You are on page 1of 11

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 1 of 7

Home About Advertise Disclaimer

Instrumentation and Process Control


No Measurements No Controls
The webpage cannot be found

Solenoid Valve Sizing for Shutdown Valve Actuator


In most application unlike control valve that triggered by I/P Positioner to modulate, the shutdown valve is triggered by a solenoid valves. Since the shutdown valve is a ball valve that simply open or close (on/off) the solenoid valve act as a gate of instrument air supply to the actuator. For example, if the plant is in normal condition, then the shutdown valve is open or close by energizing a solenoid valve. The energized solenoid valve (usually 3/2 way valve) will make an instrument air supply goes to the shutdown valve actuator while when the solenoid valve is de-energized, the instrument air supply will close and make the actuator loss air supply. Loss of air supply at actuator will make the actuator goes to its fail position (failure close, failure open, or failure in last position). See below picture to get a clear understanding.

In the project specification or datasheet, usually the solenoid valve is specified as in size. Why it should be ? Why it doesnt 3/8, , 1 etc? Actually, when the project specification mentioned that the solenoid valve shall be , its ok, but the shutdown

http://instrumentation.web.id/?p=468

2/22/2013

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 2 of 7

valve vendor shall confirm. Why? Cause the solenoid valve has a certain Cv. This Cv will determine how much the instrument air can be delivered to the actuator with a certain pressure (usually minimum instrument air pressure goes to valve is 80 psig). So the actuator air consumption is the key factor to determine the solenoid valve size. The bigger the actuator, it may lead to a bigger solenoid valve too. So lets derived the actuator air consumption first and then calculate the required Cv to select the right solenoid valves size. Calculation of Shutdown Valves Actuator Air Consumption Vs = Area (in2) x Stroke (in) Vs = . (in3) Divide by stroking time to get the volumetric flow rate, Q = Vs (in3) / t (second) Q = Vs (in3) / (t / 60) minute Q = . (in3/minute) Convert to cubic feet per minute, Q = ( (Vs (in3) * 0.000578704 (ft3/in3) ) / (t/60) minute Q = ..(ft3 / minute) Q = CFM (cubic feet per minute) Convert to standard condition, Q = CFM * (P actual / P standard) * (T standard / T actual) Q = CFM * ((14.7 + Ps)/14.7) * (520 / (460+T)) Q = SCFM (Standard Cubic Feet per Minute) Where, 14.7 = absolute atmospheric pressure (in psia) 520 = standard conditions in Rankine (60 Fahrenheit = 520 R) Ps = gauge pressure of instrument air (psig) T = temperature of instrument air (F) Now lets determine the required Cv with the following formula provided by solenoid valve vendors. Cv = Q / ( (Differential pressure*Po/((460 + T)*SG))^0.5 * 22.5) Where,

http://instrumentation.web.id/?p=468

2/22/2013

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 3 of 7

SG = specific gravity of instrument air = 1 T = 100 F (assumption of typical instrument air temperatures) Po = Outlet pressure (psia) Then we can calculate the solenoid valve Cv as follows: Cv = Q / ( (Differential pressure*Po/560)^0.5 * 22.5) Case example, A shutdown valve 16 size ANSI Class 600, with the following selected actuator data: Vs = Area (in2) x Stroke (in) = 1318 in3 (taken from vendor catalogue) Required Stroking time = 16 second Q = 1318 in3 / (16/60 minute) Q = 4942.5 in3/minute Q = 4942.5 in3/minute * 0.000578704 ft3/in3 Q = 2.860245 ft3/minute Q = 2.860245 * ((14.7 + 80)/14.7) * (520 / (460+100)) Q = 17.11 SCFM Cv = 17.11 / ( (5*94.7/560)^0.5 * 22.5) Cv = 0.82699239 So the required Cv is 0.827. Select the solenoid valve size based on the vendor published catalogue below (Cv data from Versa). Solenoid Valve size 1/4 1 1 Cv 1.8 4.0 11.1 14.9

From the table above we could select the solenoid valve size required for this application is inch only. Conclusion,

http://instrumentation.web.id/?p=468

2/22/2013

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 4 of 7

For most application, solenoid valve is enough to chatter the actuator instrument air consumption. So as default we could specify the solenoid valve size as in the shutdown valve datasheet. But the vendor of shutdown valve shall confirm this size per their actuator selection.

The webpage cannot be found


Category: Ball Valves, Solenoid Valves

Comments
Leave a Reply Name (required)

Email Address(required)

Website

Comments

Submit Comment

CAPTCHA Code *

Search
Search for:
Search

http://instrumentation.web.id/?p=468

2/22/2013

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 5 of 7

Searching for calculation of Looking for Calculation Of air consumption for on


Top answers for Calculation Of air consumption for on off valve
www.InternetCorkBoard.com

Searching for Calculation Of air consumption for on


Top answers for Calculation Of air consumption for on off valve
www.Answered-Questions.com

Calculation Of air consumption for on off


Get local answers for Calculation Of air consumption for on off valve
www.Answered-Questions.com

Looking for Calculation Of air consumption for on


Discover 100+ answers for Calculation Of air consumption for on off valve
www.Answered-Questions.com

Calculation Of air consumption for on off


Top answers for Calculation Of air consumption for on off valve
www.Answered-Questions.com

Chitika | Opt out?

