You are on page 1of 72

Bulletin 331-E Metric

NEW!
!
O
V
NUO
!
U
A
E
NOUV
NEU!
A DVANCED T ECHNOLOGY

IN

I N D U C E D D R A F T, C O U N T E R F L O W C O O L I N G T O W E R S
139 to 18144 kW NOMINAL CAPACITY

TECHNOLOGY

FOR THE

C E RTI F I E D

Mr. GoodTower

F U T U R E . . . A V A I L A B L E T O D AY !

E N

I S O

9 0 0 1 : 2 0 0 0

T HE A DVANCED T ECHNOLOGY D ESI GN


EVAPCO, Inc., continues its dedication to
advancements in induced draft counterflow cooling
tower technology and easy maintenance by proudly
introducing the NEW CTI Certified and IBC compliant
Advanced Technology Cooling Tower.

Easiest Maintenance with


Highest Efficiency

EVAPCOs success has been the


result of a continual commitment
to product improvement, quality
workmanship and a dedication to
providing unparalleled service.

The Z-725 Mill Hot-Dip Galvanized Steel


Construction is the heaviest level of
galvanizing available for manufacturing
cooling towers and has more zinc protection
than competitive designs
using Z-275 and Z-600 steel.
ZINC

Z-725

Z-600

Z-2

STEEL
ZINC

EVAPCO

OTHERS

75

Mill hot-dip galvanized steel has been


successfully used for over 25 years for the
protection of cooling towers against
corrosion.

Our emphasis on research and


development has led to many product innovations a hallmark of
EVAPCO through the years.
The ongoing R & D Program
enables EVAPCO to provide the
most advanced products in the
industry technology for the
future, available today.
With 17 facilities in eight countries
and over 170 sales offices in 42
countries world-wide, EVAPCO is
ready to assist in all your equipment needs.

There are various grades of mill galvanized


steel each with differing amounts of zinc
protection. EVAPCO has been a leader in
the industry in developing heavier
galvanizing, and was the first to standardize
on Z-725 mill hot-dip galvanized steel.
Z-725 designation means there is a
minimum of 725 g/m2 of surface area as
measured in a triple spot test.

Z-725 Galvanized Steel

ince its founding in 1976,


EVAPCO, Inc. has become a
world-wide leader in supplying quality cooling equipment for
thousands of customers in both the
commercial and industrial markets.

The AT Cooling Tower is corrosion


protected by the EVAPCOAT
Corrosion Protection System

During fabrication, all panel edges are


coated with a 95% pure zinc-rich compound
for extended corrosion resistance.

EVAPCOAT - Corrosion Protection System consists of:


Z-725 Galvanized Steel Construction.
Stainless steel suction strainer eliminates excessive wear and
corrosion.
Non-corrosive PVC Water Distribution System, Drift Eliminators
and Inlet Louvers.

PROVIDING EASIER SOLUTIONS

AND

BETTER CHOICES

The AT/UAT is the result of a tradition of engineering success based on easy maintenance,
durable construction and a highly efficient design. The AT/UAT brings marquee features
that make the AT/UAT the best choice in cooling towers.

The Ultimate Corrosion


Protection

Stainless Steel AISI 304

EVAPCO offers the UAT cooling tower with a


standard Type 316 stainless steel lower section
and 304 stainless steel upper section. Since the
cold water basin provides the structural support
for the unit and is the area most susceptible to
corrosion, it is constructed with the highest
quality materials. The UAT is the ONLY cooling
tower in the industry that offers this protection
as standard.

Stainless Steel AISI 316

The chemical compositions of Type 304 and 316


stainless steel are similar. However, there are
several differences in their makeup that allow
Type 316 SS to have better corrosion resistance
than Type 304 SS. Type 316 SS contains
molybdenum (304 SS does not) and has a
greater percentage of nickel than Type 304 SS.
Type 316 SS provides superior corrosion
resistance to a wide variety of environments.
Also, resistance of stainless steels to pitting
and/or crevice corrosion in the presence of
chloride or other halide ions is enhanced by
molybdenum content.
Type 316 SS material offers the best protection
against corrosion. Once again, EVAPCO raises
the quality standard in the cooling tower
industry with the UAT!
The UAT can be upgraded to complete
Type 316 SS construction.

The Ultra-AT is a 100% corrosion resistant cooling tower constructed of stainless steel.
The premium components include:
Type 304 Stainless Steel: Upper casing and structure Mechanical equipment support Fan Cowl
PVC: Patented Evapak Fill Water distribution system Air inlet louvers Drift eliminators
Type 316 Stainless Steel: Cold water basin Vertical support columns Air inlet louver frames

T HE A DVANCED T ECHNOLOGY D ESI GN

Technical Support Services

Available in 55 Cross Sections and a range of 139 to 18144


kW Nominal Capacity, the AT/UAT has a model for every
application. If there is an application for which the
standard catalog product line does not work, EVAPCO will
make a cooling tower that will fit your requirement!
Consult your local EVAPCO Representative for a cooling
tower solution.

EVAPCOs Website
Log on to EVAPCOs website
http://www.evapco.eu for expanded product information. Users can
download Product Literature,
Rigging
and
Maintenance
Instructions from their computer.
The iES Equipment Selection
Software program may be accessed
using Microsoft Internet Explorer
after contacting your local EVAPCO
sales representative. Users may
make Requests for Quotation
through the website or by e-mailing EVAPCO at this address:
evapco.europe@evapco.eu
With the internet Equipment
Solution program, equipment
selections, written specifications,
unit drawing files and EVAPCO online information are readily available from the comfort of your own
office!

Totally Enclosed Fan Motors


Motors positioned for external access.
Assures long life.
Motor location allows for easy accessibility
and serviceability.

EVAPCO Power-Band Drive System


The AT Cooling Tower features the highly successful, easy
maintenance, heavy duty Power-Band Drive System.
Standard heavy-duty pillow block bearings with a minimum
L10 life of 75.000 hours.
Extended lube lines.
External motor/belt adjustment.
Aluminum Alloy Sheaves in moist airstream, Solid-Back
Multi-Groove Power-Band Belts and Totally Enclosed
motors are standard.

NEW!
Louver Access Door
Hinged access panel with
quick release mechanism
Allows easy access to
perform routine maintenance and inspection of
the makeup assembly,
strainer screen and basin
Available on larger models

internet Equipment Solution


iES is a Web based computer selection program which allows the
design engineer to choose EVAPCO
models and optimize unit selections. The program allows the engineer to evaluate the equipments
thermal performance, space and
energy requirements. Once the
model is selected and optional
equipment features are inserted,
the engineer may output a complete specification AND a unit
drawing from this program. The
software is designed to provide the
user with maximum flexibility in
analyzing the various selection
parameters while in a friendly and
familiar Windows format.
The iES software is available to all
consulting engineering offices and
contractors.

NEW!
Easy Field Assembly
A new field assembly seam
design which ensures easier
assembly and reduced
potential for field seam leaks
Self-guided channels guide
the fan casing section into
position improving the
quality of the field seam
Eliminates up to 66%
of fasteners

WST Air Inlet Louvers


(Water and Sight Tight)
Easily removable for access.
Optimized design keeps sunlight outpreventing biological
growth.
Keeps water in while keeping
dirt and debris out
Patent pending

AND

BETTER CHOICES
ENGINEERING

PROVIDING EASIER SOLUTIONS

CTI Certified

Low Sound Options


available

Refer to page 23
for details

Refer to page 15 for details

Super Low Sound Fan


(optional)
Extremely wide sloped fan
blades for sound sensitive
applications.
One piece molded heavy
duty construction.
9-15 dB(A) sound reduction.

APPLICATIONS

SOUND

Soft-connect blade to
hub design.
VFD-friendly
Eliminates critical blade passing
frequencies at any speed.

IBC

Smooth Flow Fan

NEW! EvapJet Nozzle

Water Distribution System

MAINTENANCE

OPTIONS

Non-corrosive PVC construction with new EvapJet


nozzles.
Large orifice nozzles prevent clogging and are
threaded for easy removal and positive positioning.
66% fewer nozzles!
System branches have threaded end caps to assist
with debris removal.

Clean Pan Sloped Basin


Design

IBC Compliant
Design
Refer to page 21
for details

Certificate of Compliance
AT, USS, UAT, UT Cooling Towers
ATW Closed Circuit Coolers
HTC, ATC-E Evaporative Condensers
Are certified to meet or exceed the Seismic and Wind Load Provisions
set forth in the applicable building codes for this project.
These products have been manufactured following all
applicable quality assurance programs.
Applicable Building Codes:
IBC 2006
ASCE-7
NFPA 5000

Referenced Report:
VMA-43387
Approval Agency:
VMC Seismic Consulting Group

EVAPCO...Specialists in Heat Transfer Products and Services.

Designed to completely drain


the cold water basin.
Helps prevent buildup of
sediment and biological film.
Eliminates standing water
after drain down.

ID IBC COC 001

Mark owned by the Cooling Technology Institute

DESIGN

CTI

Fast, On-Time Shipments. The AT/UAT is a completely factory assembled


cooling tower manufactured by a dedicated professional workforce,
experts in building cooling towers. Factory trained mechanics and
EVAPCOs strict quality control and inspection procedures guarantee
the quality of every unit shipped. EVAPCOs controlled factory
environment ensures fast on-time shipments, allowing the AT/UAT
to be available WHEN THE CUSTOMER WANTS IT!

