Electrical Safety
Why Electrical Safety Practices and Procedures?
An estimated 30,000 nonnon-fatal electrical shock accidents occur each year with 3,600 disabling injuries Over 600 people die from electrocution each year Electrocution remains the fourth (4th) highest cause of industrial fatalities Approximately 3000 reported flash burn incidents reported annually along with approximately 350 deaths
6/12/2013
Electrical Safety
NFPA 70E Standard for Electrical Safety in the Workplace Formally Standard for Electrical Safety Requirements for Employee Workplaces Workplaces Began 1976 by NFPA to assist OSHA
Electrical Hazards
6/12/2013
Long term
Memory Loss Nervous disorders Chemical imbalances Damage to vital organs Sometimes Fatal
6/12/2013
Women Perception Threshold 0.001 Amps (1 mA) mA) Painful Shock 0.009 Amps (9 mA) mA) Cannot LetLet-Go Level 0.010 Amps (10 mA) mA) Ventricular Fibrillation 0.100 Amps (100 mA) mA) 3 Seconds 0.200 Amps (200 mA) mA) 1 Second Heart Failure 0.5 Amps (500 mA) mA) Organ Burn and Cell Breakdown 1.5 Amps (1500 mA) mA)
Perception Threshold 0.0007 Amps (0.7 mA) mA) Painful Shock 0.006 Amps (6 mA) mA) Cannot LetLet-Go Level 0.010 Amps (10 mA) mA) Ventricular Fibrillation 0.100 Amps (100 mA) mA) 3 Seconds 0.200 Amps (200 mA) mA) 1 Second Heart Failure 0.5 Amps (500 mA) mA) Organ Burn and Cell Breakdown 1.5 Amps (1500 mA) mA)
Ohm Ohms Law for Electric current (amps), voltage and Body Resistance The typical body has a contact resistance of 500 ohms at the point of contact with the electrical source. The body has an internal resistance of approximately 100 ohms. There is another point of contact to ground of 5000 ohms.
120v / (500+ 100+ 5000) = 21mA 50v / (500+ 100+ 5000) = 8.9 mA
The body has a natural defense system (Skin) Why 50 volts? How can you raise body resistance? The key to survival is decrease our exposure.
It is around 10 mA that the cannot let go go level is reached. Once this is reached, exposure time is increased and the possibility of electrocution may occur.
6/12/2013
Caused by exposure to the arc flash Can cause more surface burns if the initial arc flash ignites other material such as clothing 1st degree to 3rd degree It has and may cause death
Caused by current flowing through organs of the body Caused by currents in excess of 1.5 amps 4th degree (internal) Internal organs Typically fatal
Surface Burns Caused by exposure to the arc flash Can cause more surface burns if the initial arc flash ignites other material such as clothing 1st degree to 3rd degree It has and may cause death!
6/12/2013
Place Circuits in an Electrically Safe Working Conditions by Locking Out and Tagging Out all sources (LOTO)
Chapter 1, Section 120.2(D) of NFPA 70E
2.
Primarily covered by installation standards contained in the National Electric CodeCode-NFPA 70 The incidence of fire ignition has dropped dramatically since the advent of the NEC and the acceptance of installation requirements within the industry.
6/12/2013
Exposure to Danger
The National Electric Code protects individuals from shock hazards under normal conditions. It is not designed to protect us from abnormal conditions. We need additional policies to protect from abnormal conditions
Conditions
Normal Conditions
Panel covers in place Equipment plugged in normally Normal, designed protection in place
Abnormal Conditions
Panel covers removed. Equipment temporarily wired Damaged or Faulty Equipment Normal designed protection such as guards, limits switches, etc. not in place
6/12/2013
The Company
OSHA NFPA 70 E Electrical Safety Procedures Manual Electrical Safety Training
You
The first line of defense Only you can truly keep you safe Implement Safety Procedures Outlined in Safety Manual Only you can ensure that you go home at night
Dust, impurities, and corrosion at contact surfaces Dust, impurities, and corrosion at contact surfaces
Produces heat, loosening contact and creating sparks Sparks start arcs
Failure of insulating materials Snapping of leads at connections due to human, rodents or birds rodents or birds Accidental touching / dropping of tools, nuts-bolts, or bolts, or metal parts
6/12/2013
Old School
To consider circuits to be energized To insulate and protect ourselves Stand to one side if you suspect an arc flash/blast Use your left hand and turn away from operating handle
New School
Arc Flash and Blast hazards were not formally studied until 1993 (IEEE 1584 began study) Electricians have not experienced arc flash and blasts to the same frequency as electrical shock. We have not been trained how to avoid and minimize arc flash and blasts in the past. The Electrical Energized Work Practices outlined in NFPA 70E incorporates measures to help avoid or minimize damage from arc flash.
