The wall in this area shall be designed to avoid spread of fire.
NOTE The dotted area denotes the volume of the entire quantity of insulating fluid of the
transformer spilled on the floor
Figure11 ExampIe for smaII transformer without graveI Iayer and catchment tank
Transformer Handbook Page 208
Re. 9 PROTECTION, CONTROL AND AUXILIARY SYSTEMS
Re. 9.1 Monitoring and controI systems
Monitoring, protection, regulating and control devices shall be provided, as necessary, for the
correct and safe functioning of the equipment.
Automatic devices, designed to offer selectivity and quick operation, shall provide protection
against the effects of unacceptable overload and internal and external faults appropriate to the size
and significance of installation.
Equipment shall comply with the severity class (see EC 60255) corresponding to the part of the
installation in which it is located.
Facilities shall be provided for isolating the control circuit of each primary switching equipment or
each switchgear bay in order to allow maintenance of high voltage equipment to be performed
safely.
Provision shall be made to allow for repair, maintenance, and/or testing to be carried out on
protection and control devices without any danger to personnel or the equipment.
Control circuits and signalling circuits shall, preferably, be functionally separated. Tripping signals
shall be displayed on the protection panel if it exists.
Alarm and fault-indicating equipment shall clearly indicate danger and fault conditions; several
signals can be combined as a common signal to be transmitted to a remote control point.
The control equipment and system, including cables and cords, shall be designed and installed to
minimize the possibility of damage to the connected equipment due to electromagnetic
interference. Basic rules are given in 9.5.
The control equipment and system, including cables and cords, shall be designed and installed in
such a way that they minimize the danger from operating failure, inadvertent operation or incorrect
information. n meeting this requirement, influences such as voltage dips, supply failure, insulation
faults and electromagnetic interference effects shall be taken into account.
Re. 10 EARTHING SYSTEMS
Re. 10.1 GeneraI
This clause provides the criteria for design, installation, testing and maintenance of an earthing
system such that it operates under all conditions and ensures the safety of human life in any place
to which persons have legitimate access. t also provides the criteria to ensure that the integrity of
equipment connected and in proximity to the earthing system is maintained.
Re. 10.2 FundamentaI requirements
Re. 10.2.1 Safety criteria
The hazard to human beings is that a current will flow through the region of the heart which is
sufficient to cause ventricular fibrillation. The current limit, for power-frequency purposes, should be
derived from EC 60479-1 (curve C1). For substation design, this curve needs to be translated into
voltage limits for comparison with the calculated step and touch voltages taking into account the
impedance present in the body current path. Annex B shows curves of typical voltage limits. The
voltage limits shall take into account the following factors:
proportion of current flowing through the region of the heart;
body impedance along the current path
(based on the 5 % values of table 1 of EC 60479-1);
resistance between the body contact points and return paths
(e.g. remote earth, earth electrode);
fault duration;
fault current magnitude.
t must also be recognized that fault occurrence, fault current magnitude, fault duration and
presence of human beings are probabilistic in nature.
Page 209 Transformer Handbook
Re. Annex A
(normative)
VaIues of rated insuIation IeveIs and minimum cIearances based on
current practice in some countries
TabIe A.1 - VaIues of rated insuIation IeveIs and minimum cIearances in air for
1 kV < 8
m
245 kV for highest voItages for equipment 8
m
not standardized
by the IEC based on current practice in some countries
NominaI
voItage
of
system
Highest
voItage for
equipment
Rated short-
duration power-
frequency
withstand
voItage
Rated Iightning
impuIse
withstand
voItage
a
Minimum phase-to-earth and
phase-to-phase cIearance, 1
b
8n
r.m.s.
8m
r.m.s.
r.m.s.
1,2/50 s
(peak vaIue)
Indoor
instaIIations
Outdoor
instaIIations
VoItage
range
kV kV kV kV mm mm
2,75 15
30
45
60
60
70
90
120
120
120
4,76 19 60 90 120
5,5 19
45
60
75
70
90
120
120
120
120
8,25 27
60
75
95
90
120
160
120
150
160
8,25
26
35
75
95
120
160
150
160
15
35
50
95
110
160
180
160
180
15,5 35
75
85
110
120
150
180
150
160
180
15 17,5 38
110
125
180
220
22 (20) 24 50 150 280
22 25 50
95
125
150
190
210
290
25,8
50
70
125
150
220
280
I
27 50
95
125
150
160
220
280
a
The rated lightning impulse is applicable phase-to-phase and phase-to-earth.