A S Y

O L U T I O N S

E T T E R

H O I C E S

D E S I G N F E AT U R E S
The Advanced Technology Design
The AT/UAT Cooling Tower product line is an Advanced Technology design which utilizes induced draft, counterflow technologythe most efficient in the industry and the best design for operation in a freezing climate. The counterflow design provides the AT/UAT Cooling Tower with inherently better operational and maintenance features. These features
are described below.

Principle of Operation, Reduced Air Circulation

Hot Saturated Discharge Air

Hot Water In

Cool Dry
Entering Air
Cooled
Water Out

Warm water from the heat source is pumped to the water distribution system
at the top of the tower. The water is distributed over the wet deck fill by
means of large orifice nozzles. Simultaneously, air is drawn in through the air
inlet louvers at the base of the tower and travels upward through the wet
deck fill opposite the water flow. A small portion of the water is evaporated
which removes the heat from the remaining water. The warm moist air is
drawn to the top of the cooling tower by the fan and discharged to the
atmosphere. The cooled water drains to the basin at the bottom of the tower
and is returned to the heat source.
The vertical air discharge of the AT/UAT design and the distance between the
discharge air and fresh air intakes, reduces the chance of air recirculation,
since the warm humid air is directed up and away from the unit. For detailed
layout information please consult EVAPCOs Equipment Layout Guidelines
Bulletin 311.

Patented High Efficient Drift Eliminators


An extremely efficient drift eliminator system is standard on the AT/UAT
Cooling Tower. The system removes entrained water droplets from the air
stream to limit the drift rate to less than 0.001% of the recirculating water rate.
With a low drift rate, the AT/UAT Cooling Tower rejects less water and water
treatment chemicals. The AT/UAT can be located in areas where minimum
water carryover is critical, such as parking lots.
The drift eliminators are constructed of an inert polyvinyl chloride (PVC) plastic
material which effectively eliminates corrosion of these vital components.
They are assembled in sections to facilitate easy removal for inspection of the
water distribution system.

Patented EVAPAK Fill

The Evapak film type fill design used in the AT/UAT Cooling Tower line is
specially designed to induce highly turbulent mixing of the air and water for
heat transfer. Special drainage tips allow high water loadings without excessive
pressure drop. The fill is constructed of inert polyvinyl chloride, (PVC). It will not
rot or decay and is formulated to withstand water temperatures of 55C. The
fill also has excellent fire resistant qualities providing a flame spread rating of
5 per ASTM-E84-81a. (The flame spread rating scale ranges from 0 for noncombustible to 100 for highly combustible). Because of the unique way in
which the cross-fluted sheets are bonded together, the structural integrity of
the fill is greatly enhanced, making the fill usable as a working platform.
A high temperature fill is available for water temperatures exceeding 55C.
Consult your EVAPCO representative for further details.

Superior WST Air Inlet Louver and Screen Design

DESIGN

EVAPCOS WST Inlet Louvers keep water in and sunlight out of the basins of
induced draft products. The unique non-planar design is made from lightweight PVC sections which easily fit together and have no loose hardware,
enabling easy basin access.
Developed with computational fluid dynamics (CFD) software, the louvers
air channels are optimized to maintain fluid dynamic and thermodynamic
efficiency and block all line-of-sight paths into the basin eliminating splashout, even when the fans are off. Additionally, algae growth is minimized by
blocking all sunlight.
The combination of easy basin access, no splash-out and minimized algae
growth saves the end user money on maintenance hours, water consumption and water treatment costs.
The patent of the latest WST louver is pending.

A S Y

O L U T I O N S

E T T E R

H O I C E S

D E S I G N F E AT U R E S
Reduced Piping Costs
Each cell of the AT/UAT Cooling Tower is furnished
with one inlet and one outlet piping connection. This
design reduces the amount of external piping and
thereby lowers the installed cost of the cooling tower.
The water distribution system is pressurized and self
balancing. Since field balancing is not required on the
AT/UAT, the need for flow balancing valves is eliminated, further reducing the cost of tower installation.
The wide orifice nozzles with anti-sludge ring used in
the AT/UAT water distribution system helps prevent
clogging, reducing the maintenance costs of the water
distribution system.

Pressurized Water Distribution System


The water distribution system is made of schedule 40
PVC pipe and ABS plastic water diffusers for corrosion
protection in this key area. The piping is easily removable for cleaning. The water diffusers have a large
orifice and are practically impossible to clog. In addition, the spray branches have threaded end caps to
allow easy debris removal.

All AT/UAT units have as per standard


the EvapJet Nozzle to ensure that
every square meter of heat transfer
surface receives complete and even
water coverage, resulting in maximum thermal performance.

Previous
EVAPCO
Nozzle

NEW
EvapJet Nozzle

Optimum Design for Freezing Climates


18 C Entering Water Temperature

Water
Temperature

12.8 C

The even temperature gradient of the counterflow fill


design makes the AT/UAT Cooling Tower the ideal unit
for operation in freezing climates.

10 C
7.2 C

Entering
Entering Air
Air at
at -12
10 FC Wet-Bulb
10
Wet-Bulb Temperature
Temperature

6.9 C Net
Outlet Water
Temperature

The counterflow design of the AT/UAT Cooling Tower


fill section reduces the chance of ice formation and
with bottom support, eliminates fill collapse should ice
form.

DESIGN

15.6 C

The counterflow fill design used in the AT/UAT Cooling


Tower is well suited for winter operation. The wet
deck surface is totally encased, and protected from
freezing winds thus inhibiting ice formation on the fill
section.

A S Y

O L U T I O N S

E T T E R

H O I C E S

M A I N T E N A N C E F E AT U R E S
The Advanced Technology Easy Maintenance Basin Design
The cold water basin is the most important area of a cooling tower to maintain. As a result of the evaporation process in a cooling tower, dirt and debris will collect in the basin and must be cleaned out on a regular basis. EVAPCOs AT/UAT basin section is
designed to allow quick and easy access -promoting maintenance of the cold water basin. The basin features the following:

Easy Access
The cold water basin section is easily accessible by simply removing the (2)
two Quick Release Fasteners on the inlet louver assemblies surrounding
the cooling tower and lifting out the lightweight louver.
The basin of 2,4 m wide and bigger units can be accessed from all (4) four
sides of the cooling tower. The bottom of the fill section of 2,4 m wide
and bigger units is a minimum of 1,2 m above the basin floor. This open
basin design enables the AT/UAT basin to be easily cleaned.

Louver Access Door (optional)


To aid in basin maintenance, all AT/UAT models can be equipped
with an optional louver access door. This feature allows easy
access to perform routine maintenance and inspection of the
makeup assembly, strainer screen and basin without removing an
entire inlet louver. The louver access door is standard on models
with 1,5 and 1,8 m tall louver sizes.

Easy, Removable Air Inlet Louvers with Quick


Release Fasteners
The AT/UAT features a Quick Release Fastener design consisting of (2)
two large thumbscrews and a retaining bracket system. By loosening the
thumbscrews, the retaining bracket lifts away from the louver frame, allowing the louver to be removed while the retaining bracket and thumbscrews
stay on the cooling tower.
Design allows quick removal of louvers.
Louver fastener is large and easy to release.
Louver fastener remains on the uniteliminating the possibility of
missing hardware

Clean Pan Basin Design


The AT/UAT features a completely sloped basin from the upper to lower
pan section (1,2 m wide units have no step). This Clean Pan design allows
the water to be completely drained from the basin. The cooling tower
water will drain from the upper section to the depressed lower pan section
where the dirt and debris can be easily flushed out through the drain.
This design helps prevent buildup of sedimentary deposits, biological films
and minimizes standing water.

Stainless Steel Strainers


MAINTENANCE

The EVAPCO standard for many years, the stainless steel strainer is one
component of the cooling tower subject to excessive wear and corrosion.
With stainless steel construction, this component will last the life of the
cooling tower.

A S Y

O L U T I O N S

E T T E R

H O I C E S

M A I N T E N A N C E F E AT U R E S
The Advanced Technology Easy Maintenance Drive System
The EVAPCO POWER-BAND drive system utilized on the AT/UAT Cooling Tower is the easiest belt drive system to
maintain in the industry. There is no need to stand inside the cold water basin to service the bearings, belts or electrical
equipment. In addition, there is no need for fan deck handrails or safety cages, since all periodic maintenance can be
safely performed from the side of the AT/UAT. The most important features of this design are listed below.

Models AT / UAT 14-64 through AT / UAT 14-912


Models AT / UAT 19-56 through AT / UAT 38-942
Motor Mount, Power Band Belt Adjustment and Bearing Lubrication
The fan motor and drive assembly are designed to allow easy servicing of
the motor and adjustment of the belt tension from the exterior of the
unit. The T.E.F.C. fan motor is mounted on the outside on these models
and is protected from the weather by a cover which swings away for
maintenance.
A large access door is located on the side of the unit for easy access to the
fan drive system. The belt can be adjusted by tightening the J-Bolts on
the motor base and the tension can be checked easily through the access
door, all while standing at the side of the unit. The bearing lubrication
lines have been extended to the exterior casing and are located by the
access door, thus making bearing lubrication easy.

