Lutron eLumen Zone/Area Machine


FS-8700-97

DESCRIPTION

The Lutron Machine driver allows the FieldServer to transfer data to and from devices over RS-232 using Lutron eLumen protocol. The FieldServer can emulate either a Server or Client, although the Lutron Machine driver is only available in Client configuration. Server drivers are for FieldServer testing purposes only. Max Nodes Supported FieldServer Mode Client Server

Nodes 1 1

Comments Only one Lutron Machine driver Client node is able to be connected to a Lutron eLumen panel. One BACNet IP node provides an interface to the Lutron eLumen panel.

The Lutron Grafik Machine Zone/Area Machine driver, hereafter simply referred to as the Lutron Machine driver, provides a BACNet IP interface to a Lutron eLumen panel. The driver can be configured to represent zones or areas as used in the Lutron eLumen panel. The FieldServer acts as both Client and Server to provide BACNet objects to an external BACNet Client. In Server mode, the FieldServer collects data from the eLumen panel and holds the data ready for reads from an external BACNet Client. In Client mode, the FieldServer executes pre-defined commands on the eLumen panel, for example, running scripts.

FORMAL DRIVER TYPE

Serial Client Only

COMPATIBILITY MATRIX
Compatible with this driver Yes Yes No Yes Yes No No No No No No

FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoNode QuickServer FS-QS-1010 QuickServer FS-QS-1011 ProtoCessor FPC-FO2 ProtoCessor FPC-FD2

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 5

Doc. No.

Ver: 1.04 Rev: 1

Lutron eLumen Zone/Area Machine


FS-8700-97

CONNECTION INFORMATION
Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability RS-232, RS-485 9600 8 1 None No

DEVICES TESTED
Tested (FACTORY, SITE) Site

Device Lutron Grafik 6000

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 5

Doc. No.

Ver: 1.04 Rev: 1

Lutron eLumen Zone/Area Machine


FS-8700-97

CONNECTION CONFIGURATIONS

The FieldServer is connected to the Lutron eLumen panel as shown in the connection drawing below: Configure the eLumen panel according to manufacturers instructions.

FS-8917-03 CAT 5 CABLE FS-8915-10 LUTRON SERIAL RS-232 INTERFACE PART # 470-784

FieldServer

P1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 5

FS-8917-03

Doc. No.

Ver: 1.04 Rev: 1

Lutron eLumen Zone/Area Machine


FS-8700-97

120V 15A Dedicated Control Feed

Wallstation link

To control stations

Aux Link (RS-485) User Interface link

eLumen Processor Dimmer panel link

To dimmer panels

Inter-processor link

FieldServer

P1

6.1

Pinouts
From RJ45-01 RJ45-04 RJ45-08 To DB9F-02 DB9M-08 DB9F-05 DB9F-07 DB9M-03 Color Red White Black Brown Green

Function RX CTS GND RTS TX

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 5

Doc. No.

Ver: 1.04 Rev: 1

Lutron eLumen Zone/Area Machine


FS-8700-97

7 7.1

COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: Data Types Supported


Description (or Device Data Type) Zone Intensity, Last Scene number Relay status, Scene on status Desired Intensity, Desired Scene, Scripts Scripts Scripts System variables System variables

FieldServer Data Type Analog Input Binary Input Analog Output Binary Output Multistate Output Analog Value Binary Value

7.2

Read and Write operations supported


FieldServer as a Server Provide Analog Input Status: Get Zone Intensity, Get Area Status Provide Binary Input Status: Get Zone Intensity, Get Area Status Provide Analog Value Status: Get System Variable Value Provide Binary Value Status: Get System Variable Value Accept Analog Setpoints: Select Scene in Area, Run Script Accept Binary Commands: Run Script

FieldServer as a Client Read Analog Input Status: Get Zone Intensity, Get Area Status Read Binary Input Status: Get Zone Intensity, Get Area Status Read Analog Value Status: Get System Variable Value Read Binary Value Status: Get System Variable Value Write Analog Setpoints: Select Scene in Area, Run Script Write Binary Commands: Run Script

7.3

Unsupported Functions and Data Types


Reason FieldServer is a data transfer device, and as such, programming messages are not required

Function Programming messages

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 5 of 5