSW FNF CDCC 1 CDCC 0 CLLK spare 9th Byte
FI ALATYP CECC
* *
bit number 7 6 5 4
3 2 1
* Not Relevant
Figure 293: G1, Mark I, TLV53 Bytes
G1, Mark II
The TLV53 byte definitions for G1, Mark ll are shown in Figure 294.
Element Identifier (=53) 1st Byte Element Identifier (=53) 2nd Byte
*
DMDT 2
AD DMDT 0 BSI
Length (=6) HWSW FNF CDCC 1 CDCC 0 CLLK spare 9th Byte
FI ALATYP CECC
* *
bit number 7 6 5 4
3 2 1
* Not Relevant
Figure 294: G1, Mark II, TLV53 Bytes
G2, FU 2
The TLV53 byte definitions for G2, FU 2 are shown in the following figure.
561 / 584
Element Identifier (=53) 1st Byte Element Identifier (=53) 2nd Byte
*
0
EVAD ALAN 0
AD 0 BSI
Length (=6) HWSW FNF DMOD CDEC CLLK spare 9th Byte
FI ALATYP CECC
EXT FUCO 0
* *
bit number
7 6 5 4 3 2 1
* Not Relevant
Figure 295: G2, FU2, TLV53 Bytes
G2, FU 3
The TLV53 byte definitions for G2, FU 3 are shown in the following figure.
Element Identifier (=53) 1st Byte Element Identifier (=53) 2nd Byte
*
0
EVAD ALAN 0
AD 0 BSI
FI ALATYP 0 CLLK
INT 0 FHI
EXT FUCO 0
* *
bit number 7 spare 9th Byte 6 5 4
* Not Relevant
Figure 296: G1, FU3, TLV53 Bytes
562 / 584
The field definitions for the fourth and fifth bytes of TLV53 are shown in the following table. Description Alarm Condition Event. Begin/End alarm. Significant only if EVAD=0 Begin. End. Hardware or Software alarm HW SW Alarm Severity Fatal. Non-fatal. Alarm Mode Failure. Incident. Internal Entities At least one internal FU entity is involved. See Table 14. No internal FU entity is involved. External entities At least one external FU entity is involved. See Table 15. No external FU entity is involved. Alarm Number (i.e., TS number for FHI link unavailability at TS number level). Alarm Type.
Table 12: Field Definitions for Fourth and Fifth Bytes of TLV53
563 / 584
Alarms
The FU alarms and alarm types for TLV53 are shown in Table 13. G1, G2 FU2/FU3 DRFU X
ALATYP 1
ALAN 0
Micro-BTS X
NON-SCP-MP-FAULT Non-SCP micro-processor fault, detected in operational state. AL-LIST-ER Alarm list erased, detected in operational state. LAPD link lost. MCLU link 0 lost. MCLU link 1 lost. BSI link 0 lost. Both BSI links lost. FHI link 0 fully available uplink. FHI link 1 fully available uplink.
4 5 6 7 8 9 10 11
0 0 0 0 0 0 0 0
X X X X X X X X
X -
FHI-LINK-0-UN-TDMA FHI link 0 unavailable at TDMA frame level. FHI-LINK-1-UN-TDMA FHI link 1 unavailable at TDMA frame level. INT-HW-FAIL NR-SCP-MP-FAULT Hardware failure. Non-recoverable SCP micro-processor fault. (FU is not in operational state.) Non-recoverable software failure. (Bad checksum.) Alarm list erased. (Detected in state other than operational.) FU rejects telecom parameters from BSC. One or more messages missing: preprocess configure, MS power control, BS power control. Irrelevant parameters. Both MCLU links failed.
12
16 17
0 0
X X
18
NR-SW-FAILURE
19
AL-LIST-ER
21
TELECOM-REJ
TELECOM-REJ (0)
1 22 0
X X
X -
564 / 584
ALATYP 23 25
ALAN 0 0
Description of Fault Code Both FHI links failed. Fatal FUB fault. Hardware failure detected by autotest.
Micro-BTS X
FATAL-FUB-FAULT (2)
Non-recoverable SCP software failure. (Checksum error detected during fault localization state, FU-RESTART sequences for SCP/DSP FU SW, or saved parameters for FU configuration.) Clock failure during initialization. FN failure during initialization. -
3 4
X X
26
FUB-BBSI-LINK-FAULT BBSI link problem still exists after BBSI-TIMER expires. (Equivalent to G1/G2: BOTH-BSI-LINKS.) FUB-BBSI-LINK-TROUBLE link problem existed for less BBSI than BBSI-TIMER period.