6/12/2013
Electric arcs produce the highest temperatures on earth up to 35,000 degrees Fahrenheit (4 x temp of the sun) The intense heat from arc causes the sudden expansion of air that results in a blast with very strong air pressure (Lightning is a natural arc). All known materials are vaporized at this temperature. (Copper expands 67,000 times, Water 1670 times).
NOTES ARE FROM NOTES ARE FROM Practical Solution Guide to Arc Flash Flash Hazards
Arcs in enclosures, such as a Motor Control Centers (MCCs ) or switchgear, magnify blast and (MCCs) energy transmitted as the blast is forced to the open side of the enclosure. Arcs spray droplets of molten metal at highhigh-speed pressure. Blast shrapnel can penetrate the body. Blast pressure waves have thrown workers across rooms and knocked them off ladders. Pressure on the chest can be higher than 2000 lbs/ sq. ft.
10
6/12/2013
Clothing can be ignited several feet away unless flameflame-resistant clothing is used. Hearing loss from sound blast. The sound can have a magnitude as high as 140 dB at a distance of 2 feet from the arc. Energy released is a function of: system voltage fault current magnitude fault duration
Practical Solution Guide to Arc Flash Hazards, By By Chet Davis, P.E.;et al
11
6/12/2013
Approach Boundaries
Approach Boundaries
NPFA 70E70E-2004 Ch. 1, Section 130.2 p24p24-25
Flash Protection Boundary linear distance to prevent any more than 2nd degree burns from a potential arcarc-flash (Typically 4 feet) Limited Approach Boundary entered only by qualified persons or unqualified persons that have been advised and are escorted by a qualified person Restricted Approach Boundary entered only by qualified persons required to use shock protection techniques and PPE Prohibited Approach Boundary entered only by qualified persons requiring same protection as if direct contact with live part
12
6/12/2013
10 ft for 480 V for movable energized object 3 ft 6 in. for fixed energized object
3.
Determine the Personnel Protective Equipment : Use Voltage Rated Gloves rated greater or equal to the voltage of the system Use Voltage Rated Tools rated greater or equal to the voltage of the system
13
6/12/2013
Flash Hazard
Ch. 1, Sec. 130.3 Flash Hazard Analysis.
A flash hazard analysis shall be done in order to protect personnel from the possibility of being injured by an arc flash. The analysis shall determine the Flash Protection Boundary and the personal protective equipment that people within the Flash Protection Boundary shall use. use.
How to Comply with NFPA 70E for FLASH Protection? 1.Determine the Flash Protection Boundary 2.Determine the incident energy exposure level 3.Determine the Protective Clothing and PPE
How to Comply with NFPA 70E for FLASH Protection? 1. Determine Flash Protection Boundary:
Calculate using the IShortShort-Circuit Amperes & the clearing time for the overcurrent protection (see Formula below & on Page 25 of NFPA 70E70E-2004 OR default to four feet 600 V or less @ 300 kA cycles per 130.3(A) of NFPA 70E70E-2004) Flash Protection Boundary Formula (600 V or less) DC= [53 x MVA x t] 1/2where Dc = Arc Flash Boundary (AFB) in FeetMVA = Transformer capacity in MVAt= MVAt= clearing time in seconds Second Degree Burn Threshold1.2 cal/cm1.2 cal/cm2
14
6/12/2013
How to Comply with NFPA 70E for FLASH Protection? 2.Determine 2.Determine the Incident Energy Level:
Calculate incident energy exposure level for the distance between worker workers face & chest from the potential arc source (18 (18 typical) OR use 130.7(C)(9) and 130.7(C)(10) Incident energy formula for Arc in a Cubic Box :
EMB= 1038.7DA-1.4738tA[0.0093F20.3453F + 5.9675] Where
EMB= cal/cm2in 20 inch Cubic Box DA= distance from electrode in inches (typically this value would be 18 18) tA= clearing time F= Ishortshort-Circuit Amperes available (range of 16 kA to 50 kA)
How to Comply with NFPA 70E for FLASH Protection? 3. Determine the Proper PPE: Once the incident energy is determined, the PPE has to have a rating equal to or greater than the incident energy available See 130.7(C)(11). If the alternate method is used: Use 130.7(C)(9) for the task, then the proper PPE is selected from 130.7(C)(10) of NFPA 70E70E-2004.
