You are on page 1of 2

Lifelight 3PH-UPS Sytems

MECHANICAL SPECIFICATIONS
MODEL NUMBER SYSTEM INVERTER CABINET DIMENSIONS BATTERY CABINET DIMENSIONS BATTERY COMBINED kVA TOTAL EFFICIENCY WIDTH DEPTH HEIGHT WIDTH DEPTH HEIGHT CABINET WEIGHTS RATING WATTS (%) (in.) (in.) (in.) (in.) (in.) (in.) QTY. (lbs)

3UPSS-15000-208Y/120-208Y/120 15 12,000 >92% 3UPSS-30000-208Y/120-208Y/120 30 24,000 >92% 3UPSS-50000-208Y/120-208Y/120 50 40,000 >92% Other Input and Output Voltages Available on Request

42 42 42

22.5 22.5 22.5

71 71 71

42 42 42

22.5 22.5 22.5

71 71 71

1 2 3

2750 5200 7580

ELECTRICAL SPECIFICATIONS
Power Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15, 30 or 50kVA Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208Y/120 or 480Y/277 VAC Input Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .+10%, -15% Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208Y/120 or 480Y/277 VAC Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 Hz. +/- 5% Output Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . .+/- 2% Typical Output Wave Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sinewave<5% with 100% linear load Crest Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5:1 Typical Input Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Input Main Circuit Breaker Output Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Output Main Circuit Breaker Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .<92% Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sealed, Maintenance-Free (AGM) Battery Recharge Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Conforms to UL 924 Standards External Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Provision for hardwire connection of external battery cabinets or DC source. Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .The unit will protect itself and the load against surges as defined in ANSI/IEEE C62.45, Categories A & B. Output Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Shielded, isolation transformer Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Complete from line

Visit Big Beam on the web at:

www.bigbeam.com

You'll find the latest company and product information as well as handy on-line tools:
Our complete product catalog. Interactive Big Beam Representative Listing to communicate with the rep in your area. Literature request forms. Electronic Mail Room for communicating directly with Big Beam.

ENVIRONMENTAL SPECIFICATIONS
Humidity ...................................................................................5 - 95% RH non-condensing Operating Temperature ............................................................-32F to +104F (0C to +40C) Storage Temperature ..............................................................-4F to 140F (-20C to 60C) Audible Noise ..........................................................................<58dB Measured on Response Curve "A" Safety Agencies ......................................................................Listed to UL 924 Standard

STANDARD FEATURES

FACTORY OPTIONS

Reliability (200,000 Hrs.) Energy Star Rated - TP1 Industrial Application 90 Minutes Battery Back-up Front Service Access DSP/PWM Inverter Proven Non-linear Load Capability Incandescent, Fluorescent, HID Compatible

Maintenance By-Pass Switch (MBYP) Outdoor or Harsh Environment Cabinets "Hydrogen Off-Gassing Termination" Output Circuit Breakers Normally-Off Output Circuit Breakers Seismic Rated Bracket Normally - Off Output Remote Shutdown Remote Panel Normally - Off "Hold-On" Factory Start Up (TOS) Extended Warranty (EW)

Big Beam Emergency Systems, Inc.

815-459-6143 www.bigbeam.com

290 East Prairie Street P O Box 518 Crystal Lake, IL 60039-0518 fax 815-459-6126 sales 815-459-6143 www.bigbeam.com email: info@bigbeam.com

Lifelight Mini-UPS Sytems


Lifelight Mini-UPS System
Emergency Lighting Inverter Single Phase, 500 - 3000 VA

Lifelight Mini-UPS Sytems


MECHANICAL SPECIFICATIONS
MODEL NUMBER VA RATING TOTAL WATTS SYSTEM EFFICIENCY (%) INVERTER CABINET DIMENSIONS WIDTH DEPTH HEIGHT (in.) (in.) (in.) CABINET WEIGHT (lbs)

Lifelight UPS Sytems


MECHANICAL SPECIFICATIONS
MODEL NUMBER kVA RATING TOTAL WATTS SYSTEM EFFICIENCY (%) INVERTER CABINET DIMENSIONS WIDTH DEPTH HEIGHT (in.) (in.) (in.) BATTERY CABINET DIMENSIONS COMBINED WIDTH DEPTH HEIGHT WEIGHTS (in.) (in.) (in.) (lbs)

The Lifelight Mini-UPS is a low cost, single phase, space saving, central lighting inverter that replaces older, larger and higher cost cabinets. The Lifelight Mini-UPS integrated solid-state technology reduces maintenance time of critical egress lighting, making the Lifelight Mini-UPS more efficient and effective in keeping your system lit when you need it. The small footprint of the Lifelight Mini-UPS allows for better utilization of your floor space. The front access control panel also makes it easier for maintenance. The Lifelight Mini-UPS is a true on-line system, providing 90 minutes of battery time for HID, fluorescent and incandescent lamp applications.

MUPSS-500-120-120-90 MUPSS-750-120-120-90 MUPSS-1000-120-120-90 MUPSS-1250-120-120-90 MUPSS-1500-120-120-90 MUPSS-2000-120-120-90 MUPSS-3000-120-120-90

500 750 1000 1250 1500 2000 3000

350 525 700 875 1050 1400 2100

>85% >85% >85% >85% >85% >85% >85%

24 24 24 24 24 24 24

22 22 22 22 22 22 22

36 36 36 36 36 36 36

260 310 350 445 455 510 550

Standard Input / Output Voltages: 120VAC. Other voltages available on request.

