COMMERCIAL HEAT PUMP

PERFORMANCE TABLES

HOW TO USE THE CHART


s For temperatures not on the table, averaging between two temperatures on the table will provide a reasonable estimate.
s For relative humidity values not on the table, estimates can be calculated by using the formula in the example below.
Example:

for a heating value for an AWH-35 at 70 DB and 55 EWT at 45% RH compare to the known value of 30,600
Btu/h at 70 DB and 55 EWT at 50% RH.
X = 45 x 30600
50

X Btu/h = New RH x Known Btu/h


Known RH

X = ~ 27,540 Btu/h

s Note: AWH unit performance has a slight curve through operating temperature and relative humidity ranges. The
calculations above produce a linear performance and should only be used for estimating purposes.
s The 80 dry bulb band is the proposed AHRI* rating point for commercial heat pump water heaters
s Recovery rate is calculated at 60 T with beginning water temperature of 70 and finishing water temperature of 130
s Minimum entering air temperature 50 F. Maximum entering air temperature 95 F.
*Air-conditioning, Heating and Refrigeration Institute

AWH-35
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

22800
22500
22200
26400
26100
25400
30600
30100
28900
35300
34600
32900
43500
42500
39700

17300
16400
13600
20800
19700
16600
24700
23600
19900
29200
27900
23700
37000
35400
30100

4.1
3.6
2.6
4.7
4.1
2.9
5.2
4.6
3.2
5.8
5.1
3.6
6.7
6.0
4.1

1.62
1.81
2.53
1.66
1.86
2.58
1.72
1.91
2.64
1.78
1.97
2.71
1.90
2.09
2.82

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

37500
37100
36600
43400
42900
41900
50300
49500
47700
58000
57000
54300
71500
69900
65600

28900
27400
22800
34600
32900
27700
41100
39200
33200
48500
46300
39300
61300
58600
49900

4.3
3.8
2.6
4.9
4.3
3.0
5.5
4.8
3.3
6.1
5.3
3.6
7.0
6.2
4.2

2.53
2.85
4.05
2.60
2.93
4.16
2.70
3.02
4.26
2.80
3.13
4.38
3.00
3.32
4.59

Recovery
Rate
(GPH)

45

51

59

67

81

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

23500
23200
22700
27400
27000
26000
32000
31500
30000
37200
36500
34500
45900
44700
41600

17900
17000
14000
21700
20600
17200
26100
24900
21000
31100
29700
25100
39300
37500
31800

4.2
3.7
2.6
4.8
4.2
2.9
5.4
4.8
3.3
6.0
5.3
3.7
6.9
6.2
4.3

1.63
1.82
2.54
1.67
1.87
2.59
1.74
1.93
2.66
1.81
2.00
2.74
1.94
2.12
2.86

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

38600
38200
37400
45100
44500
43000
52600
51800
49600
61200
60100
56900
75500
73700
68700

29900
28400
23600
36200
34400
28700
43300
41300
34900
51500
49200
41800
65000
62100
52800

4.5
3.9
2.7
5.0
4.4
3.0
5.7
5.0
3.4
6.3
5.5
3.8
7.2
6.4
4.3

2.54
2.87
4.06
2.62
2.96
4.17
2.73
3.06
4.29
2.85
3.18
4.43
3.07
3.38
4.64

Recovery
Rate
(GPH)

46

53

61

70

85

AWH-55
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH
Recovery
Rate
(GPH)

74

85

97

110

134

Recovery
Rate
(GPH)

76

87

101

116

141

Recovery from 70F to 130F


April 2011R

Page 1 of 4

AOSTD63170

COMMERCIAL HEAT PUMP


PERFORMANCE TABLES
AWH-75
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

50400
49900
49200
58400
57500
55900
67600
66300
63500
77800
76100
71800
95800
93200
86300

38600
36700
30100
46000
43800
36300
54600
52000
43300
64200
61200
51200
81300
77600
65300

4.3
3.8
2.6
4.7
4.2
2.9
5.2
4.6
3.2
5.7
5.1
3.5
6.6
6.0
4.1

3.46
3.87
5.58
3.62
4.01
5.74
3.80
4.19
5.90
3.98
4.36
6.03
4.24
4.58
6.16

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

65700
64900
63400
76100
75000
72300
88000
86400
82200
101300
99100
93000
124100
120800
111300

51400
48900
40300
61200
58300
48500
72400
69100
57800
84900
81000
68100
106700
102000
86000

4.6
4.1
2.7
5.1
4.5
3.0
5.6
5.0
3.4
6.2
5.5
3.7
7.1
6.4
4.4

4.18
4.70
6.78
4.36
4.88
6.97
4.58
5.08
7.15
4.80
5.28
7.29
5.09
5.51
7.40

Recovery
Rate
(GPH)

