METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS.

(MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

TABLE OF CONTENTS

Item Description 1.0 Scope. 2.0 References. 3.0 Access / Egress 4.0 Health &Safety Hazards 4.1 Safety Rules during Testing. 4.2 Safety Lighting. 4.3 Task Lighting 4.4 Emergency Arrangements. 4.5 Risk and Controls. 5.0 Abbreviations and Definitions. 6.0 Roles/Responsibilities/Competence. 7.0 Testing and Commissioning Procedures.
7.1 Attachment 1- Method of Commissioning:

8.0 Training. 9.0 Working Hours. 10.0Manpower Requirement and Supervision. 11.0Test Instruments Requirements. 12.0Requirements. 12.1General Requirements. 13.0Personnel Equipment. 14.0Supporting Information. 15.0Distribution 16.0Other information

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

17.0Attachments 17.1Method of Commissioning : MDBs, MCCs, EMDBs & Capacitor Banks 17.2Method of Commissioning : SMDBs, ESMDBs &DBs. 17.3Method of Commissioning: VFD Panels. 17.4Calibration Certificates. 17.5Risk Assessment. 17.6Test Reports.

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

1.0

SCOPE

This Procedure Covers the Testing and Commissioning of Electrical Panels in the DUCAB HV & EHV
Facility. The MDBs, EMDBs and Capacitor banks are installed at the LV rooms, while MCC Panels are at VCV Tower roof, CCV Tower roof, EHV Test lab electrical room , Chiller plant area and mechanical plant room. EMCCs are located at VCV Tower roof, CCV Tower roof and Administration office first Floor. ESMDBs are installed at Factory area and VCV Tower electrical room (Ground floor). SMDBs and DBs are installed at all areas in the project as indicated on the service drawings. This procedure will also ensure proper workmanship and conforms to Contract documents, manufacturers instructions and standards.

2.0

REFERENCES
2.1 2.2 2.3 2.4 Approved MACAIR Shop Drawings for Power layout. (Ref: Ducab KB644/SD- 00107, 00108, 00161-00170, 00174-00176, 00187-00199, 00203, 01027,01324,01325 & 01485). MACAIR Project Quality Plan. MACAIR Safety Manual Manufacturers recommendations.

3.0

ACCESS /EGRESS
The Commissioning of the System will commence only when Main Contractor clearance is given for access to conduct the Testing and Commissioning.

4.0

HEALTH & SAFETY HAZARDS


Health and Safety procedures by Main Contractor and MACAIR will be implemented for this job. A routine safety check will be done by the Safety Officer In-charge as per MACAIR Safety Procedure. 4.1 Safety Rules During Commissioning In order to ensure safe conditions during testing the following rules have to be followed: 4.1.1 Persons engaged with this commissioning are experienced and have received proper and adequate training related to procedures and test equipment utilized for the particular testing activity. 4.1.2 Test instruments and test leads should be maintained in a safe condition and the test methods not to create danger either for the operator or for other persons. Safety Lighting Safety Lights will be used in case of power failure ensuring good illumination at the working area to aid evacuation if necessary.

4.2

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

4.3

Task Lighting Adequate lighting shall be provided to ensure good illumination at the working area.

4.4

Emergency Arrangements 4.4.1 General: Site Safety procedures will be followed and in case of any emergency, Safety Officer will administer the emergency arrangements as per the system, stop work and report to nearest Assembly Point, etc. Safety Officer Name : Mr. Reghupathy, (Con # 0559262923) Fire Precautions: No significant fire risks associated with this activity but general fire precaution measures will be taken. Communication: Via mobile phones issued to all engineers.

4.4.2 4.4.3 4.5

Risk and Controls 4.5.1 4.5.2 Please refer to the Risk Assessment attached in Section 17.6 Environmental considerations: There are no waste materials associated with this activity.

