You are on page 1of 1

Table of Asymmetrical Current Factors

System
X/R Ratio
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
20.0
30.0
40.0
50.0
100.0
infinity

Instantaneous
Peak Factor
1.4142
1.4142
1.4142
1.4149
1.4181
1.4250
1.4362
1.4511
1.4692
1.4897
1.5122
1.7560
1.9495
2.0892
2.1924
2.2708
2.3323
2.3817
2.4222
2.4561
2.6256
2.6890
2.7224
2.7427
2.7848
2.8284

Half-Cycle
Factor
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.001
1.002
1.002
1.042
1.115
1.191
1.263
1.304
1.347
1.381
1.412
1.438
1.570
1.618
1.643
1.662
1.697
1.732

Source:ElectricalSystemsDesign,TheodoreR.Bosela(2003)

Time of Peak
tp (ms)
4.2
4.4
4.7
4.9
5.2
5.4
5.5
5.7
5.8
5.9
6.1
6.8
7.1
7.4
7.5
7.6
7.7
7.8
7.8
7.9
8.1
8.2
8.2
8.2
8.3
8.3

You might also like