99

113

129

146

177

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

51900
51300
50300
60700
59600
57400
70600
69200
65800
82100
80200
75200
101100
98100
90300

40000
38000
31100
48200
45800
37700
57500
54800
45600
68200
65100
54500
86400
82400
69200

4.4
3.9
2.6
4.9
4.3
2.9
5.4
4.8
3.2
5.9
5.3
3.6
6.9
6.2
4.3

3.49
3.89
5.61
3.66
4.06
5.77
3.85
4.24
5.94
4.05
4.42
6.08
4.30
4.61
6.17

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

67600
66700
64700
78900
77500
74000
92000
90200
85200
106800
104300
97200
130600
126900
116200

53200
50500
41500
63900
60700
50100
76100
72600
60600
90100
86000
72200
113000
108000
90900

4.7
4.1
2.8
5.2
4.6
3.1
5.8
5.1
3.5
6.4
5.7
3.9
7.4
6.7
4.6

4.21
4.73
6.80
4.42
4.92
7.00
4.65
5.14
7.20
4.89
5.35
7.34
5.15
5.54
7.39

Recovery
Rate
(GPH)

101

116

134

153

185

AWH-100
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH
Recovery
Rate
(GPH)

128

146

167

190

228

Recovery
Rate
(GPH)

131

150

173

199

239

AWH-115
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

75300
74400
73200
87200
85900
83300
100800
98900
94500
116000
113400
106900
142300
138400
127700

59000
56100
46400
70200
66800
55700
82900
79100
66200
97200
92700
77900
122300
116700
98300

4.6
4.1
2.7
5.1
4.5
3.0
5.6
5.0
3.3
6.2
5.5
3.7
7.1
6.4
4.3

4.76
5.36
7.86
4.98
5.58
8.08
5.24
5.82
8.30
5.50
6.05
8.48
5.85
6.34
8.63

Recovery
Rate
(GPH)

147

168

192

218

262

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

77500
76500
74700
90400
88900
85300
105400
103300
97900
122300
119400
111600
149900
145400
133400

61100
58000
47800
73200
69600
57600
87200
83100
69400
103200
98400
82500
129700
123600
103900

4.7
4.1
2.8
5.3
4.6
3.1
5.8
5.1
3.4
6.4
5.7
3.8
7.4
6.7
4.5

4.80
5.40
7.89
5.04
5.64
8.12
5.32
5.90
8.35
5.60
6.14
8.53
5.92
6.38
8.64

Recovery
Rate
(GPH)

151

173

199

228

274

Recovery from 70F to 130F


April 2011R

Page 2 of 4

AOSTD63170

COMMERCIAL HEAT PUMP


PERFORMANCE TABLES
AWH-140
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

92700
91900
90500
107500
106100
102800
124900
122500
116800
144700
141300
132700
180000
174800
161100

71300
67800
56000
85100
81000
67400
101400
96400
80400
120000
113900
95100
153100
145400
121400

4.3
3.8
2.6
4.8
4.2
2.9
5.3
4.7
3.2
5.9
5.2
3.5
6.7
5.9
4.1

6.28
7.07
10.10
6.56
7.35
10.37
6.88
7.66
10.68
7.24
8.01
11.02
7.86
8.63
11.62

Recovery
Rate
(GPH)

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

95600
94600
92500
112000
110100
105600
130700
128100
121400
152800
149100
139300
190800
185000
169300

73900
70200
57900
89300
84800
70000
106900
101600
84600
127600
121300
101200
163300
154900
129000

4.4
3.9
2.7
4.9
4.3
3.0
5.5
4.8
3.3
6.1
5.4
3.7
6.9
6.2
4.2

6.34
7.13
10.14
6.64
7.42
10.43
6.98
7.76
10.78
7.38
8.16
11.16
8.05
8.81
11.79

182

208

237

270

330

Recovery
Rate
(GPH)

187

214

247

285

348

AWH-170
Dry
Bulb
Temp.
F

50

60

70

80

95

50% RH

60% RH

Entering
Water
Temp.
F

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

55
70
110
55
70
110
55
70
110
55
70
110
55
70
110

113400
112500
110100
131200
129700
125300
149600
142600
144300
175200
172100
162300
217000
212400
197400

86900
82600
68100
103700
98900
82300
123200
117500
98300
145200
138600
116400
184500
176200
148400

4.3
3.8
2.6
4.8
4.2
2.9
5.3
4.7
3.2
5.8
5.1
3.5
6.7
5.9
4.0

7.78
8.75
12.30
8.06
9.04
12.61
8.26
8.96
13.14
8.78
9.81
13.45
9.53
10.62
14.33

Recovery
Rate
(GPH)

Heating
Capacity
(BTUH)

Cooling
Capacity
(BTUH)