Models AT / UAT 110-112 through AT / UAT 428-1248


Motor Mount, Power Band Belt Adjustment and Bearing Lubrication
The T.E.A.O. fan motor is located inside the fan casing on the large AT/UAT
Cooling Tower, and is mounted on a rugged heavy duty motor base. The motor
base is designed to swing completely to the outside of the unit through a very
large hinged (1,3 m2) access door greatly simplifying maintenance.
The unique swinging motor mount designed for these models features easy
belt adjustment from the exterior of the unit. The T.E.A.O. fan motor is
mounted on an adjustable base which is supported by two heavy duty galvanized steel pipes. The belt is adjusted by tightening an all-thread which runs
through the motor base.

MAINTENANCE

The innovative motor base features a


unique locking mechanism for a positive
belt adjustment and is also used to
adjust the belt tension if a wrench is not
available.
Bearing lubrication fittings are extended
to the side of the unit inside the access
door to allow easy application of the
bearing lubricant. This external location
allows for easy servicing of the bearings
and is another important advantage of
EVAPCO equipment.

A S Y

O L U T I O N S

E T T E R

H O I C E S

M A I N T E N A N C E F E AT U R E S
The Advanced Technology Easy Maintenance Drive System

(continued)

Fan Motors
All AT/UAT Cooling Tower models utilize heavy duty totally enclosed fan
motors designed specifically for cooling tower applications. In addition to
the standard motors offered on each cooling tower, EVAPCO offers many
optional motors to meet your specific needs, including:
Multi-Speed Motors
Inverter-Duty Motors for VFD Applications
The T.E.F.C. motors are located on the outside of the unit on Models
AT 14-64 through AT/UAT 38-942 and are protected by a hinged, swing
away cover.
Models AT/UAT 110-112 through 428-1248 have T.E.A.O. motors located
inside the fan section on a heavy duty motor base. The motor base swings
to the outside for motor repair or removal, for AT/UAT 110-112 through
428-1248.
On Models AT/UAT 14-64 through 14-912

On Models AT/UAT 19-56 through 38-942

On Models AT/UAT 110-112 through 428-1248

Power-Band Belt Drive


The Power-Band drive is a solid-back multigroove belt system that has
high lateral rigidity. The belt is designed for cooling tower service, and is
constructed of neoprene with polyester cords. The drive belt is sized for
1.5 service factor of the motor nameplate kW ensuring long and trouble
free operation.

Drive System Sheaves

MAINTENANCE

Drive system sheaves located in the warm, moist atmosphere inside the
cooling tower are constructed of an aluminum alloy. Those located externally are protected by a hinged protective cover.

Fan Shaft Bearings


The fan shaft bearings on the AT/UAT cooling tower are specially selected
to provide long life, minimizing costly downtime. They are rated for an
L-10 life of 75.000 to 135.000 hours, making them the heaviest duty pillow
block bearing in the industry used for cooling tower duty.

10

A S Y

O L U T I O N S

E T T E R

H O I C E S

OPTIONAL EQUIPMENT
Optional Equipment for Easier Operation and Maintenance
The standard design of the EVAPCO AT/UAT provides the customer with the easiest cooling tower to maintain in the industry. There are additional options which can make maintenance easier and extend the life of the cooling tower. These
options are listed below.

Sloped Access Ladders


The EVAPCO designed access ladder features a sloped ships type
ladder arrangement which provides fast and easy access to the
water distribution system and drive components. A handrail is
attached to the sloped ladder for safe and easy ascent and descent.
The ladder(s) will ship loose and must be field mounted.
Note: The sloped access ladder is available on all models AT/UAT 19-56
through AT/UAT 428-1248.
A safety cage is not included in this design. Check conformity
with local legislation before application.

Working Platform & Ladder with Davit


AT/UAT Cooling Towers are available with an external working platform and ladder to allow easy servicing of the fan motor and water
distribution system. Providing a convenient platform to perform
work, the heavy duty platform is self-supporting-which eliminates
the need for any external support. A less expensive alternative to
field erected catwalks, the working platform option uses a straight
ladder as standard and ships in sections for easy installation.
Note: The Working Platform is not available on models AT/UAT 14-64
through 14-912.
The davit option eliminates crane rentals and facilitates the removal
of motors. The davit and bracket are constructed of aluminum and
are mounted on the side of the unit. The optional fan motor davit
ships loose and is installed in the field.

Stainless Steel Water Touch Basin


(for AT Cooling Towers only)

OPTIONS

The AT Cooling Tower has a modular design which allows specific


areas to be enhanced for increased corrosion protection. The basin
area of the cooling tower experiences turbulent mixing of air and
water, in addition to silt build-up. In conjunction with the EVAPCOAT
Corrosion Protection System, EVAPCO offers an optional Stainless
Steel Water Touch Basin. This option provides Type 304 or Type 316
stainless steel for the entire basin area including the support columns
of the cooling tower and the louver frames.
The basin section provides the structural support for the unit and is
the most important part of the cooling tower. The Stainless Steel
Water Touch Basin provides maximum corrosion protection.

Basin Level Platform


AT/UAT Cooling Towers can be equipped with a basin level platform
and ladder to allow easy servicing of the cold water basin.
This option is only available on larger units.
Facilitates Maintenance
- Adjust Float Assembly
- Clean Basin and Suction Strainer
Self Supporting and Easy Installation
- Platform Supported from Unit
- Ladder Requires Field Support
- Ships in Modules for Easy Installation

11

A S Y

O L U T I O N S

E T T E R

H O I C E S

OPTIONAL EQUIPMENT
Optional Equipment for Easier Operation and Maintenance
Electric Heaters

Remote Sump Configuration

Electric immersion heaters are available factory installed in


the basin of the cooling tower. They are sized to maintain a
+5C pan water temperature with the fans off and an ambient air temperature of -18C. They are furnished with a combination thermostat/low water protection device to cycle the
heater on when required and to prevent the heater elements from energizing unless they are completely submerged. All components are in weather proof enclosures for
outdoor use. The heater power contactors and electric
wiring are not included as standard.

Optional Remote
Sump Connections
by EVAPCO

Remote Sump by others

Electric Water Level Control

OPTIONS

EVAPCO cooling towers are available with an optional electric water level control system in place of the standard
mechanical makeup valve and float assembly. This package
provides very accurate control for the basin water level and
does not require field adjustment, even under varying operating conditions.
The control consists of multiple heavy duty stainless steel
electrodes. These electrodes are mounted external to the
unit in a vertical stand pipe. For winter operation, the stand
pipe must be wrapped with electric heating cable and insulated to protect it from freezing.
The weather protected slow closing solenoid valve(s) for the
makeup water connection is factory supplied and is ready
for piping to a water supply with a pressure between 140
and 340 kPa.

For units operating in areas where ambient temperatures


may be very low, or where low temperatures may occur during periods when the unit is not operating, a sump located
inside the building is the preferred means of ensuring that
the basin water will not freeze. For these applications, the
cooling tower will be supplied without the suction strainers
but with an oversize bottom outlet.

Other Options
Vibration Isolators (single cell units only)
Vibration Switches
Fill Access Doors
Sump Sweeper Piping
Many more options ...

Fill Access Door

12

Flanged Connections

A S Y

O L U T I O N S

E T T E R

H O I C E S

A P P L I C AT I O N S
Special Applications of the AT/UAT Cooling Tower
The standard AT/UAT Cooling Tower is suitable for the majority of air conditioning and industrial cooling applications. However, there
are some design situations where special consideration must be given with regard to materials of construction, thermal performance,
sound level and water quality. Some of these special applications are described below.

AT/UAT CoolingTowers are constructed of heavy duty


materials and are designed for superior performance providing long, trouble-free operation. However, proper equipment
selection, installation and maintenance are necessary to ensure
optimum unit performance. Several of the major considerations when designing and operating a cooling tower installation are presented in the following paragraphs. For additional
information, contact your local EVAPCO representative.

Air Circulation
The location of a cooling tower is an important consideration
when reviewing system design. Since cooling towers use
large quantities of air, adequate spacing around the unit is
necessary for it to perform properly. The best place to locate
any cooling tower is on a roof or at ground level away from
walls and other obstructions. Cooling towers that are located
in wells, enclosures, or are adjacent to high walls must be
properly located to avoid the effects of recirculation.
Recirculation occurs when some of the hot moist discharge
air leaving the cooling tower flows back into the fresh air
inlet. When recirculation causes the inlet wet bulb temperature to the cooling tower to be increased, the capacity of the
cooling tower is decreased. Refer to EVAPCO Bulletin 311,
Equipment Layout Manual, for the recommended layout
guidelines for cooling towers.