27
If the INT bit in the fourth byte of TLV53 has a value of 1, the bits FUCO, FUIF, CECC, CDCC 0, CDCC 1, DMDT 0, DMDT 1, DMDT 2, DMDT 3, DMOD, FICE, DADE, and DEDE indicate the fault situation of the board in terms of internal entities to the FU. The definition of each bit, correlated with the FI bit in the fourth byte, is shown in the following table. Bit Value 0 and FI = 0 0 and FI = 1 1 and FI = 0 1 and FI = 1 Description The board has not detected any fault. The board is not faulty. The board has detected a fault. The board is faulty.
565 / 584
Eighth Byte
If the EXT bit in the fourth byte of TLV53 has a value of 1, the BSI, CLLK and FHI fields indicate the fault situation in terms of external entities to the FU. The definition of each field in the eighth byte is shown in the following table. Field Name BSI 00 01 10 11 CLLK 00 01 10 11 FHI 00 01 10 11 Value Description BSIA Inputs No link is faulty. Only link 0 is faulty. Not relevant. Both links (0 & 1) are faulty. FCLU Inputs No clock links are faulty. Clock link 0 is faulty. Clock link 1 is faulty. Both clock links (0 & 1) are faulty. FU Inputs No FHI links are faulty. FHI link 0 is faulty. FHI link 1 is faulty. Both FHI links (0 & 1) are faulty.
566 / 584
Error Type
Description Record sequence number error. File header error. Record type error. Sequence error. Software checksum error. Time out error at the beginning of the SCP downloading. Block sequence number error. File length error. Record length error. Time out error from an FU entity.
567 / 584
Software Identity
Table 19 shows the software identity. Software Identity 00 DRFU DRSCP (SCP software) 01 DRMFP (MFP software) 02 DRENC (ENC software) 03 DRDEM (DEM software) 04 DRDEC (DEC software) 05 DRTMUX (TRXMUX software) 06 DRBED (BED software) FF Table 19: TLV58 Software Identity Not identified
568 / 584
Board Identity
Board Identity 00 01 02 03 04 05 06 07 08
Table 20 shows the board identity. G1 MKII FUCO FUIF CECC CDEC CDEC DMOD/DMAD DMOD/DMAD DMAD DMAD DRFU DRFU (G1) -
If several boards are concerned, only the board with the shortest mnemonic is identified. Table 21 shows the DSP identity. Type G1 FU/G2 FU3 Description FUCO board: 00 - SCP 01 - MFP FUE boards: Bit i refers to DSP number i. DRFU DEM and DEC processors: Bit i refers to DSP number i. SCP, MFP, and RXP processors, and BED and TRXMUX FPGAs: DSP identification is meaningless because there is one specific software package for each processor. Table 21: TLV58 DSP Identity
569 / 584
Element Identifier (=53) 1st Byte Element Identifier (=53) 2nd Byte
EVAD
AD
FI
INT
EXT
DMDT 2
DMDT 1
DMDT 0 BSI
CECC CLLK
FUIF FHI
FUCO DMDT 3
* *
bit number 7 6 5 4 spare 10th Byte
* Not Relevant
Figure 297: G1, Mark I TLV59 Bytes
570 / 584
Table 22 shows the definitions of TLV 59 FU Alarm Type 20 alarms (G1/G2 and Micro-BTS only). G1, G2 FU2/FU3 DRFU X X
ALATYP ALAN 20 0 2
Description of Fault Code Recoverable software failure. SCP or DSP exception. FU telecom configuration failure. (Time out elapsed or algorithm configuration parameters refused during FU initialization). Other recoverable cases, such as spurious hardware problem, or hardware problem not detected by tests. TS configuration failure.
Micro-BTS X X
REC-SW-FAIL (3)
4 5 6
X X
SYS-INFO 3 parameters out of range. X G1/G2 FU, DRFU: Failure of both BSI, both FHI, or both MCLU links detected in operational or fault localization states. Micro-BTS: BBSI link fault detected in operational state. X
7 8
Pushbutton reset. Failure of LAPD link for more than BCCH Cut Timer value.
