DESCRIPTION
The Lutron Machine driver allows the FieldServer to transfer data to and from devices over RS-232 using Lutron eLumen protocol. The FieldServer can emulate either a Server or Client, although the Lutron Machine driver is only available in Client configuration. Server drivers are for FieldServer testing purposes only. Max Nodes Supported FieldServer Mode Client Server
Nodes 1 1
Comments Only one Lutron Machine driver Client node is able to be connected to a Lutron eLumen panel. One BACNet IP node provides an interface to the Lutron eLumen panel.
The Lutron Grafik Machine Zone/Area Machine driver, hereafter simply referred to as the Lutron Machine driver, provides a BACNet IP interface to a Lutron eLumen panel. The driver can be configured to represent zones or areas as used in the Lutron eLumen panel. The FieldServer acts as both Client and Server to provide BACNet objects to an external BACNet Client. In Server mode, the FieldServer collects data from the eLumen panel and holds the data ready for reads from an external BACNet Client. In Client mode, the FieldServer executes pre-defined commands on the eLumen panel, for example, running scripts.
COMPATIBILITY MATRIX
Compatible with this driver Yes Yes No Yes Yes No No No No No No
FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 FS-x40 SlotServer ProtoNode QuickServer FS-QS-1010 QuickServer FS-QS-1011 ProtoCessor FPC-FO2 ProtoCessor FPC-FD2
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 5
Doc. No.
CONNECTION INFORMATION
Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability RS-232, RS-485 9600 8 1 None No
DEVICES TESTED
Tested (FACTORY, SITE) Site
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 5
Doc. No.
CONNECTION CONFIGURATIONS
The FieldServer is connected to the Lutron eLumen panel as shown in the connection drawing below: Configure the eLumen panel according to manufacturers instructions.
FS-8917-03 CAT 5 CABLE FS-8915-10 LUTRON SERIAL RS-232 INTERFACE PART # 470-784
FieldServer
P1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 5
FS-8917-03
Doc. No.
Wallstation link
To control stations
To dimmer panels
Inter-processor link
FieldServer
P1
6.1
Pinouts
From RJ45-01 RJ45-04 RJ45-08 To DB9F-02 DB9M-08 DB9F-05 DB9F-07 DB9M-03 Color Red White Black Brown Green
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 5
Doc. No.
7 7.1
FieldServer Data Type Analog Input Binary Input Analog Output Binary Output Multistate Output Analog Value Binary Value
7.2
FieldServer as a Client Read Analog Input Status: Get Zone Intensity, Get Area Status Read Binary Input Status: Get Zone Intensity, Get Area Status Read Analog Value Status: Get System Variable Value Read Binary Value Status: Get System Variable Value Write Analog Setpoints: Select Scene in Area, Run Script Write Binary Commands: Run Script
7.3
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 5 of 5