Maintaining the Recirculated Water System


A cooling tower removes heat by evaporating a portion of
the recirculated spray water. As a general rule, a cooling
tower evaporates 1.58 l/h per 1 kW of cooling capacity. As
this water evaporates, it leaves behind all of its mineral content and impurities. Therefore, it is important to bleed an
amount equal to that which is evaporated to prevent the
buildup of impurities. If this is not done, the mineral content
in the water will increase until the solids eventually deposit in
the unit, causing heavy scaling. The bleed line should be
installed in the external piping of the unit. It must be properly sized for the application and be provided with a metering
valve and flow measurement device to allow for field adjustment of the bleed rate.

control will be required. The simplest form of capacity control is to cycle the fans on and off. However, this type of control results in larger temperature differentials and does not
provide close control of the leaving water temperature.
A better method of capacity control is to use two speed fan
motors, which adds a second step of control. Two speed
motors are an excellent method of capacity control for the
AT/UAT Cooling Tower. This arrangement gives capacity steps
of 10% (fans off), 60% (Fans at half speed) and 100%.
Two speed motors also reduce operating costs. At half speed,
the motor draws approximately 15% of the full load power.
Since the maximum wet bulb temperature and maximum load
very seldom coincide, the cooling tower will actually operate
at half speed about 80% of the time. Therefore, power costs
will be reduced during the major portion of the year.
A third advantage of two speed motors is that noise levels are
reduced by approximately 6 dB(A) when operating at half
speed. Since both the load and wet bulb temperature are
normally lower at night, the sound generated by the cooling
tower will be substantially reduced during the most noise sensitive time period.
For multiple cell units, both fan cycling and two speed motors
can be used to provide additional steps of control. The combination of fan cycling and two speed motors offers a simple
and inexpensive means of controlling unit capacity along with
substantially reducing the energy costs of the cooling tower.
The best method of capacity control is the use of Variable
Frequency Drives. This stepless control guarantees an optimized fan speed and as per consequence, an optimized heat
rejection. Important energy/cost saving can be realized.

Piping
Cooling tower piping should be designed and installed in
accordance with generally accepted engineering practices. All
piping should be supported by properly designing hangers
and supports with allowances made for possible expansion
and contraction of the piping system. No external loads
should be placed on the cooling tower connections. Do NOT
anchor any of the piping supports to the cooling tower or its
framework.

Water Treatment

Control of Biological Contamination

EVAPCO recommends that all cooling tower users should consult a reputable water treatment company familiar with local
water conditions in order to determine the extent and type of
water treatment program recommended for each specific
application. Any chemical water treatment used must be
compatible with the construction of the unit. If acid is used
for treatment, it should be accurately metered and the concentration properly controlled. Consult EVAPCOs
Maintenance Bulletin 112 for additional information.

Water quality should be checked regularly for biological contamination. If biological contamination is detected, a more
aggressive water treatment and mechanical cleaning program
should be undertaken. The water treatment program should
be performed by a qualified water treatment company. It is
important that all internal surfaces be kept clean of accumulated dirt and sludge. In addition, the drift eliminators should
be checked periodically to ensure that they are clean and
have not been damaged.

Capacity Control

Note: The location of the cooling tower must be considered during the equipment layout stages of a project. It is
important to prevent the discharge air (potential of biological contamination) from being introduced into the
fresh air intakes of the building.

The design wet bulb temperature for which a cooling tower is


sized occurs only a small percentage of the time. Since the
wet bulb temperature is lower than design much of the time,
and cooling loads tend to fluctuate, some form of capacity

APPLICATIONS

System Design

13

A S Y

O L U T I O N S

E T T E R

H O I C E S

A P P L I C AT I O N S
Freecooling
Freecooling is when chilled water is produced by the
cooling tower without the use of a mechanical chiller
during low ambient conditions. The freecooling or economizer mode of an air conditioning system is used to
save cost per kWH when the conditions allow the water
in the tower to be cooled to chiller like temperatures,
typically 5.5C 7C leaving water temperature.
EVAPCOs AT/UAT counterflow cooling towers are well
suited for free cooling applications. The counterflow fill
design helps preventing ice formation with its even temperature gradient through the fill section and enclosed
location blocking it from the elements. However, special
caution must be taken when selecting, sizing and operating a cooling tower during normal winter or severe winter applications.
Please consult EVAPCOs Engineering Bulletin on Free
Cooling Operation of Open Cooling Towers or EVAPCO
to assist in selecting a tower for a freecooling application.

High Temperature Applications


EVAPCOs AT/UAT Cooling Tower as standard is capable
of handling up to 55C entering water temperature. It
will not deform or degrade at a continuous temperature
application of 55C.

APPLICATIONS

However, there are applications where a higher temperature rated fill is required. For these applications, a fill
material is available as an option which allows the entering water temperature to operate at a continuous 65C.
Please consult the factory for selections of high temperature fill Cooling Towers.

Dirty Water Applications


The fill used in the AT/UAT Cooling Tower is designed to
operate in almost all cooling water applications.
However, there are some dirty water applications
where the standard fill spacing is not adequate, such as a
pulp and paper mill cooling towers or other applications
where heavy particulate will be mixed in with the water.
For additional information, contact your local EVAPCO
representative.

Alternate AT/UAT Arrangements


The AT/UAT Cooling Tower will fit almost every application. However, there are installations with special piping
locations or existing steel that will require the AT/UAT to
be modified to fit the layout.
Please contact the factory and we will develop a design
to fit your need.

Consult the Factory for:

14

Layout Guidelines
Equalizer Connection Sizing and Location
Remote Sump Connection Sizing and Location
Seismic and Wind Load Application
Operating and Maintenance Questions
Ladders, Platforms and Motor Davits

Notes:

A S Y

O L U T I O N S

E T T E R

H O I C E S

Ultra Quiet
Cooling Towers

The AT/UAT Cooling


Tower is now available
with four (4) equipment
options to reduce the
overall sound gener-

SOUND

ated from the side


or top of the
AT/UAT Cooling
Tower. Each
option provides
various levels of
sound reduction
and can be used in
combination to provide the lowest sound
level.

Ultra Quiet operation


for induced draft
counterflow
Cooling Towers

15

A S Y

O L U T I O N S

E T T E R

H O I C E S

A D VA N C E D T E C H N O L O G Y
LOW SOUND SOLUTIONS
Super Low Sound Solution for Sound Sensitive Applications

Family of Super Low Sound Fans

SOUND

The Super Low Sound Fan


Reduced Sound Levels versus Model AT/UAT Standard Fan
EVAPCO's Super Low Sound Fan on the AT/UAT cooling tower utilizes an extremely wide chord blade design
applied for sound sensitive applications where the lowest sound levels are desired. The fan is one piece molded heavy
duty FRP construction utilizing a forward swept blade design. The Super Low Sound Fan reduces sound levels 9 to 15
dB(A) compared to the Model AT/UAT standard fan.

The SUPER Low Sound Fan on the AT/UAT cooling tower


reduces sound levels 9-15 dB(A) and eliminates audible blade
passing frequencies indicative of straight bladed axial type
fans.
Refer to the Narrow Band Spectrum graph which shows how
straight bladed axial fans produce blade passing frequencies
the same phenomena that produce the signature pulsating
helicopter noise.
The blade passing frequencies are audible spikes in sound
pressure levels, but are not apparent in the octave band
sound spectrum.

Blade Passing Frequencies


Sound Pressure Level (dB)

Improved Sound Quality versus


Model AT/UAT Standard Fan

Standard Axial Fan


Super Low Sound Fan

Frequency (Hz)

Narrow Band Spectrum Analysis

The Super Low Sound Fan on the AT/UAT Cooling Tower reduces sound levels and betters the sound quality!

NOTE: These low sound options may impact the overall installed dimensions of the AT/UAT
Cooling Tower selected.

16

A S Y

O L U T I O N S

E T T E R

H O I C E S

A D VA N C E D T E C H N O L O G Y
LOW SOUND SOLUTIONS
Additional Solutions for Sound Sensitive Applications
Low Sound Fan

4 7 dB(A) Reduction!
The Low Sound Fan offered by EVAPCO is a wide chord blade design for
sound sensitive applications where low sound levels are desired. The Low
Sound Fan shall utilize a unique soft-connect blade-to-hub design that is
compatible with Variable Speed Drives.
The Low Sound Fan is capable of reducing the unit sound pressure levels
4 dB(A) to 7 dB(A), depending upon specific unit selection and measurement location. The fans are high efficiency axial propeller type and
are on the AT/UAT cooling towers.
The Low Sound Fan is available on all 2.4 m wide and larger AT/UAT
Cooling Towers.

Water Silencer

SOUND

Reduces Water Noise in the Cold Water Basin up to 7 dB(A)!


The water silencer option is available for all induced draft models and is
located in the falling water area of the cold water basin. The water
silencer will reduce the high frequency noise associated with the falling
water and is capable of reducing overall sound levels 4 dB(A) to 7 dB(A)
measured at 1.5 m from the side or end of the unit. The water silencers
reduce overall sound levels 9 dB(A) to 12 dB(A) (depending on water
loading and louver height) measured 1.5 m from the side or end of the
unit when water is circulated with fans off.
The water silencers are constructed of lightweight PVC sections and can
be easily removed for access to the basin area. The water silencer will
have no impact on unit thermal performance.
The Water Silencer is available on ALL AT/UAT Cooling Towers.

Fan Discharge Sound Attenuation

Up to 10 dB(A) Reduction!
The discharge attenuator is a factory assembled straight sided discharge
hood designed to reduce overall discharge sound levels at full fan speed 5
dB(A) to 10 dB(A), depending on specific unit selection and measurement location. It is constructed of Z-725 galvanized steel as standard
(options available for Type 304 stainless steel) and includes insulated walls
and a low pressure drop baffling system that is acoustically lined with
high density fiberglass. The discharge attenuator is supported entirely by
the unit and is shipped as an assembled section for easy mounting in the
field. The discharge attenuator is covered by a heavy gauge hot dip galvanized steel fan guard to prevent debris from entering the attenuator.
The discharge attenuator will have a minimal impact on unit thermal performance (0%-2% derate depending on specific unit selection).
The Discharge Attenuator is available on ALL 2.4 m wide and larger
AT/UAT Cooling Towers.
(Note: The Fan Discharge Attenuator Option is NOT available on models
provided with the Super Low Sound Fan.)