X X
Table 22: TLV59 FU Alarm Type 20 Alarms for G1/G2 and Micro-BTS
571 / 584
Table 23 shows the definitions of TLV 59 for the TRE faults (Evolium BTS only). EVAD indicates the faultcondition: 1 = Eventtype (EV), 0 = Appearance/Disappearance type (AD). AD indicates the Appearance/Disappearance state; 1 = Appearance (ON), 0 = Disappearance (OFF). ALATYP 1 5 6 9 13 20 0 21 22 23 24 25 27 28 29 30 31 32 33 34 21 0 25 0 1 AD AD EV EV EV EV EV EV EV EV EV EV EV EV EV EV EV ALAN 0 0 0 0 0 EVAD AD AD AD AD AD Description of Fault Code CLKI clock failure (1) CLKI frame failure RSL LAPD link failure Non fatal temperature failure TRE VSWR failure (1) Recoverable failure Microprocessor failure BCCH failure Algorithm failure TLC_CONFIG_T expiry TS reconfiguration failure SYS INFO 3 failure BCCH_CUT timeout Radio failure ECPL failure L1 DSP failure L1 DSP no response failure Internal serial interface failure FCLK IT failure Internal FN failure Handover/Power control algorithms configuration refused Missing message TRE fatal failure (1) Microprocessor failure HW failure
572 / 584
ALATYP
ALAN 2 3 4 5 6 7 8 9 10 11 20 28 29 30 31 32 33 34
EVAD AD AD AD AD AD AD AD AD AD AD AD AD AD AD AD AD AD AD
Description of Fault Code SW failure CLKI synchronization failure Autoreconfiguration failure Configuration failure BSII failure (2) IOM LAPD link failure SW activation failure Downloading failure HW watchdog reset Configuration file failure Temperature failure Radio failure ECPL failure L1 DSP failure L1 DSP no response failure Internal serial interface failure FCLK IT failure Internal FN failure
Table 23: TLV59 for TRE faults of Evolium BTS (1) As this alarm is fatal for the module, no alarm disappearance indication is supplied. The alarm disappearance is detected on Alarm In Force List report. (2) As the link connection is lost, the failure cannot be spontaneously reported to the OMU/SUM. But the corresponding alarm is stored in the Alarms In Force List and may be obtained by the OMU/SUM on Alarm In Force List report (if the failure has disappeared), as long as the module stays in out of order state (as the reason for which the OUT OF ORDER state has been entered).
573 / 584
Table 24 shows the definitions of TLV 59 for the AN faults (Evolium BTS only). EVAD indicates the faultcondition: 1 = Eventtype (EV), 0 = Appearance/Disappearance type (AD). AD indicates the Appearance/Disappearance state; 1 = Appearance (ON), 0 = Disappearance (OFF). ALATYP 1 2 0 1 2 3 4 5 7 0 1 2 3 14 15 16 17 18 19 20 0 10 EV EV 0 0 0 0 0 0 AD AD AD AD AD AD AD AD AD AD 0 0 AD AD AD AD AD AD ALAN 0 EVAD AD Description of Fault Code CLKI clock failure LNA failure LNA 1 partial failure LNA 2 partial failure LNA 1 total failure LNA 2 total failure VSWR circuitry failure CLKI frame failure Antenna VSWR failure AN1_VSWR1_AL AN2_VSWR1_AL AN1_VSWR2_AL AN2_VSWR2_AL Microprocessor failure HW failure SW failure Configuration failure SW activation failure Downloading failure Recoverable failure Microprocessor failure Watchdog reset
574 / 584
Table 25 shows the definitions of TLV 59 for the TRANS&CLOCK faults (Evolium A9100 BTS only). EVAD indicates the faultcondition: 1 = Eventtype (EV), 0 = Appearance/Disappearance type (AD). AD indicates the Appearance/Disappearance state; 1 = Appearance (ON), 0 = Disappearance (OFF). ALATYP 3 0 1 2 3 4 8 14 16 18 19 20 0 10 25 1 3 AD AD EV EV 0 0 0 0 0 AD AD AD AD AD AD AD AD AD AD ALAN EVAD Description of Fault Code Internal CLOCK failure FN input from master lost Frame signal input from master lost Reference clock input from master lost PCM synchronization unusable GPS synchronization lost Oven warm up alarm Microprocessor failure SW failure SW activation failure Downloading failure Recoverable failure Microprocessor failure Watchdog reset TRANS&CLOCK fatal failure (1) HW failure Internal Clock failure
Table 25: TLV59 for TRANS&CLOCK faults of Evolium A9100 BTS (1) As this alarm is fatal for the module, no alarm disappearance indication is supplied. The alarm disappearance is detected on Alarm In Force List report.
