SITE ACCEPTANCE TEST RECORD

Description:

BB & INTEGRATED BF MAIN-2 BAY UNIT -7SS523

Contract No:

Date:

310311143/ 00
Contractor:

Site:

Panel/Bay Name:

NEW QAISUMAH 380/115/13.8 KV BSP

1. GENERAL DATA AND INFORMATION:


PANEL REFERENCE MANUFACTURE MODEL RATED CURRENT SERIAL NO. DRAWING REF DESIGNATION SIEMENS TYPE OF RELAY FIRMWARE VER AUX VOLTAGE CT RATIO

2. MECHANICAL CHECK AND VISUAL INSPECTION

Item
1 2 3

Description
Inspect for physical damage / defects. Verify connections as per approved drawing. Check tightness of all connections.

Remarks

3. ELECTRICAL TESTS:
3.1. FUNCTION TEST

Item
1 2 3 4 5

Description
Case Earthing checked. All Binary inputs checked All Binary Outputs checked Trip contacts checked. LED operations checked

Remarks

3.2. MEASUREMMENTS:
Measurements at Display (%) L1 L2 L3 LN

Applied Phase L1 L2 L3 L1-L2-L3

Applied Current (A) 1.0 1.0 1.0 1.0

Tested by: NCC Name : Signature:

Witnessed by: SEC-CSD

Name:
Signature:

P a g e | 1 of 3

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Description:

BB & INTEGRATED BF MAIN-2 BAY UNIT -7SS523

Contract No:

Date:

310311143/ 00
Contractor:

Site:

Panel/Bay Name:

NEW QAISUMAH 380/115/13.8 KV BSP

3.3 OVERCURRENT FUNCTION PHASE AND GROUND (Definite time) 3.3.1. II >

PHASE L1 L2 L3 N

I> SETTING (A) 1.0 1.0 1.0 0.2

PICKUP (A)

TIME SETTING( sec)

TIME MEASURED @2XIs (sec)

REMARKS

0.203

0.518

PASS

3.3.2. . I>> PHASE L1 L2 L3 N I>> SETTING (A) 2.0 2.0 2.0 0.5 PICKUP (A) TIME SETTING(se c) TIME MEASURED @2XIs (msec) REMARKS

3.3.3. INVERSE CHARACTERISTICS CHARACTERISTIC: NORMAL INVERSE PHASE L1 L2 L3 N CALCULATED TIME @ 10*Ip (sec)

Ip = 1 I/In Tp = 1.0 IEp =0.2 I/In TEp = 1.0 MEASURED TIME (sec) LIMIT REMARKS

3.4 BACKUP BREAKERFAIL PROTECTION:

Tested by: NCC Name : Signature:

Witnessed by: SEC-CSD

Name:
Signature:

P a g e | 2 of 3

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Description:

BB & INTEGRATED BF MAIN-2 BAY UNIT -7SS523

Contract No:

Date:

310311143/ 00
Contractor:

Site:

Panel/Bay Name:

NEW QAISUMAH 380/115/13.8 KV BSP


CURRENT THRESHOL D SETTING (A)

PHAS E L1 L2 L3

TIME SETTING( msec)

TIME MEASURED (msec)

REMARKS

3.5 MEASURED VALUE SUPERVISION


I = IL1 + IL2 + IL3 + IE | I | = | IL1 | + | IL2 | + | IL3 | + | IE | The measured value monitoring picks up if | I | > 0.2 I/IN Measured value pickup : 0.205 A 3.6 BINARY INPUT ASSIGNMENTS:

Tested by: NCC Name : Signature:

Witnessed by: SEC-CSD

Name:
Signature:

P a g e | 3 of 3

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Description:

BB & INTEGRATED BF MAIN-2 BAY UNIT -7SS523

Contract No:

Date:

310311143/ 00
Contractor:

Site:

Panel/Bay Name:

NEW QAISUMAH 380/115/13.8 KV BSP


S.No BI01 BI02 BI03 BI04 BI05 BI06 BI07 BI08 BI09 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 DESCRIPTION D754 Disconnector Open D754 Disconnector Close D755 Disconnector Open D755 Disconnector Close A720 CB Open A720 CB Close Spare Spare Spare Spare Protn Breaker fail Initiation Spare Spare Spare Spare Spare Spare Spare Spare Spare TERMINALS 20X48:1&2 20X48:3&4 20X48:5&6 20X48:7&8 20X48:9&10 20X48:11&12 20X48:13&14 20X48:15&16 20X48:17&18 20X48:19&20 20X43:1&2 20X43:3&4 20X43:5&6 20X48:21&22 20X48:23&24 20X48:25&26 20X48:27&28 20X48:29&30 20X48:31&32 20X48:33&34 STATUS REMARKS

Tested by: NCC Name : Signature:

Witnessed by: SEC-CSD

Name:
Signature:

P a g e | 4 of 3

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA

SITE ACCEPTANCE TEST RECORD


Description:

BB & INTEGRATED BF MAIN-2 BAY UNIT -7SS523

Contract No:

Date:

310311143/ 00
Contractor:

Site:

Panel/Bay Name:

NEW QAISUMAH 380/115/13.8 KV BSP

3.7 BINARY OUTPUT ASSIGNMENTS: B. DESCRIPTION TERMINALS O/P 5C4&5C3/6C4&6C K1 BF stage-1 trip 3 5C4&5C2/6C4&6C K2 BF stage-2 trip 2 Busbar diff trip/busbar 5C4&5C1/6C4&6C K3 K4 K5 M1 M2 intertrip Bay unit faulty Spare Bay out of service Watch dog contacts

STATUS

REMARKS

1 6D3&6D4/6D1&6D 2 5D3&5D4 7D1&7D2 8D1&8D2/8D3&8D 4

Tested by: NCC Name : Signature:

Witnessed by: SEC-CSD

Name:
Signature:

P a g e | 5 of 3

NATIONAL CONTRACTING CO. LTD., T&D CENTER, P.O. BOX 90, AL-KHOBAR-31952, KSA