Consult EVAPCOs iES selection software for unit sound levels. If a detailed analysis or full
octave band data sheet is required for your application, please consult your EVAPCO Sales
Representative.

17

A S Y

O L U T I O N S

E T T E R

H O I C E S

SOUND BASIC
Background in Sound Basics
Sound
Sound is the alteration in pressure, stress, particle displacement and particle velocity, which is propagated in an elastic
material. Audible sound is the sensation produced at the ear
by very small pressure fluctuations in the air.

62 lx
250 lx
1000 lx

Sound Pressure
Sound pressure is the intensity of sound. Sound pressure, Lp
in decibels is the ratio of measured pressure, P in the air to a
reference sound pressure, PO = 2 x10 5 Pascal following the
following formula:
L p (dB) = 10 log10 ( P2/ PO2)

7.5 m 15 m 30 m

SOUND PRESSURE

The most important point to understand about sound


pressure level is that sound pressure level is what is
actually being measured when sound data is
recorded. Microphones that measure sound are pressure
sensitive devices that are calibrated to convert the sound
pressure waves into decibels.

SOUND

30 m 15 m 7.5 m

Sound Power

Similar to the intensity coming from a light bulb


which gets dimmer as one gets further and further
away, sound pressure decreases in decibels as your
ear gets further from the sound source.

100W

Sound Power is the energy of sound. Sound power, Lw in


decibels is the ratio of the calculated sound power, W to
a reference power, Wo =1 picowatt, according to the
following formula:
L w (dB) = 10 log10 (W/Wo)
The most important point to remember about sound
power level is that sound power level is not a measured value, but is calculated based on the measured
sound pressure.

SOUND POWER
Similar to the wattage of a light bulb that does not
change the farther one is away from the light bulb,
sound power does not vary with distance.

76 dB(A)
dB((A)

Adding Multiple Sound Sources


Since the decibel is a logarithmic function, the numbers are
not added linearly. Therefore, two 73 dB sound sources
added together do not equal 146 dB. The resultant sound
would actually be 76 dB. The following table shows how to
add decibels from two sound sources.

18

Difference in
dB Level

Add to the higher


dB Level

0 to 1
2 to 3
4 to 8
9 or greater

3
2
1
0

73 dB(A)
dB(A
dB(
B(A)
A)

73
7
3 dB(A)
dB(A)

A S Y

O L U T I O N S

E T T E R

H O I C E S

SOUND BASIC
Sound Science and Cooling Towers
Sound Frequency
LowLow-Mid
Frequencies
Travel through and
Trav
around
Obstructions
a
aro
ar
u

Fan Noise

Fan Noise

Low / Mid frequencies that travel long distances,


through walls, and around obstructions.

Very difficult to attenuate. Reduce fan noise by using


Low Sound Fans.

Dominates what is measured and heard at the


cooling tower and at the sound sensitive location.

High Frequency
H
Self
Se Attenuating

Water
Noise

High frequencies that attenuate naturally with


distance. Attenuated easily by walls, trees or
other obstructions.

Totally masked and drowned out by fan noise at a


short distance away from the cooling tower.

SOUND

Water Noise

Sound Pressure The A-Weighted Scale


The A-weighted scale, dB(A) is a means to translate what a sound meter microphone
measures to how the human ear perceives the sound.

dB(A) Formula and Conversions:

Typical Sound Pressure Levels of


Well Known Noises:

f=8000
dB(A) =10 log 10

10 ((dB+Cf) /10)

f=63
where:
let:
Band

C f = correction factor per band


dB = measured sound pressure
Z f = (dB + Cf)/10
Center
Freq. (Hz)

Frequency
Range (Hz)

Sample
Data (dB)

Cf
(dB)

Zf

63

44-88

68

-26.2

4.18

125

89-175

76

-16.1

5.99

250

176-350

77

-8.6

6.84

500

351-700

73

-3.2

6.98

1000

701-1400

70

7.00

2000

1401-2800

68

+1.2

6.92

4000

2801-5600

71

+1.0

7.20

8000

5601-11200

73

-1.1

7.19

Jet Airplane, 45 meters away


Painful
Very Uncomfortable
Circular Saw
Nightclub
Semi Truck
Sidewalk of a Busy Road
Household Vacuum, 1 meter away
Normal Conversation
Inside Average Home
Quiet Library
Bedroom at Night

140 dB(A)
130 dB(A)
120 dB(A)
110 dB(A)
100 dB(A)
90 dB(A)
80 dB(A)
70 dB(A)
60 dB(A)
50 dB(A)
40 dB(A)
30 dB(A)

Notable Facts about Sound:


+/- 1 dB(A) is inaudible to the human ear
Decreasing a noise source by 10 dB(A) sounds half as
loud to the human ear

Example calculation of the dB(A) formula using the Sample Data above.
dB(A) = 10 log10 10(Z1) + 10(Z2) + 10(Z3) + 10(Z4) + 10(Z5) + 10(Z6) + 10(Z7) + 10(Z8)
= 10 log10 (67114245.2) = 78.3 dB(A)

19

A S Y

O L U T I O N S

E T T E R

H O I C E S

SPECIFYING SOUND
Sound Verifications
Microphone
Location

Specify sound pressure in dB(A) measured 1,5 m above the fan


discharge during full speed operation.
All manufacturers can meet a performance specification with Low Sound Options
Fan noise is what matters. 1,5 m above the fan is where it matters.

1,5 m

45

Measurement Location
Per Cooling Technology Institute Standard ATC-128
Sound Microphone location 1,5 m above the cooling tower fan cowl edge at a
45 angle.
This position assures accurate sound measurements by eliminating a source of
uncertainty by taking the microphone out of the high velocity fan discharge air.

Easy Verification

SOUND

At 1,5 m from the cooling tower, a sound meter records only cooling tower noise. Interested parties can easily verify the
actual noise coming from the cooling tower against the specified sound data with good certainty.
New
Cooling
Tower

tr
tee
Fee
0m

15

15
0m
Fee
tee
trs

Rooftop
Air
Handler

Sound Quality
Sound coming from the top of the cooling tower is comprised of lowand mid-frequency fan noise. Low- and mid-frequency fan rumble is
very difficult to attenuate. Fan rumble travels through everything and
around everything and what is audible at any sound sensitive location.

trs
tee
Fee
0m
15

15
0m
Fee
tee
trs

Microphone

Existing
Cooling
Tower

If sound were specified at 15 meters or some greater distance from the


sound sensitive location, there is increased uncertainty in the measured
data due to other possible sound sources within the 15 meters radius of
the sound microphone.

Road
Traffic

Sound coming from the sides of the cooling tower is comprised of high
frequency water noise, is much less objectionable than fan noise and
attenuates naturally with distance.

Acoustical Shadow*
Subjective reactions to the overall noise generated by cooling
towers indicate that as one walks away from a tower intake, a
point is reached where the water noise is masked by the fan noise.
The point coincides with the point at which one emerges from the
acoustical shadow of the tower structure, which shields intake
water noise from discharge fan noise.
*Seelbach & Oran, What To Do About Cooling Tower Noise,
Industrial Acoustics Company.
Sound measured at the side of a cooling tower is inside the acoustical shadow of the noise emitted from the top. Outside
the acoustical shadow, the low- and mid-frequency fan noise
completely masks the high frequency water noise.

Low-Mid Frequencies
Travel through and
around Obstructions
Fan Noise

Acoustical
Shadow

Water
Noise

High Frequency
Self Attenuating

Specify fan noise because it matters! Specify fan noise where it matters!

20

A S Y

O L U T I O N S

E T T E R

H O I C E S

We Stand Tall
Through it All!

The International

IBC

Building Code (IBC) is a


comprehensive set of
regulations addressing
the structural design
and installation
requirements for
building systems
including HVAC
and industrial
refrigeration
equipment.

With the advent


of the IBC,
EVAPCO is
proud to
introduce the new and
improved line of AT and UAT
Cooling Towers with IBC 2006
compliance standard.

Wind, Rain,
Earthquake
and Hurricane
EVAPCO Cooling Towers designed to
withstand seismic or wind load forces.

21

A S Y

O L U T I O N S

E T T E R

H O I C E S

IBC COMPLIANCE
In its continuing commitment to be the leaders in evaporative cooling equipment
design and services, EVAPCO AT/UAT Cooling Towers are now Independently Certified to
withstand Seismic and Wind Loads in accordance with IBC 2006.

What is IBC?
International Building Code

IBC

The International Building Code (IBC) is a comprehensive set of


regulations addressing both the structural design and the installation requirements for building systems including HVAC and
industrial refrigeration equipment.
Compared to previous building codes that considered only the
building structure and component anchorage, the requirements
contained within the IBC address anchorage, structural integrity,
and the operational capability of a component following either a
seismic or wind load event. Simply stated, the IBC code provisions require that evaporative cooling equipment, and all other
components permanently installed on a structure, must be
designed to meet the same seismic or wind load forces as the
building to which they are attached.

