Professional Documents
Culture Documents
MECHANICAL SPECIFICATIONS
MODEL NUMBER SYSTEM INVERTER CABINET DIMENSIONS BATTERY CABINET DIMENSIONS BATTERY COMBINED kVA TOTAL EFFICIENCY WIDTH DEPTH HEIGHT WIDTH DEPTH HEIGHT CABINET WEIGHTS RATING WATTS (%) (in.) (in.) (in.) (in.) (in.) (in.) QTY. (lbs)
3UPSS-15000-208Y/120-208Y/120 15 12,000 >92% 3UPSS-30000-208Y/120-208Y/120 30 24,000 >92% 3UPSS-50000-208Y/120-208Y/120 50 40,000 >92% Other Input and Output Voltages Available on Request
42 42 42
71 71 71
42 42 42
71 71 71
1 2 3
ELECTRICAL SPECIFICATIONS
Power Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15, 30 or 50kVA Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208Y/120 or 480Y/277 VAC Input Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .+10%, -15% Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208Y/120 or 480Y/277 VAC Output Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 Hz. +/- 5% Output Voltage Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . .+/- 2% Typical Output Wave Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sinewave<5% with 100% linear load Crest Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5:1 Typical Input Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Input Main Circuit Breaker Output Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Output Main Circuit Breaker Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .<92% Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sealed, Maintenance-Free (AGM) Battery Recharge Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Conforms to UL 924 Standards External Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Provision for hardwire connection of external battery cabinets or DC source. Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .The unit will protect itself and the load against surges as defined in ANSI/IEEE C62.45, Categories A & B. Output Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Shielded, isolation transformer Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Complete from line
www.bigbeam.com
You'll find the latest company and product information as well as handy on-line tools:
Our complete product catalog. Interactive Big Beam Representative Listing to communicate with the rep in your area. Literature request forms. Electronic Mail Room for communicating directly with Big Beam.
ENVIRONMENTAL SPECIFICATIONS
Humidity ...................................................................................5 - 95% RH non-condensing Operating Temperature ............................................................-32F to +104F (0C to +40C) Storage Temperature ..............................................................-4F to 140F (-20C to 60C) Audible Noise ..........................................................................<58dB Measured on Response Curve "A" Safety Agencies ......................................................................Listed to UL 924 Standard
STANDARD FEATURES
FACTORY OPTIONS
Reliability (200,000 Hrs.) Energy Star Rated - TP1 Industrial Application 90 Minutes Battery Back-up Front Service Access DSP/PWM Inverter Proven Non-linear Load Capability Incandescent, Fluorescent, HID Compatible
Maintenance By-Pass Switch (MBYP) Outdoor or Harsh Environment Cabinets "Hydrogen Off-Gassing Termination" Output Circuit Breakers Normally-Off Output Circuit Breakers Seismic Rated Bracket Normally - Off Output Remote Shutdown Remote Panel Normally - Off "Hold-On" Factory Start Up (TOS) Extended Warranty (EW)
815-459-6143 www.bigbeam.com
290 East Prairie Street P O Box 518 Crystal Lake, IL 60039-0518 fax 815-459-6126 sales 815-459-6143 www.bigbeam.com email: info@bigbeam.com
The Lifelight Mini-UPS is a low cost, single phase, space saving, central lighting inverter that replaces older, larger and higher cost cabinets. The Lifelight Mini-UPS integrated solid-state technology reduces maintenance time of critical egress lighting, making the Lifelight Mini-UPS more efficient and effective in keeping your system lit when you need it. The small footprint of the Lifelight Mini-UPS allows for better utilization of your floor space. The front access control panel also makes it easier for maintenance. The Lifelight Mini-UPS is a true on-line system, providing 90 minutes of battery time for HID, fluorescent and incandescent lamp applications.
24 24 24 24 24 24 24
22 22 22 22 22 22 22
36 36 36 36 36 36 36
UPSS-3000-120-120-90 3 2100 UPSS-5000-120-120-90 5 3500 UPSS-7500-208-208-90 7.5 5250 UPSS-10000-208-208-90 10 7000 UPSS-12500-208-208-90 12.5 8750 UPSS-15000-208-208-90 15 10500 UPSS-18000-208-208-90 18 12600 Other Input and Output Voltages Available
42 42 42 42 42 42 42
48 71 71 48 48 48 48
~ ~ ~ 42 42 42 42
~ ~ ~ 71 71 71 71
ENVIRONMENTAL SPECIFICATIONS
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 - 95% RH non-condensing Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -32F to +104F (0C to +40C) Operating Altitiude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Up to 6,000 feet (1,829 meters) Non-operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Up to 10,000 feet (3,048 meters) Safety Agencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Listed to UL 924 Standard
The Lifelight UPS and 3PH-UPS systems use DSP/PWM inverter technology. This guarantees that no matter what lamp application is being used, whether HID, fluorescent or incandescent, this is the on-line system to meet your requirements. The Lifelight UPS and 3PH-UPS systems are also available for harsh environments that exist in industrial applications. The systems can be housed in NEMA 3R or a totally enclosed 4X or 12X cabinet. Location of the units is no longer a factor with the Lifelight UPS and 3PHUPS systems. The enclosure and the monitoring package allows the enduser to select a site either indoor or outdoor, with control and self-diagnostic capabilities. The Lifelight UPS and 3PH-UPS systems feature a hydrogen off-gassing termination switch option. When the facility exhaust fan stops, the battery charger will stop charging, but the inverter will continue to operate and provide power to the load with full battery back-up.
FACTORY OPTIONS
Low Profile Compact Cabinet 90 Minutes Battery Back-up AC Power ON Indicator Battery ON Indicator = AC Line Switch Charger ON Indicator = Test Button DC Battery Switch
Output Circuit Breakers (OCB) available in increments of 1, 3, 6, 9 or 12 Normally On Load (NOL) Normally Off Load (NOFFL) Maintenance By-Pass Switch (MBYP) 50 or 60 Hz Three Phase Configuatations Factory Start Up (TOS) Extended Warranty (EW) Outdoor or Harsh Environment Cabinets
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 - 95% RH non-condensing Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -32F to +104F (0C to +40C) Storage Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-4F to 140F (-20C to 60C) Audible Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .<58dB Measured on Response Curve "A" Safety Agencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Listed to UL 924 Standard
STANDARD FEATURES
FACTORY OPTIONS
Reliability (200,000 Hrs.) Energy Star Rated - TP1 Industrial Application 90 Minutes Battery Back-up Front Service Access DSP/PWM Inverter Proven Non-linear Load Capability Incandescent, Fluorescent, HID Compatible
Maintenance By-Pass Switch (MBYP) Outdoor or Harsh Environment Cabinets "Hydrogen Off-Gassing Termination" Output Circuit Breakers Normally-Off Output Circuit Breakers Seismic Rated Bracket Normally - Off Output Remote Shutdown Remote Panel Normally - Off "Hold-On" Factory Start Up (TOS) Extended Warranty (EW)
815-459-6143 www.bigbeam.com
815-459-6143 www.bigbeam.com
815-459-6143 www.bigbeam.com