C.O.P

kW
Input

116700
115600
112500
136200
134400
128600
158800
156200
148100
185000
181500
170200
229700
224400
207300

90000
85600
70300
108500
103200
85300
129800
123800
103400
154400
147400
123700
196300
187300
157500

4.4
3.8
2.7
4.9
4.3
3.0
5.5
4.8
3.3
6.1
5.3
3.7
6.9
6.0
4.2

7.83
8.80
12.35
8.13
9.13
12.69
8.50
9.51
13.11
8.95
9.99
13.64
9.78
10.87
14.60

222

254

290

331

404

Recovery
Rate
(GPH)

227

261

302

348

426

Recovery from 70F to 130F

COMMERCIAL HEAT PUMP ELECTRICAL PERFORMANCE TABLE


COMPRESSOR
LRA
MCC

BLOWER MOTOR
FLA
HP

PUMP (230V/1PH)
FLA
HP

Model

V / Ph / Hz

AWH-35
AWH-35
AWH-35

208-230/1/60
208-230/3/60
460/3/60

18.60
10.90
5.40

100.00
77.00
39.00

29.00
17.00
8.50

3.60
2.3-2.4
1.20

1/2
1/2
1/2

0.88
0.88
0.88

AWH-55
AWH-55
AWH-55

208-230/1/60
208-230/3/60
460/3/60

27.90
19.90
8.70

175.00
115.00
63.00

43.50
31.00
13.50

5.30
2.9-3
1.50

3/4
3/4
3/4

AWH-75
AWH-75

208-230/3/60
460/3/60

24.00
11.50

196.00
100.00

37.50
18.00

3.5-3.6
1.80

AWH-100
AWH-100

208-230/3/60
460/3/60

28.20
14.10

225.00
114.00

44.00
22.00

AWH-115
AWH-115

208-230/3/60
460/3/60

35.30
17.90

239.00
125.00

AWH-140
AWH-140

208-230/3/60
460/3/60

48.10
21.80

AWH-170
AWH-170

208-230/3/60
460/3/60

52.60
25.60

RLA

MCA

MFS

1/8
1/8
1/8

28
17
9

45
25
12

0.88
0.88
0.88

1/8
1/8
1/8

42
29
13

60
45
20

1
1

0.88
0.88

1/8
1/8

35
17

50
25

3.5-3.6
1.80

1
1

0.88
0.88

1/8
1/8

40
20

60
30

55.00
28.00

3.5-3.6
1.80

1
1

1.00
1.00

1/6
1/6

49
25

80
40

300.00
150.00

75.00
34.00

4.8-4.8
2.40

1 1/2
1 1/2

1.00
1.00

1/6
1/6

66
31

110
50

340.00
173.00

82.00
40.00

6.2-6.2
3.10

2
2

2.50
2.50

1/2
1/2

75
37

125
60

RLA = Running Load Amps LRA = Locked Rotor Amps MCC = Maximum Continuous Current

April 2011R

FLA = Full Load Amps MCA = Minimum Circuit Ampacity MFS = Maximum Fuse Size

Page 3 of 4

AOSTD63170

COMMERCIAL HEAT PUMP


DIMENSION TABLES

Dimensions common to all units


1
2

7/8" electrical pilot holes for power and control


2" unit foot

AWH Dimension Table


Overall
Dimensions
(inches)

Model

Supply Air
Dimensions
(inches)

Filter Area
Dimensions
(inches)

AWH-35

24.75

40

26

14

17.5

17.75

20.25

21.5

AWH-55

28.5

47

32

16

20

20.5

24

25

AWH-75

28.5

57

32

18

22

24

24

AWH-100

42.5

63

38

22

26

28

AWH-115

42.5

63

38

22

26

28

AWH-140

42.5

63

38

24

28

AWH-170

42.5

75

46

28

32

A = Height
B = Width
C = Depth

AOSTD63170

27

4.375

0.75

11

35

2.5

4.375

0.75

11

25

47

1.5

4.375

1.5

0.75

11

38

39.25

49.5

1.5

4.875

1.5

16

38

39.25

49.5

1.5

4.875

1.5

16

28

38

39.25

49.5

2.5

4.875

1.5

16

34

38

39.25

63.75

1.5

4.875

16

D = Supply Flange Dimension


E = Supply Flange Height Locator
F = Supply Flange Horizontal Locator
G = Filter Height

Page 4 of 4

Piping Locators
(inches)

H = Filter Height Locator


I = Filter Horizontal
J = Filter Horizontal Locator
K = Entering Water X-axis Locator

A. O. Smith Corp., 2011

L = Condensate Connection X-axis Locator


M = Entering/Leaving Water Connections * FPT
N = Condensate Connection Size * FPT
O = Power Pilot Hole Y-axis Locator

Printed in U. S. A.