How Does IBC 2006 Apply to Cooling Towers?


Based on site design factors, calculations are made to determine
the equivalent seismic g force and wind load (kilo-Newton per
square meter, kN/m2) on the unit. The cooling tower must be
designed to withstand the greater of either the seismic or wind
load.

Independent Certification
Although the IBC references and is based on the structural building code ASCE 7, many chapters and paragraphs of ASCE 7 are
superceded by the IBC, independent certification and methods of
analysis are such paragraphs. Per the most recent edition of the
code, the EVAPCO compliance process included an exhaustive
analysis by an independent approval agency. As required by the
International Building Code, EVAPCO supplies a certificate of
compliance as part of its submittal documents. The certificate of
compliance demonstrates that the equipment has been independently tested and analyzed in accordance with the IBC seismic and wind load requirements. Evapco has worked closely with
the independent approval agency, The VMC Group, to complete
the independent equipment testing and analysis.
If the seismic g force or wind load psf requirements for the
project site are known, EVAPCOs online equipment selection
software, iES, will allow you to choose the required structural
design package either standard construction or upgraded construction.
For further questions regarding IBC compliance, please contact
your local EVAPCO Representative.

The New AT/UAT is offered with a choice of TWO structural


design packages:
Standard Structural Design For projects with
1.0g seismic or 2,87 kN/m2 wind loads
Upgraded Structural Design Required for projects with
>1.0 g seismic or 6,94 kN/m2 wind loads
All locations with design criteria resulting in a seismic design
force of up to 1.0g or a wind load of 2,87 kN/m2 or below will
be provided with the standard AT/UAT structural design. An
upgraded structural design is available for installations with
design criteria resulting in g forces greater than 1.0g. The
highest g force location in North America is 5.12g. The highest wind load shown on the maps is 273 km/h, which is approximately equal to 6,94 kN/m2 velocity pressure. Therefore, the
upgraded structural design package option for the New
AT/UAT is designed for 5.12 g and 6,94 kN/m2 making it applicable to ALL building locations in North America.

Design Implementation
EVAPCO applies the seismic design and wind load information
provided for the project to determine the equipment design necessary to meet IBC requirements. This process ensures that the
mechanical equipment and its components are compliant per the
provisions of the IBC as given in the plans and specifications for
the project.

22

Certificate of Compliance
AT, USS, UAT, UT Cooling Towers
ATW Closed Circuit Coolers
HTC, ATC-E Evaporative Condensers
Are certified to meet or exceed the Seismic and Wind Load Provisions
set forth in the applicable building codes for this project.
These products have been manufactured following all
applicable quality assurance programs.
Applicable Building Codes:
IBC 2006
ASCE-7
NFPA 5000

Referenced Report:
VMA-43387
Approval Agency:
VMC Seismic Consulting Group

EVAPCO...Specialists in Heat Transfer Products and Services.

ID IBC COC 001

A S Y

O L U T I O N S

E T T E R

H O I C E S

CTI Certified
AT and UAT
Cooling Towers

CTI

CTI Certification
Purpose (STD-201)
This standard sets forth
a program whereby the
Cooling Technology
Institute will certify
that all models of a
line of evaporative
heat rejection equipment offered for sale
by a specific manufacturer will perform
thermally in
accordance with the
manufacturers
published ratings...

Technology for the Future,


Available Today!

Mark owned by the Cooling Technology Institute

23

A S Y

O L U T I O N S

E T T E R

H O I C E S

C T I C E RT I F I C AT I O N
In its continuing commitment to be the leaders in evaporative cooling equipment design and
services, EVAPCO AT/UAT Cooling Towers are now Independently Certified by CTI, to perform
thermally in accordance with the published data.

CTI

What is CTI?
COOLIN

G TEC
HNOL
OGY
INSTITU

Cooling Technology Institute


The Cooling Technology Institute is an organization headquartered in the United States with over 400 member companies
from around the globe. CTI membership is composed of manufacturers, suppliers, owner operators, and test agencies from
over 40 countries. In 2008 CTI certified more than 5000
Evaporative Heat Transfer Systems (EHTS) from 49 product line of
24 participants.

TE

OGY
HNOL
G TEC
COOLIN ITUTE
INST

CTI CO

Standa

DE TO

rd Spec

Accepta

ance
Perform
hermal
d for T fication
ti
Standar
er
C
of
ection
eat Rej
ative H
Evapor quipment
E

Water

nce Tes
t Code
for
Cooling
Towers

CTIs Mission and Objectives


This can be best explained by the CTIs published Mission
statement and Objectives revised in December 2003 and
published on their website www.cti.org.
CTI Mission Statement
To advocate and promote the use of environmentally
responsible Evaporative Heat Transfer Systems (EHTS)
for the benefit of the public by encouraging:
Education
Research
Standards Development and Verification
Government Relations
Technical Information Exchange
CTI Objectives
Maintain and expand a broad base membership of
individuals and organizations interested in
Evaporative Heat Transfer Systems (EHTS).
Identify and address emerging and evolving issues
concerning EHTS.
Encourage and support educational programs in
various formats to enhance the capabilities and
competence of the industry to realize the maximum
benefit of EHTS.
Encourage and support cooperative research to
improve EHTS technology and efficiency for the
long-term benefit of the environment.
Assure acceptable minimum quality levels and
performance of EHTS and their components by
establishing standard specifications, guidelines, and
certification programs.
Establish standard testing and performance analysis
systems and procedures for EHTS.
Communicate with and influence governmental
entities regarding the environmentally responsible
technologies, benefits, and issues associated with
EHTS.
Encourage and support forums and methods for
exchanging technical information on EHTS.

24

WE

ificatio R
ns

CTI Code

ATC-105

STD 201

Benefits to the End User


CTI defines an independent testing certification program
that is specifiable, enforceable and available to all equipment manufacturers. End users that purchase CTI certified products are assured that those products will perform thermally as specified.
Additionally CTI certification is the first step for the Green
Building Concept in Europe:
LEED - Leadership in Energy and Environmental
Design
Best Available Practice
Green Building Rating System

Thermal Performance Guarantee


In addition to the CTI Certification, Evapco unequivocally
guarantees the Thermal Performance of ALL Evapco
Equipment. Every unit order is confirmed with a submittal
package that includes an Evapco Thermal Performance
Guarantee Certificate.

A S Y

O L U T I O N S

E T T E R

H O I C E S

C T I C E RT I F I C AT I O N
CTI Certification Program

Submit Application for Certification


CTI completes a technical review of the product
line submitted
CTI performs an initial qualification test in a
laboratory on a specified model number
CTI issues an Approval Letter with Validation
Number if test is passed. Letter is also distributed
to all members of CTI to inform everyone that a
successfull certification has been completed.
The Certification Validation Number assigned
should be fixed to each tower sold and displayed in
all catalogs and other literature
Product Line must undergo an Annual Reverification
Test - Different model number is selected every year
More details can be found on the CTI website
www.cti.org

CTI Certification Test Parameters

Entering Wet Bulb temperature - 12.8C to 32.2C


Cooling Range - Minimum of 2.2C
Cooling Approach - Minimum of 2.8C
Process Fluid Temperature - Maximum of 51.7C
Barometric Pressure - 91.4 to 105 kPa
More details can be found on the CTI website
www.cti.org

Evapco Europe CTI Certified AT Product Line


AT Line of CTI Certified Cooling Towers
CTI Certification Validation Number 99-13-01
Includes UAT model numbers
Includes the use of side, end or bottom water inlet
configuration
Includes optional Super Low Sound Fan (SLSF)
Includes optional pan Water Silencers (WS)
Includes optional external service platform and
ladders for access
iES Technical data sheet will state CTI Certified
Selection if the selection falls within the CTI
Certification Test Parameters
Unit will receive a CTI Certified Shield located near
the nameplate

CTI

CTI Certification Process

Note
All CTI Certified Product Lines of all manufacturers
with CTI certified products can be found on the
website: http://www.cti.org/certification.shtml

CTI Certification Limitations


Specific manufacturers product line name and
model numbers
Applicable only to product lines and model numbers
submitted
Multiple cell model numbers are allowed if the
airflow is not affected or the configuration impact is
included in the unit rating
Optional accessories are allowed if the aiflow is not
affected or the accessory impact is accounted for in
the rating
More details can be found on the CTI website
www.cti.org

Mark owned by the Cooling Technology Institute

25

Notes:

26

A S Y

O L U T I O N S

E T T E R

H O I C E S

A S Y

O L U T I O N S

E T T E R

H O I C E S

ENGINEERING

Thermal
Performance

Engineering
Data
& Dimensions

27

ENGINEERING

C O O L I N G C A PA C I T Y
M O D E L S AT/UAT 14-64
M O D E L S AT/UAT 18-49

TO

14-912
18-914

TO

Cooling capacity in l/s*


MODEL
NO.

