CIVIL LEGEND
EXISTING THIS CONTRACT
DESIGN CRITERIA
157.7 158.5 SPOT ELEVATION CONTOUR LINE
2. REFER TO THE DRAWINGS FOR ADDITIONAL AND SPECIFIC STRUCTURE LOADINGS AND REQUIREMENTS. WIND LOAD: UBC WIND PRESSURE MPH WIND SPEED EXPOSURE IW SEISMIC LOAD: UBC SEISMIC ZONE 4 SPACING<6" FOR ELECTRICAL AND MECHANICAL, PIPING, AND TANKS AND THEIR ANCHORAGE THE BASE SHEAR EQUATION OF Fp = 0.7CaIpWp AND: Nv = 1.0 I = 1.25 Ip = 1.5 1. APPLICABLE CODE: 1997 (UNIFORM BUILDING CODE) UBC, AS AMENDED BY THE STATE OF CALIFORNIA AND LOCAL AGENCIES (2001 CBC). 1.
CONCRETE REINFORCING
CLEARANCE FOR REINFORCEMENT BARS, UNLESS SHOWN OTHERWISE, SHALL BE: WHEN PLACED ON GROUND: 3" ALL OTHER CONCRETE SURFACES: 2. 2" A NEW PIPE
c CH2M HILL
DOUBLE LINE
SINGLE LINE
EXISTING PIPE SEE SPECIFICATION 03301 FOR CONCRETE EQUIPMENT PAD AND ANCHORAGE DETAILS. REINFORCEMENT BENDS AND LAPS, UNLESS OTHERWISE NOTED, SHALL SATISFY THE FOLLOWING MINIMUM REQUIREMENTS:
3:1
DRAINAGEWAY OR DITCH
3. = 70 =C = 1.15
4.
#3
#4
OR
LIGHT POLE POST OR GUARD POST UTILITY POLE SURVEY CONTROL POINT OR POINT OF INTERSECTION CENTER LINE OR INFILTRATION TRENCH
5.
SPACING>6"
TOP BARS SHALL BE DEFINED AS ANY HORIZONTAL BARS PLACED SUCH THAT MORE THAN 12 INCHES OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR IN ANY SINGLE POUR. HORIZONTAL WALL BARS ARE CONSIDERED TOP BARS. TEE ELBOW DOWN
NET ALLOWABLE SOIL BEARING PRESSURES: 1500 PSF W/ 1/3 INCREASE FOR WIND OR SEISMIC. COEFFICIENT OF FRICTION AGAINST SLIDING: 0.35 EQUIVALENT PASSIVE FLUID PRESSURE: 670 PCF SYMBOL
P/L
PROPERTY LINE DOUBLE WALL CONTAINMENT EXTRACTION PIPELINE DRAWING MATCH LINE
1.
DRAWING LEGEND
TEE UP LEGEND TEE DOWN B
GENERAL INFORMATION
FOR NUMBER, TYPE, SIZE, ARRANGEMENT, AND/OR LOCATION OF EQUIPMENT PADS SEE OTHER DISCIPLINE DRAWINGS. COORDINATE WITH EQUIPMENT SUPPLIER PRIOR TO PLACING SLABS, WALLS AND FOUNDATIONS. COORDINATE PIPING OPENINGS WITH OTHER DISCIPLINE DRAWINGS. CUT NO STRUCTURAL MEMBERS FOR PIPES, DUCTS, ETC, UNLESS SPECIFICALLY DETAILED OR APPROVED IN WRITING BY THE ENGINEER. VISITS TO THE JOB SITE BY THE ENGINEER TO OBSERVE THE CONSTRUCTION DO NOT IN ANY WAY MEAN THAT ENGINEER IS GUARANTORS OF CONSTRUCTORS WORK, NOR RESPONSIBLE FOR THE COMPREHENSIVE OR SPECIAL INSPECTIONS, COORDINATION, SUPERVISION, NOR SAFETY AT THE JOB SITE. SPECIAL INSPECTION (OWNER FURNISHED) IS REQUIRED IN ACCORDANCE WITH UBC INSPECTIONS 108 AND 1701 ON THE FOLLOWING PORTIONS OF THE WORK: CONCRETE PLACEMENT REINFORCING STEEL PLACEMENT STRUCTURAL WELDING ANCHORS, EMBEDS AND BOLTS INSTALLED IN CONCRETE GRADING, EXCAVATION, AND FILLING 5. SPECIFIED CONCRETE TESTING DURING CONSTRUCTION WILL BE OWNER FURNISHED. SPECIFIED LABORATORY TEST MIXES SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
110.50
SPOT ELEVATION
N 1000.00 E 1000.00
ELBOW, 45 DEGREE
1
XX-AS-401
2.