UPSS-3000-120-120-90 3 2100 UPSS-5000-120-120-90 5 3500 UPSS-7500-208-208-90 7.5 5250 UPSS-10000-208-208-90 10 7000 UPSS-12500-208-208-90 12.5 8750 UPSS-15000-208-208-90 15 10500 UPSS-18000-208-208-90 18 12600 Other Input and Output Voltages Available

>92% >92% >92% >92% >92% >92% >92% on Request

42 42 42 42 42 42 42

22.5 22.5 22.5 22.5 22.5 22.5 22.5

48 71 71 48 48 48 48

~ ~ ~ 42 42 42 42

~ ~ ~ 22.5 22.5 22.5 22.5

~ ~ ~ 71 71 71 71

725 1650 1700 2200 2550 3150 3800

ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS


Power Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500, 750, 1000, 1250, 1500, 2000 and 3000 VA Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120, 208, 240 or 277 VAC Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120, 240, 277 or 120/240 VAC Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 Hz. +/- 1% Output Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . .+/- 3% for all loads and for Battery Discharge mode Output Wave Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sinewave <5% with 100% linear load Output Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Current limiting and short circuit protection Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .>85% Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sealed, Maintenance-Free (AGM) Battery Recharge Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Recharge Time per UL 924 Standards Power Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3, 5, 7.5, 10, 12.5, 15 or 18 kVA Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120, 208, 240 or 277 VAC Input Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .+10%, -15% Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120, 208, 240, 277 or 120/240 VAC Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 Hz. +/- 5% Output Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . .+/- 2% Typical Output Wave Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sinewave <5% with 100% linear load Crest Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5:1 Typical Input Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Input Main Circuit Breaker Output Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Output Main Circuit Breaker Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .>92% Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sealed, Maintenance-Free (AGM) Battery Recharge Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Conforms to UL 924 Standards External Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Provision for hardwire connection of external battery cabinets or DC source Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .The unit will protect itself and the load against surges as defined in ANSI/IEEE C62.45, Categories A & B. Output Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Shielded, isolation transformer Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Complete from line

Lifelight UPS System

Emergency Lighting Inverter Single Phase, 3 - 18kVA

Lifelight 3PH-UPS System


Emergency Lighting Inverter Three Phase, 15 - 50kVA

ENVIRONMENTAL SPECIFICATIONS
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 - 95% RH non-condensing Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -32F to +104F (0C to +40C) Operating Altitiude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Up to 6,000 feet (1,829 meters) Non-operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Up to 10,000 feet (3,048 meters) Safety Agencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Listed to UL 924 Standard

The Lifelight UPS and 3PH-UPS systems use DSP/PWM inverter technology. This guarantees that no matter what lamp application is being used, whether HID, fluorescent or incandescent, this is the on-line system to meet your requirements. The Lifelight UPS and 3PH-UPS systems are also available for harsh environments that exist in industrial applications. The systems can be housed in NEMA 3R or a totally enclosed 4X or 12X cabinet. Location of the units is no longer a factor with the Lifelight UPS and 3PHUPS systems. The enclosure and the monitoring package allows the enduser to select a site either indoor or outdoor, with control and self-diagnostic capabilities. The Lifelight UPS and 3PH-UPS systems feature a hydrogen off-gassing termination switch option. When the facility exhaust fan stops, the battery charger will stop charging, but the inverter will continue to operate and provide power to the load with full battery back-up.

ENVIRONMENTAL SPECIFICATIONS STANDARD FEATURES


FACTORY OPTIONS

Low Profile Compact Cabinet 90 Minutes Battery Back-up AC Power ON Indicator Battery ON Indicator = AC Line Switch Charger ON Indicator = Test Button DC Battery Switch

Output Circuit Breakers (OCB) available in increments of 1, 3, 6, 9 or 12 Normally On Load (NOL) Normally Off Load (NOFFL) Maintenance By-Pass Switch (MBYP) 50 or 60 Hz Three Phase Configuatations Factory Start Up (TOS) Extended Warranty (EW) Outdoor or Harsh Environment Cabinets

Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 - 95% RH non-condensing Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -32F to +104F (0C to +40C) Storage Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-4F to 140F (-20C to 60C) Audible Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .<58dB Measured on Response Curve "A" Safety Agencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Listed to UL 924 Standard

STANDARD FEATURES

FACTORY OPTIONS

Reliability (200,000 Hrs.) Energy Star Rated - TP1 Industrial Application 90 Minutes Battery Back-up Front Service Access DSP/PWM Inverter Proven Non-linear Load Capability Incandescent, Fluorescent, HID Compatible

Maintenance By-Pass Switch (MBYP) Outdoor or Harsh Environment Cabinets "Hydrogen Off-Gassing Termination" Output Circuit Breakers Normally-Off Output Circuit Breakers Seismic Rated Bracket Normally - Off Output Remote Shutdown Remote Panel Normally - Off "Hold-On" Factory Start Up (TOS) Extended Warranty (EW)

815-459-6143 www.bigbeam.com

815-459-6143 www.bigbeam.com

815-459-6143 www.bigbeam.com