EWT
LWT
WB

AT/UAT 14-64
AT/UAT 14-74
AT/UAT 14-84
AT/UAT 14-94
AT/UAT 14-66
AT/UAT 14-76
AT/UAT 14-86
AT/UAT 14-96
AT/UAT 14-69
AT/UAT 14-79
AT/UAT 14-89
AT/UAT 14-99
AT/UAT 14-612
AT/UAT 14-712
AT/UAT 14-812
AT/UAT 14-912

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

9,3
10,1
10,7
11,5
15,8
17,0
18,3
19,5
21,4
23,3
24,9
26,7
32,1
34,6
37,3
39,7

5,2
6,0
6,2
7,1
9,1
10,4
10,9
12,2
12,0
13,9
14,4
16,4
18,5
21,1
22,2
24,7

8,6
9,4
10,0
10,8
14,7
15,9
17,1
18,3
19,8
21,7
23,1
25,0
29,8
32,3
34,8
37,2

4,7
5,5
5,7
6,5
8,3
9,5
10,0
11,2
10,8
12,7
13,1
15,1
16,8
19,4
20,3
22,9

7,7
8,5
9,1
9,9
13,3
14,5
15,6
16,8
17,8
19,8
21,0
22,9
27,0
29,6
31,7
34,1

4,1
4,9
5,1
5,9
7,4
8,6
9,0
10,2
9,6
11,4
11,7
13,6
15,0
17,5
18,2
20,8

6,8
7,6
8,0
8,9
11,7
13,0
13,9
15,1
15,7
17,6
18,6
20,5
23,9
26,5
28,2
30,7

4,4
5,2
5,4
6,2
7,8
9,0
9,5
10,7
10,2
12,0
12,4
14,3
15,8
18,4
19,2
21,8

8,9
9,7
10,4
11,2
15,2
16,5
17,7
18,9
20,6
22,5
24,0
25,9
31,0
33,5
36,0
38,5

5,8
6,6
6,9
7,8
10,1
11,4
12,1
13,3
13,5
15,4
16,1
18,0
20,6
23,2
24,6
27,1

8,0
8,8
9,4
10,2
13,8
15,0
16,1
17,3
18,5
20,4
21,7
23,6
28,0
30,5
32,7
35,1

5,3
6,1
6,3
7,2
9,2
10,5
11,0
12,3
12,2
14,1
14,6
16,6
18,7
21,3
22,5
25,0

6,9
7,7
8,2
9,0
11,9
13,2
14,1
15,3
16,0
17,9
18,9
20,8
24,3
26,9
28,7
31,1

9,8
10,6
11,3
12,1
16,7
17,9
19,3
20,5
22,7
24,5
26,2
28,1
33,9
36,4
39,2
41,8

4,6
5,4
5,6
6,4
8,1
9,4
9,8
11,0
10,6
12,5
12,9
14,8
16,5
19,0
19,9
22,5

6,5
7,3
7,7
8,6
11,3
12,6
13,4
14,6
15,1
17,0
17,9
19,8
22,9
25,6
27,2
29,7

7,3
8,1
8,6
9,4
12,5
13,8
14,8
16,0
16,8
18,8
19,8
21,7
25,5
28,1
30,1
32,5

8,8
9,7
10,3
11,1
15,1
16,4
17,6
18,8
20,5
22,4
23,8
25,7
30,8
33,3
35,8
38,2

4,9
5,7
5,9
6,7
8,6
9,8
10,3
11,6
11,2
13,1
13,6
15,5
17,4
20,0
21,0
23,5

5,9
6,8
7,1
7,9
10,3
11,6
12,3
13,5
13,7
15,6
16,3
18,3
21,0
23,6
25,0
27,5

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

51
53
58
59
62
64
58
66
67
71
73
64
68
73
79
82
83
86
79
82
86
86
89
92
96
99

31
31
36
37
39
40
35
39
42
44
46
38
43
43
49
52
52
54
47
52
51
53
56
57
60
63

48
50
54
55
58
60
54
61
63
66
68
60
63
68
74
77
78
80
73
77
80
80
84
86
89
93

28
29
33
35
36
38
32
36
39
41
43
35
39
40
45
48
48
51
43
48
46
48
53
53
55
59

43
45
49
51
53
55
49
56
58
61
63
55
58
62
67
70
71
74
67
70
73
73
77
79
82
85

25
26
30
32
32
35
29
32
36
37
40
32
36
35
41
44
44
47
39
44
42
44
48
48
50
54

39
40
44
46
48
49
44
50
52
55
57
49
52
55
61
63
64
67
60
63
65
66
69
71
74
77

27
27
31
33
34
36
30
34
38
39
41
33
38
37
43
46
46
49
41
46
44
46
50
50
52
56

49
52
56
57
60
62
56
64
65
68
71
62
66
71
76
79
80
83
76
80
83
83
87
89
93
96

34
35
39
41
42
44
38
43
46
48
50
43
46
48
54
56
57
59
52
56
56
58
61
63
65
68

45
47
51
52
55
56
51
58
59
62
65
56
60
64
70
72
73
76
69
73
75
76
79
81
84
88

31
32
36
38
39
41
35
40
43
44
47
39
43
44
49
52
52
55
48
52
51
53
57
58
60
64

39
41
45
46
48
50
45
51
53
55
57
50
53
56
62
64
65
68
61
64
66
67
70
72
75
78

54
56
61
62
65
--61
69
71
74
77
68
71
77
83
86
87
--83
86
90
90
94
97
100
---

28
28
32
34
35
37
31
35
39
40
42
34
39
39
44
47
47
50
43
47
46
47
52
52
54
58

38
39
43
44
46
48
42
48
50
53
55
47
51
53
59
61
62
64
58
61
62
64
67
69
71
75

41
43
47
48
51
52
47
53
55
58
60
52
55
59
64
67
68
70
64
67
69
70
73
75
78
81

49
51
55
57
59
61
55
63
65
68
70
62
65
70
76
79
80
83
75
79
82
82
86
88
92
96

29
30
34
36
37
39
33
37
40
42
44
36
41
41
46
49
49
52
45
49
48
50
54
54
57
60

35
35
40
41
43
44
39
44
47
49
51
43
47
49
54
57
58
60
53
57
57
59
62
64
66
69

Cooling capacity in l/s*


MODEL
NO.

AT/UAT 18-49
AT/UAT 18-59
AT/UAT 18-69
AT/UAT 18-79
AT/UAT 18-89
AT/UAT 18-99
AT/UAT18-511
AT/UAT 18-611
AT/UAT 18-711
AT/UAT 18-811
AT/UAT 18-911
AT/UAT 18-312
AT/UAT 18-412
AT/UAT 18-512
AT/UAT 18-612
AT/UAT 18-712
AT/UAT 18-812
AT/UAT 18-912
AT/UAT 18-214
AT/UAT 18-314
AT/UAT 18-414
AT/UAT 18-514
AT/UAT 18-614
AT/UAT 18-714
AT/UAT 18-814
AT/UAT 18-914

EWT
LWT
WB

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

28

M O D E L S AT/UAT 28-518

TO

216-914
Cooling capacity in l/s*

MODEL
NO.

AT/UAT 28-518
AT/UAT 28-618
AT/UAT 28-718
AT/UAT 28-818
AT/UAT 28-918
AT/UAT 28-521
AT/UAT 28-621
AT/UAT 28-721
AT/UAT 28-821
AT/UAT 28-921
AT/UAT 28-524
AT/UAT 28-624
AT/UAT 28-724
AT/UAT 28-824
AT/UAT 28-924
AT/UAT 28-428
AT/UAT 28-528
AT/UAT 28-628
AT/UAT 28-728
AT/UAT 28-828
AT/UAT 28-928
AT/UAT 38-236
AT/UAT 38-336
AT/UAT 38-436
AT/UAT 38-536
AT/UAT 38-636
AT/UAT 38-736
AT/UAT 38-836
AT/UAT 38-936
AT/UAT 38-442
AT/UAT 38-542
AT/UAT 38-642
AT/UAT 38-742
AT/UAT 38-842
AT/UAT 38-942
AT/UAT 216-49
AT/UAT 216-59
AT/UAT 216-69
AT/UAT 216-79
AT/UAT 216-89
AT/UAT 216-99
AT/UAT 216-511
AT/UAT 216-611
AT/UAT 216-711
AT/UAT 216-811
AT/UAT 216-911
AT/UAT 216-312
AT/UAT 216-412
AT/UAT 216-512
AT/UAT 216-612
AT/UAT 216-712
AT/UAT 216-812
AT/UAT 216-912
AT/UAT 216-214
AT/UAT 216-314
AT/UAT 216-414
AT/UAT 216-514
AT/UAT 216-614
AT/UAT 216-714
AT/UAT 216-814
AT/UAT 216-914

EWT
LWT
WB

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

99
108
116
125
129
117
121
133
143
148
136
147
157
166
172
157
172
184
191
191
199
180
193
203
220
216
236
249
258
223
258
276
287
287
298
102
107
115
118
124
127
117
133
136
143
148
126
133
143
154
160
162
168
155
162
170
169
177
182
189
197

62
63
72
78
82
70
76
79
89
93
85
87
98
104
109
95
101
114
119
121
126
102
115
128
130
132
146
155
163
139
152
171
179
182
189
62
63
71
75
77
81
70
79
86
89
93
75
83
84
95
101
101
106
93
102
100
104
112
113
118
124

92
100
109
117
121
109
113
124
133
138
127
137
147
155
161
146
160
172
179
179
186
167
180
190
205
202
221
233
241
209
240
258
268
268
279
95
99
108
111
116
119
109
124
127
133
138
117
124
134
144
150
152
157
145
152
158
158
165
170
176
184