OR
CONCENTRIC REDUCER
ECCENTRIC REDUCER
4.
UNION
GRAVEL SURFACING
VALVES SYMBOLS
CHECKERED PLATE
BUTTERFLY
GROUT GAUGE WITH COCK GRANULAR FILL STRAINER EARTH OR FINISH GRADE FLEX PIPE CONNECTOR
GATE
NOTES:
SWING GATE
1. EXISTING PIPING, EQUIPMENT, AND TOPOGRAPHY IS SHOWN SCREENED AND/OR LIGHT-LINED. NEW PIPING, EQUIPMENT, STRUCTURE, AND FINISHED GRADE IS SHOWN HEAVY-LINED. 2. THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS MAY APPEAR ON THIS SHEET AND NOT BE USED ON THE PLANS.
FOUNDATIONS
1. SLABS-ON-GRADE SPECIFICALLY NOTED TO BE ON FILL SHALL BEAR ON 6" MIN. COMPACTED GRANULAR FILL AS SPECIFIED. LINE OF EXISTING GRADES, AS SHOWN ON THE BUILDING ELEVATIONS AND SECTIONS ARE APPROXIMATE. THEY ARE AT THE WALL FACE, OR ON THE SECTION END EXCEPT AS NOTED.
2.
SWING CHECK
T
ABBREVIATIONS
1.
CONCRETE
28-DAY CAST-IN-PLACE CONCRETE STRENGTHS: TYPICAL: 4000 PSI REINFORCING STEEL: TYPICAL: WOOD STUD WALL (PLAN)
TEMPERATURE SENSOR
RIGID INSULATION ADDL CONT CTRD DI EA EJ EW EXST MIN REQD T&B TYP WS ADDITIONAL CONTINUOUS CENTERED DUCTILE IRON EACH EXPANSION JOINT EACH WAY EXISTING MINIMUM REQUIRED TOP AND BOTTOM TYPICAL WATERSTOP 2. ASTM A615, GRADE 60 BATT INSULATION 3. FABRICATION AND PLACEMENT OF REINFORCING STEEL SHALL BE IN ACCORDANCE WITH CRSI MSP-1 "MANUAL OF STANDARD PRACTICE" AND ACI 301 "SPECIFICATIONS FOR STRUCTURAL, CONCRETE FOR BUILDING". ROUGHEN AND CLEAN CONSTRUCTION JOINTS IN WALLS AND SLABS AS SPECIFIED PRIOR TO PLACING ADJACENT CONCRETE. THE CONTRACTOR SHALL COORDINATE PLACEMENT OF OPENINGS, CURBS, DOWELS, SLEEVES, CONDUITS, BOLTS AND INSERTS PRIOR TO PLACEMENT OF CONCRETE. NO ALUMINUM CONDUIT OR PRODUCTS CONTAINING ALUMINUM OR ANY OTHER MATERIAL INJURIOUS TO THE CONCRETE SHALL BE EMBEDDED IN THE CONCRETE.
PS
PRESSURE SWITCH HOSE VALVE (HV-X) X = NO. IN SPECS
REUSE OF DOCUMENTS:
4.
XCO
GYPSUM WALLBOARD
X=
5.
6.
ACOUSTICAL TILE
HD-Y
HUB DRAIN Y-T WITH DEEP SEAL TRAP Y-P WITH PRIMED TRAP
FD-XY
E
G N
I CH
. E J Mc H EL
FLOOR DRAIN X - NO. IN SPECS Y - T WITH DEEP SEAL TRAP Y - P WITH PRIMED TRAP
DSGN MJ MCHENRY
I A
VERIFY SCALE
BAR IS ONE INCH ON ORIGINAL DRAWING. 0 1"
CI I V L
O F CA L FO I
N R
HYDROGEOLOGIC, INC OU-I MID-PLUME GROUNDWATER TREATMENT FORT ORD MONTEREY, CALIFORNIA
GENERAL
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF CH2M HILL AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CH2MHILL.