JB0803- ISOLUX

BOLT CALCULATION FOR M42 ANCHOR BOLT


MAXIMUM UPLIFT FORCE ( COLUMN E-5) = DESIGN DIAMETER = Nos. OF BOLTS PROVIDED = MAXIMUM HORIZONTAL FORCE (COLUMN D-5) = UPLIFT PER BOLT = LENGTH OF EMBEDMENT PROVIDED = CHECK FOR EMBEDED LENGTH As per AISC guidelines L= Apsf/3.14 mm Tu 4tf'c ( sq. mm) 257 45 6 733 42.83 1600 KN ( DUE TO WIND ALONG -X AXIS ) mm Nos KN ( DUE TO SEISMIC ALONG Z AXIS ) KN ( DUE TO WIND ALONG -X AXIS ) mm

Apsf (required surface area) = where Tu = force in N = 42833.33 t = resistant factor = 0.75 f'c = compressive strength of concrete = Apsf = L= Minimum length of embedment = 12 d =

32

N/sq.mm

2523.98 mm 28.35 540.00 mm mm HENCE SAFE

PROVIDED LENGTH > 28.35 mm or 540 mm CHECK FOR TENSION As per ACI-318 Nsa = n Ase,N futa where Nsa = nominal stregth in tension in Newton n = nos. of bolts in a group. = 6 Ase,N = effective x-sectional area of a single bolt =

d2 4 = 1589.625 ( sq. mm) futa = not greater than 1.9 fya or 861.845 N/sq.mm(125000 psi) whichever is less fya = yield strenth of anchor steel in N/sq.mm = 250 Nsa = 4530.43 KN > 257 KN HENCE SAFE CHECK FOR SHEAR As per ACI-318 Vsa = n 0.6 Ase,V futa where Vsa = nominal stregth in shear in pounds n = nos. of bolts in a group. = 6 Ase,V = effective x-sectional area of a single bolt =

d2 4 = 1589.625 ( sq. mm) futa = not greater than 1.9 fya or 861.845 N/sq.mm(125000 psi) whichever is less fya = yield strenth of anchor steel in N/sq.mm = 250 Vsa = 2718.25875 KN > 733 KN HENCE SAFE CHECK FOR PULL OUT As per ACI-318 Npn = c,p Np where Npn = nominal pull out stregth in pounds c,p = modification factor = 1.4 and Np = 8 Abrg f'c where Abrg = net bearing area of bolt head(dia 2d) = = 32

f'c = compressive strength of concrete = Np = now Npn =

d2 4 6358.5 N/sq.mm

( sq. mm)

1627776 Newton 2278.886 KN > 42.83 KN HENCE SAFE