5.0

ABBREVIATIONS & DEFINITIONS MC PM PE PE SO QA/QC - Main Contractor (MACAIR) - Project Manager (MACAIR) - Project Engineer (MACAIR) - Project Engineer (Prime Electrical) - Safety Officer (MACAIR) - Quality Assurance/Quality Control (MACAIR)

6.0

ROLES/RESPONSIBILTY /COMPETENCE 6.1 6.2 6.3 6.4 PM - will have the overall responsibility of the Project for execution, quality and safety, maintain the planning and progress and coordination with Main Contractor. PE - will be responsible for day to day activities in the Site for System Testing and Commissioning, report preparation and demonstration of System Commissioning. PE (Prime Electrical) - will be directly responsible for the System commissioning. SO - will be responsible for Health and Safety aspects in the Site in line with Main Contractor Safety requirements.

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

6.5

QA/QC - will oversee the quality requirements and quality control measures for the Project.

7.0 TESTING AND COMMISSIONING PROCEDURES

Please refer to the attachments as follows; 7.1 7.2 7.3 7.4 7.5 7.6 7.7 8.0 Method of Commissioning : MDBs, MCCs & EMDBs. Method of Commissioning : Capacitor Banks Method of Commissioning : SMDBs, ESMDBs &DBs. Method of Commissioning: VFD Panels. Calibration Certificates. Risk Assessment. Test Reports.

TRAINING
8.1 8.2 Engineers who will conduct the Commissioning shall have the experience in System Commissioning. Tool Box talks will provide general training and awareness for each activity and also undergo further training by the Quality Assurance Department.

9.0

WORKING HOURS
Site Normal Working Hours.

10.0

MANPOWER REQUIREMENT & SUPERVISION


PM PE PE SO QA/QC - Project Manager (MACAIR) - Project Engineer (MACAIR) - Project Engineer (Prime Electricals) - Safety Officer (MACAIR) - Quality Assurance/Quality Control (MACAIR)

11.0

TEST INSTRUMENT REQUIREMENT


The following Test Instruments will be used for the Commissioning of the Electrical Panels. They will be selected as having the maximum field measuring accuracy and being the best suited to the function being measured and will be applied as recommended by the manufacturer.

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

11.1

Test Instruments
11.1.1 Megger. 11.1.2 High Pot Tester. 11.1.3 Torque wrench 11.1.4 Multimeter

11.2

Calibration 11.2.1 All Instruments used shall carry current calibration certificates. Calibration periods for all instruments are recommended by the manufacturer and are in line with the requirements of the Commissioning Specialist Association. 11.2.2 Certificates shall be available for presentation prior to commencement of commissioning.

12.0

REQUIREMENTS 12.1 General Requirements Before commencing commissioning works, the following information /items will be made available. 12.1.1 System is fully installed and pre-tested. 12.1.2 All equipment are available at site.

13.0

PERSONNEL EQUIPMENT 13.1 All Commissioning Engineers and Technicians shall have the necessary Personnel Protective Equipment such as Safety Shoes and Helmet.

14.0

SUPPORTING DOCUMENTATION 14.1 14.2 14.3 Approved Inspection of 1st Fix Installation. Approved Inspection of 2nd Fix Installation. Approved Inspection of Final Fix Installation

15.0

DISTRIBUTION 15.1 15.2 15.3 15.4 Main Contractor Consultant. MEP Senior Mechanical Engineer. Health and Safety Officer.

16.0

OTHER INFORMATION

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

Not applicable for this activity.

17.0

ATTACHMENTS

17.1 17.2 17.3 17.4 17.5 17.6 17.7

Method of Commissioning : MDBs, MCCs & EMDBs Method of Commissioning : Capacitor Banks Method of Commissioning : SMDBs, ESMDBs &DBs. Method of Commissioning: VFD Panels. Calibration Certificates. Risk Assessment. Test Reports.

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.1

Method of Commissioning: MDBs, MCCs, EMDBs

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.2

Method of Commissioning: Capacitor Banks

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.3

Method of Commissioning: SMDBs, ESMDBs &DBs.

10

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.4

Method of Commissioning: VFD Panels

11

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.5

Calibration Certificate

12

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.6

Risk Assessment

13

METHOD STATEMENT FOR TESTING AND COMMISSIONING OF ELECTRICAL PANELS. (MDBs, MCCs, CAPACITOR BANKS, EMDBS, SMDBs, ESMDBs & VFD PANELS)

CONTRACTOR: MACAIR / DOC.NO:MSREV: DATE : 03/02/2011

ATTACHMENT 17.7

Test Reports

14