You are on page 1of 5

Capacidad de la acometida

Piso

Corriente(A)

Acometida

Nivel calle

131.65

2#2/0 + 1#1/0 + 1#10 THW , 4 pvc

Mezzanine

140

2#3/0 + 1#2/0 + 1#10 THW , 4 pvc

258.86

2#300 + 1#250 + 1 #10 THW, 4 pvc

367.82

2#500 + 1#400 + 1#10 THW , 4 pvc

3 al 14

457.82

2#750 + 1#600 + 1#10 THW , 4 pvc

15 al 16

452

2#750 + 1#600 + 1#10 THW , 4 pvc

17

447.13

2#750 + 1#600 + 1#10 THW , 4 pvc

18

484.17

2#1000 + 1#750 + 1#10 THW, 4 pvc

19

326.08

2#500 + 1#400 + 1#10 THW , 4 pvc

20

340.17

2#500 + 1#400 + 1#10 THW , 4 pvc

Ascensores
Cantidad

HP

Ic

Ip

40

115.03

230.07

80

230.07

460.15

Proteccin

Acometida
3#250 + 1#4/0 + 1#10 THW
2 PVC

T
3 X500 AMP

A
S
C
E
N
S
O
R
E
S

3X125 A

3X125 A
A
S
C
E
N
S
O
R
E
S

3X125 A

3X125 A

1
1

A
S
C
E
N
S
O
R
E
S
A
S
C
E
N
S
O
R
E
S

Breaker usado para el ascensor

Voltaje de Operacin:

120 Vac,120/240 Vac,125 Vdc,240 Vac,250 Vdc,277


Vac,480 Vac,500 Vdc,600 Vac MV

Capacidad de
Corriente:

500 Amp

Polos:

3 Tripolar

Dimensiones:

cm

Peso:

Gramo

Temperatura de
Operacin:
Tiempo de Respuesta: Segundo
Material:
Tipo:

TJK 636500WL

Icc:

Amp

Hidroneumtico
Cantidad

HP

Ic

Ip

25

71.88

143.77

50

143.79

323.54

R
H
I
D
R
O
N
E
U
M
A
T
I
C
O

3X150 A

Proteccin

Acometida
3#1/0 + 1#2 + 1#10 THW 2
PVC

3 X 350 AMP

3X150 A

H
I
D
R
O
N
E
U
M
A
T
I
C
O

Breaker usado para el Hidroneumtico

Voltaje de Operacin:

120 Vac,120/240 Vac,125 Vdc,240 Vac,250 Vdc,277


Vac,480 Vac,500 Vdc,600 Vac MV

Capacidad de
Corriente:

350 Amp

Polos:

3 Tripolar

Dimensiones:

cm

Peso:

Gramo

Temperatura de
Operacin:
Tiempo de Respuesta: Segundo
Material:
Tipo:

TJK 436350WL

Icc:

Amp