15
6/12/2013
Worker also require eye and hearing protection to be worn under the doubledouble-layer switching hood
Table 130.7(C)(9)
Untreated Natural Fiber TT-Shirt & Undergarments FR (8 cal/cm2) Long Sleeve Shirt & Pants Hard Hat Safety Glasses or Safety Goggles ArcArc-Rated Face Shield w/ Flash Hood or Tube Sock (Balaclava) Hearing Protection Leather Gloves Leather Work Shoes
16
6/12/2013
NEXT STEP IS TO VERIFY VOLTAGE IS OFF! Electrician goes to the machine disconnect to open and test for presence of voltage What is the HRC level? (Ans : 2*) (Ans:
ELECTRICAL HOT WORK PERMIT REQUIRED? (Ans : NO) (Ans:
17
6/12/2013
18
6/12/2013
19
6/12/2013
Step I Site Assessment and Electrical System Data Gathering Step II ShortShort-Circuit and Protective Device Coordination Studies and Arc Flash Analysis Step III Electrical Safe Work Practices Program Planning and Labeling of Electrical Panels, MCCs, MCCs, and Switchgear Step IV Electrical Safe Work Practices Training
20
6/12/2013
Step II Short-Circuit and Protective Device Coordination Studies and Arc Flash Analysis
Short Circuit Study Protective Device Coordination Study Arc Flash Analysis
21
6/12/2013
22
6/12/2013
23
6/12/2013
Step III Electrical Safe Work Practices, Program Planning and Labeling of Electrical Panels, MCCs, and Switchgear Develop Electrical Procedures Label Equipment Single Line Arc Flash Evaluation IEEE 1584 Bus Report
Step IV Electrical Safe Work Practices Training Develop Electrical Procedures Lockout/Tagout Personnel Protective Equipment Proper Tools Reference Manuals
NFPA 70E with Arc Flash NETA Safety book OSHA Standard Arc Flash Manual
24
6/12/2013
What Are the OSHA Regulations and NFPA 70E Requirements for Working on Live Equipment?
Shall
How
OSHAs general industry electrical safety standards are published in Title 29 Code of Federal Regulations (CFR), Part 1910.302 through 1910.308 Design Safety Standards for Electrical Systems, and 1910.331 through 1910.335 Electrical Safety-Related Work Practices Standards.
Title 8 Cal OSHA
OSHA also has electrical safety standards for the construction industry, in 29 CRF 1926, Subpart K. OSHAs standards for marine terminals, in 29 CFR 1917, and for longshoring, in 29 CFR 1918, reference the general industry electrical standards in Subpart S of Part 1910. The shipyard standards, in 29 CFR 1915, cover limited electrical safety work practices in 29 CFR 1915.181.
25
6/12/2013
Safety in Workplace
OSHA 1910.333 (a) (1) & NFPA 70E 130.1
Qualified electrical workers shall not be asked to work on equipment that is hot hot or live live except for two demonstrable reasons: 1. DeDe-energizing introduces additional or increased hazards e.g.
cutting ventilation to a hazardous location emergency alarm systems or
2.
(a) General.
SafetySafety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contact, when work is performed near or on equipment or circuits which are or may be energized. The specific safetysafety-related work practices shall be consistent with the nature and extent of the associated electrical hazards
26
6/12/2013
(a) (2) (B) (ii) Protective shields, protective barriers, or insulating materials shall be used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur.
The Employee
are both responsible to Coordinate and Document Hazards and Safety Procedures Contractors on working site [NFPA 70E70E-110.4(B)]
27
6/12/2013
The NFPA 70E was originally developed at OSHA OSHAs request to address electrical hazards in the workplace. OSHA bases its electrical safety requirements on the comprehensive information in NFPA 70E. Even though OSHA does not mandate compliance with NFPA 70E itself, it considers NFPA 70E to be an effective howhow-to manual for OSHA regulation compliance. OSHA 29 CFR 1910.132(d) (1) requires employers to evaluate the workplace for hazards. And based on these assessments, the employer must select and require the use of appropriate personal protective equipment (PPE) for its employees. Employers shall provide a safe environment.