575 / 584
Table 26: TLV61 Bytes (1) For TRE, only one byte is forseen, because the length of the data is < 127 bytes. TLV61, even if indicated, may not appear in an alarm message. Internal FU problems, such as a blocked internal bus or a hardware fault, can prevent the FU controller from receiving it. Several TLV61s can be sent. The definition of the Board Identification bytes for G1, G2 and Micro -BTS is shown in Table 27. A bit set to 1 identifies the board at the origin of the fault detection. G1 Bit Number 0 MARK II FUCO G2 FU 3 FUCO FU 4 FUCO Micro-BTS MBPG/MBEG MBPD/MBED MBPG/MBEG MBPD/MBED MBPG/MBEG MBPD/MBED MBPG/MBEG MBPD/MBED MBPG/MBEG MBPD/MBED MBPG/MBEG MBPD/MBED MBPG/MBEG MBPD/MBED
FUIF
FICE
DRFU
CECC
FICE
DRFU
CDEC
DEDE/DADE
DRFU
CDEC
DEDE/DADE
DRFU
DMOD/DMAD
DEDE/DADE
DRFU
DMOD/DMAD
DEDE/DADE
DRFU
576 / 584
DMAD
DADE
DRFU
Table 27: TLV61 Board Identification Bytes for G1/G2 and Micro-BTS * The boards (CDCC, CECC, ...) are numbered as in the rack, starting from the left hand side (Mark I only). The definition of the Board Identification bytes for Evolium BTS is shown in Table 28. A bit set to 1 identifies the board at the origin of the fault detection. TRANS&CLOCK (Evolium A9100 BTS only) CLOCK TRANS -
Bit Number 0 1 2 3 4 5 6
Table 28: TLV61 Board Identification Bytes for Evolium BTS (1) The bit positions are fixed by the Host interface within the TRE.
577 / 584
3 = Address error
4 = Illegal Instruction 5 = Zero Divide 6 = CHK, CHK2 Instruction 7 = cpTRAPcc, TRAPcc, TRAPV Instruction 8 = Privilege Violation 10 = Line 1010 Emulator 11 = Line 1111 Emulator 14 = Format Error 15 = Uninitialized Interrupt 24 = Spurious Interrupt 56 = Configuration Error 59 = MMU : 60 = MMU : 61 = MMU : 62 = MMU : Branch to Write Violation Code (ATC). Branch to Limit Violation Code. Branch to Supervisor Violation Code. Branch to Bus Error during Table Search Code. Branch to Page Fault or Invalid Descriptor Code. Branch to Write Violation Code.
63 = MMU :
64 = MMU :
578 / 584
Bytes
4 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 92 1
Task name Status register User stack pointer Interrupt stack pointer Data register 0 Data register 1 Data register 2 Data register 3 Data register 4 Data register 5 Data register 6 Data register 7 Address register 0 Address register 1 Address register 2 Address register 3 Address register 4 Address register 5 Address register 6 Complete STACK Frame Board Status Register (see relevant OMU HW Functional Description).
579 / 584
SBL number
SBL sub-number
External Reference Number. Used to identify the external (Abis or MMI) scenario (0 = autonomous).
Origin of Action 0 1 2 4 5 Operator command triggered from OMC-R. Operator command triggered from BSC terminal. Operator command triggered from BTS terminal. Autonomous system action. Unknown.
Failure Description. Indicates the reason for an autoreset (i.e., the reason for returning to bootstrap). If a second autoreset occurs during a download, then the first reason is maintained. 1 Three unsuccessful autorestarts.
580 / 584
Bytes
Description - Scenario Problems 2 No download after being in bootstrap for > 24 hours (sending BTS-OMU-STARTED). This is the behaviour of the release 1 and 2 OMU PROM (and should be changed with the next PROM release).
FF No information (e.g. for restart due to internal scenario Time out). (hex) Table 30: TLV83 Bytes
Required Memory Region. The requested memory region. 0 1 2 Message buffer. Memory allocation. Memory re-allocation.
60
Stackinfo
Information taken directly from the stack: Supervisor mode - the system stack User mode - the stack of a particular task.
581 / 584
582 / 584
583 / 584
584 / 584