Random Posts
Introduction of the Subsea Safety Isolation Valve (SSIV) Conventional Motor Control Centre (MCC) Interface with Plant DCS Actuated Ball Valves (Shutdown Valves) Seat Tightness Full Bore or Reduced Bore Ball Valves Pressure Regulator Valves Spring Ranges Valves Classes Non Destructive Examination (NDE) for Welding at Valves

Spam Blocked
spam comments

129,325

http://instrumentation.web.id/?p=468

2/22/2013

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 6 of 7

Enter your email address:

Subscribe

Delivered by FeedBurner

Daily Popular
Motor Operated Valve (MOV) Typical Calibration Procedure of Displacer (Buoyancy) Level Transmitter Control Valve End Connection Thermowell Insertion and Immersion Length Introduction of the Wellhead Control Panel (WHCP) Instrumentation Earthing System Wellhead Control Panel (WHCP) Schematic Part 1: Hydraulic Power Unit (HPU) Typical Calibration Procedure of Differential Pressure Transmitter Spring Return (Single Acting) vs Double Acting Valve Actuators Valve Manifold for Pressure Instrument

Categories
Analyzer Automation System Ball Valves Butterfly Valves Choke Valves Control Valves Coriolis Flow Meter Deluge Valves Displacer Level Transmitter Earthing Fire & Gas Detectors Flow Meter Foundation Fieldbus Gas Metering System Guided Wave Radar Level Transmitter HIPPS Instrument Bulk Material Instrument Calculation Instrumentation Cables Interface with Others Level Gauges Level Switches Magnetostrictive Level Transmitter Miscellaneous Motor Operated Valve (MOV)

http://instrumentation.web.id/?p=468

2/22/2013

Solenoid Valve Sizing for Shutdown Valve Actuator : Instrumentation and Process Control Page 7 of 7

Multiphase Flow Meter Orifice Flow Meter Pressure Gauges Pressure Regulator Valves Pressure Safety Valves (PSV) Pressure Transmitter Protective Coating Rotameter Solenoid Valves Subsea Safety Isolation Valve (SSIV) Temperature Gauge Temperature Transmitter Thermowell Turbine Flow Meter Ultrasonic Flow Meter Wellhead Control Panel (WHCP)

Elements of SEO is Powered by WordPress | Accessible Website Development - Alibi Productions

http://instrumentation.web.id/?p=468

2/22/2013

Instrument Air Consumption Calculation | instrumentationportal.com

Page 1 of 3

instrumentationportal.com
Instrument and Control Engineering for Process Industries

Home Insight Instrument Air Consumption Calculation

Instrument Air Consumption Calculation


Instrument air consumption shall be calculated during detail design to determin by pneumatic operated instrument as well as package which requires air for its u purpose. Instrument air consumption calculation will be the basis to size instrum consists of air compressor, air drier, and air receiver. Actuated valve such as shutdown valve, blowdown valve and control valve are in instrument air for their operation. Instrument air requirement of each instrume size and its operation. Shutdown valve and blowdown valve may be considered w control valve working continuously. It should be noted that the instrument air r steady condition is much lesser than during its transient condition. Assumption To determine the instrument air consumption, some assumptions should be ma assumptions are for example only, not as standard reference, and may differ on Normal air consumption demand Control Valve From total number of control valve, 90% of control valve operates in stable c state air consumption only, while 10% could be in unstable condition hence r consumption. Shutdown valve / Blowdown valve

http://instrumentationportal.com/2011/instrument-insight/instrument-air-consumption-calc... 2/22/2013

Instrument Air Consumption Calculation | instrumentationportal.com

Page 2 of 3

Shutdown valve and Blowdown valve only require instrument air when they predominantly during start up after shutdown, so it is considered intermitte assume that only some number of valve are working simultaneously. It could will operate simultaneously for normal air demand calculation. Peak air demand From total number of control valve, 70% of control valve operates in stable cond air consumption only, while 30% is in unstable condition hence requires transie Shutdown valve / Blowdown Valve Lets say 100% of the valve will operate simultaneously for normal air demand c *Note that the number of percentage state here is assumption only and may diff Vendor data The next step is to gather data from vendor / manufacturer catalog which provid consumption. The following is data taken from catalog: Control valve in stable condition 0.3 scfm Control valve in unstable condition 7 scfm For actuated valve, the instrument air consumption depends on size of actuator obtained from vendor catalog. The required opening or closing time of the main consumption rate. Calculation For instrument air consumption calculation, simply multiply the number of valv consumption data, then sum for all instruments. Do the calculation tabulation f condition. In addition, other package which requires instrument air shall also be

http://instrumentationportal.com/2011/instrument-insight/instrument-air-consumption-calc... 2/22/2013

Instrument Air Consumption Calculation | instrumentationportal.com

Page 3 of 3

Insight

Security System

Search engine optimization

Electric air compressor

Home Insight Instrument Air Consumption Calculation


INSTRUMENT DOCUMENT | INSTRUMENT DRAWING | INSTRUMENT BASIC K INSTRUMENT GLOSSARY | INSTRUMENT INSIGHT | INSTRUMENT JOB Copyright instrumentationportal.com

http://instrumentationportal.com/2011/instrument-insight/instrument-air-consumption-calc... 2/22/2013

You might also like