OSHA uses General Duty Clause for the enforcement of safety on the job site.
Section 5(a) (1) of the WilliamsWilliams-Steiger Occupational Safety and Health Act of 1970 A. Each Employer: Shall furnish to each of his employees employment and a place of employment which are free from recognized hazards that are causing or likely to cause death or serious physical harm to his employees; Shall comply with occupational safety and health standards promulgated under this Act. B. Each employee Shall comply with occupational safety and health standards and all rules, regulations and orders issued pursuant to this Act which are applicable to his own actions and conduct.
28
6/12/2013
OSHA has not adopted adopted NFPA 70E simply because adoption would require a lengthy and expensive process OSHA has instead referenced compliance to NFPA 70E using Section 5(a) (1) of the Occupational Safety and Health Act of 1970, commonly referred to as the general duty clause, clause, as their basis for implementation. NFPA 70E The Industry Consensus Standard NFPA 70E compliance for an employer involves putting an electrical electrical safety program in place, which will identify and analyze electrical electrical hazards in the workplace, educate the workforce on those hazards, hazards, require the use of appropriate PPE, and implement warning labels and guards to protect the workers. An employer that fails to implement NFPA 70E could have a hard time proving that it exercised due diligence after an electrical accident if adherence to NFPA 70E standards would have prevented the accident.
If the following elements are present, a general duty clause clause citation may be issued to an employer. 1. The employers failed to keep the workplace free of a hazard to which employees of that employer or were exposed. 2. The hazard was recognized. 3. The hazard was causing or was likely to cause death or serious physical harm. 4. There was a feasible and useful method to correct the hazard.
29
6/12/2013
Article 1910.135(a) (1) the employer shall ensure that each affected affected employee wears a protective helmet when working in areas where there is a potential for injury to the head from falling objects. Article 1910.135(a) (2) The employer shall ensure that a protective protective helmet designed to reduce electrical shock hazard is worn by each such affected employee when near exposed electrical conductors which could contact contact the head. ANSI Z89.1 standard, Class E hard hat, 20kV
The failure to adequately provide needed PPE could easily lead to to a general duty clause citation.
30
6/12/2013
Safety First
Personnel that are Trained in CPR should be identified and available when working near or on energized parts. The first step must be to TURN THE POWER OFF
Electrical Accident
Steps to Take
Remove the Immediate Hazard: turn Off the Power Remember that Speed is Essential Extinguish flames Call for Help (911) Begin CPR & First Aid
First Aid
Cool the burn with water Do not attempt to remove burned clothing Elevate burned limbs Handle the victim with care Treat for shock Maintain body temperature Do not give anything by mouth
31
6/12/2013
CPR
Personnel that work near or on electrically energized parts should be trained in CPR. The use of Automatic Electronic Defibrillator (AED) is recommended.
Summary
Do an arc flash hazard analysis, and document the incident energy exposure
As an alternate, use the Hazard Risk Category Classifications table to choose the PPE level required for the task
32
6/12/2013
Specifying Current Limiting Fuses on Low Voltage Switchgear Breakers Specifying ARC Resistance Medium Voltage Switchgear Remote Control of Switchgear Breakers High Resistance Grounding on Low Voltage and Medium Voltage (15kV and below) Systems
Preventive maintenance to minimize arc flash potential Work HOT only when unavoidable and only under permit Wear all PPE Required NFPA 70E Tables must be used until calculation is performed
33
6/12/2013
Panels rated 208 V or less may not require protective clothing, but verify with arc flash analysis Analyze all locations where workers are exposed Identify circuits to reduce fault current
Safety Glasses Natural Fiber Long Sleeves Shirt Natural Fiber Long Pants Stand to the side and operate breakers
34
6/12/2013
Compliance with
NEC labeling requirements NFPA 70E for PPE requirements Establish procedures (Electrical Hot Work Permit)
Compliance with
NEC labeling requirements NFPA 70E for PPE requirements Establish procedures (Electrical Hot Work Permit)
35
6/12/2013