57
58
67
72
76
64
70
72
82
87
79
79
90
96
101
87
93
105
110
113
117
92
106
118
119
122
135
144
152
129
139
158
165
169
176
57
57
66
70
71
75
64
72
80
82
87
68
77
77
88
94
93
99
85
95
91
95
104
104
109
116

85
91
100
107
111
99
103
113
122
127
116
125
135
142
148
134
146
158
164
164
171
150
164
174
187
185
202
213
221
191
219
237
246
246
256
87
91
99
101
106
109
99
113
116
122
127
107
114
122
132
137
139
144
132
139
144
145
152
156
162
169

52
52
60
66
70
58
64
65
75
80
72
71
82
87
93
78
83
96
100
104
108
81
95
108
106
110
123
131
140
118
125
143
150
155
162
51
51
60
64
65
69
58
65
73
75
80
61
70
69
80
87
85
91
77
87
82
86
95
94
99
107

76
81
90
97
100
89
93
100
110
114
105
111
121
128
133
120
130
142
148
148
154
132
146
157
166
166
182
192
200
172
194
213
221
222
231
78
80
89
92
95
99
89
101
105
110
114
95
102
108
119
124
125
130
118
125
128
130
137
140
146
152

55
55
63
69
73
61
67
68
78
83
75
75
86
91
97
82
88
100
105
108
112
86
100
113
112
115
128
137
146
123
131
150
157
162
168
54
54
63
67
68
72
61
69
76
78
83
65
73
73
83
90
89
95
81
90
86
90
99
99
103
111

95
104
113
121
125
113
117
128
138
143
131
142
152
161
166
152
166
178
185
185
193
173
187
197
213
209
229
241
250
216
249
267
278
278
289
99
103
112
115
120
123
113
128
131
138
143
122
128
139
149
155
157
163
150
157
164
164
171
176
183
190

68
70
79
86
89
78
83
87
97
102
93
96
107
113
118
105
113
125
131
132
137
114
128
139
144
145
161
170
178
153
169
188
196
197
205
68
70
78
81
84
88
78
88
93
97
102
83
91
94
104
110
111
116
103
111
111
114
121
123
129
135

87
94
103
111
114
102
107
116
126
130
120
129
139
147
152
138
151
163
169
169
176
156
169
180
193
190
209
220
228
197
226
244
253
254
264
90
94
102
105
109
113
102
117
120
126
130
110
117
126
136
142
143
149
136
143
149
149
156
161
167
174

62
64
73
79
82
71
77
80
90
94
86
88
99
105
110
96
103
115
120
122
127
103
117
129
132
134
148
157
165
141
154
173
181
183
191
62
64
72
75
78
81
71
80
86
90
94
76
84
85
96
102
102
107
94
103
101
105
113
114
119
126

77
82
91
98
101
90
95
102
112
116
106
113
123
130
135
121
132
144
150
150
156
135
149
159
169
168
185
195
203
175
198
216
225
225
234
79
82
90
93
97
100
90
102
106
112
116
97
104
110
120
126
127
132
120
127
130
132
139
142
148
154

104
114
122
131
--123
127
140
150
155
143
155
165
174
--165
181
193
201
201
--190
203
214
232
227
248
262
--235
271
290
301
302
--107
112
121
124
130
--123
140
142
150
155
132
139
151
162
168
171
177
163
171
179
178
186
191
198
207

56
57
65
71
75
63
69
71
81
86
78
78
89
94
100
85
91
104
108
111
116
90
103
116
117
119
133
141
150
127
137
155
162
166
173
56
56
65
69
70
74
63
71
78
81
86
67
76
75
86
93
92
98
84
93
89
94
102
102
107
114

74
78
87
94
97
86
90
97
107
111
101
107
117
124
129
115
125
137
143
143
149
127
141
152
160
160
176
186
193
167
187
206
214
215
224
75
77
86
89
92
96
86
97
102
107
111
92
99
104
115
120
121
126
114
121
123
125
132
135
141
147

81
86
95
102
106
94
99
107
117
121
111
118
128
136
141
127
138
150
156
156
163
142
156
166
177
176
193
203
211
182
207
225
234
235
244
83
86
94
97
101
104
94
107
111
117
121
101
108
115
126
131
133
138
125
133
136
138
144
148
154
161

95
103
112
120
124
112
116
127
137
142
130
141
151
159
165
151
165
177
184
184
191
172
185
195
211
208
227
239
248
215
247
265
276
276
287
98
102
111
114
119
122
112
127
130
137
142
121
127
138
148
154
156
162
149
156
163
163
170
175
181
189

59
60
68
74
78
66
72
74
84
89
81
82
93
98
104
90
96
108
113
116
120
95
109
122
123
125
139
148
156
133
144
163
170
173
181
58
59
68
71
73
77
67
75
82
85
89
71
79
80
90
97
96
102
88
97
94
98
106
107
112
119

68
71
80
87
90
79
84
89
99
103
94
98
109
115
120
106
114
127
132
133
139
116
130
141
147
148
163
173
180
155
172
191
199
200
208
69
71
79
83
86
89
79
89
94
99
103
84
92
95
106
112
112
117
105
113
113
116
123
125
131
137

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

29

ENGINEERING

C O O L I N G C A PA C I T Y

ENGINEERING

C O O L I N G C A PA C I T Y
M O D E L S AT/UAT 19-56

TO

110-918

Cooling capacity in l/s*


MODEL
NO.

AT/UAT 19-56
AT/UAT 19-66
AT/UAT 19-76
AT/UAT 19-86
AT/UAT 19-96
AT/UAT 19-28
AT/UAT 19-38
AT/UAT 19-48
AT/UAT 19-58
AT/UAT 19-68
AT/UAT 19-78
AT/UAT 19-88
AT/UAT 19-98
AT/UAT 26-517
AT/UAT 26-617
AT/UAT 26-717
AT/UAT 26-817
AT/UAT 26-917
AT/UAT 28-217
AT/UAT 28-317
AT/UAT 28-417
AT/UAT 28-517
AT/UAT 28-617
AT/UAT 28-717
AT/UAT 28-817
AT/UAT 28-917
AT/UAT 212-59
AT/UAT 212-69
AT/UAT 212-79
AT/UAT 212-89
AT/UAT 212-99
AT/UAT 215-29
AT/UAT 215-39
AT/UAT 215-49
AT/UAT 215-59
AT/UAT 215-69
AT/UAT 215-79
AT/UAT 215-89
AT/UAT 215-99
AT/UAT 110-112
AT/UAT 110-212
AT/UAT 110-312
AT/UAT 110-412
AT/UAT 110-512
AT/UAT 110-612
AT/UAT 110-712
AT/UAT 110-812
AT/UAT 110-912
AT/UAT 110-118
AT/UAT 110-218
AT/UAT 110-318
AT/UAT 110-418
AT/UAT 110-518
AT/UAT 110-618
AT/UAT 110-718
AT/UAT 110-818
AT/UAT 110-918

EWT
LWT
WB

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

32
34
37
40
45
39
42
44
45
48
49
52
54
64
69
74
80
90
78
83
89
89
96
98
104
109
64
69
74
80
90
78
83
89
89
96
98
104
109
83
90
90
93
96
98
101
103
108
111
111
119
124
127
134
137
145
150

18
20
23
25
28
22
24
26
27
29
31
32
34
36
40
45
50
57
43
47
51
54
58
62
65
69
36
40
45
50
57
43
47
51
54
58
62
65
69
50
52
55
55
59
62
62
65
68
62
69
71
71
77
81
87
90
95

29
32
35
37
42
36
39
41
42
45
46
49
51
59
64
69
75
84
72
77
82
83
89
92
97
102
59
64
69
75
84
72
77
82
83
89
92
97
102
78
83
84
87
90
92
94
97
101
102
104
111
115
118
125
128
136
140

16
18
21
23
27
20
21
23
25
27
29
30
32
32
36
42
46
53
39
43
47
49
54
58
60
64
32
36
42
46
53
39
43
47
49
54
58
60
64
46
48
51
51
55
58
58
61
64
56
64
65
65
70
75
80
83
88

26
29
32
34
39
32
35
37
38
41
42
45
47
53
58
64
69
78
65
70
75
76
82
84
89
93
53
58
64
69
78
65
70
75
76
82
84
89
93
71
76
77
79
82
84
86
89
92
92
95
101
104
108
114
118
124
128

14
16
19
21
24
17
19
21
22
24
26
27
29
29
32
37
41
49
35
38
41
44
48
53
54
59
29
32
37
41
49
35
38
41
44
48
53
54
59
41
43
46
45
49
53
52
56
58
49
58
58
58
63
67
74
75
81

23
25
28
31
35
28
31
33
34
37
38
40
42
47
51
57
62
70
57
62
66
68
73
76
80
84
47
51
57
62
70
57
62
66
68
73
76
80
84
63
67
69
71
74
76
78
80
83
81
86
90
92
97
102
106
112
116

15
17
20
22
25
18
20
22
23
25
27
28
31
30
34
39
43
51
37
40
44
47
51
55
57
61
30
34
39
43
51
37
40
44
47
51
55
57
61
43
45
48
48
52
55
55
58
61
52
61
61
61
66
71
77
78
84

31
33
36
39
44
37
40
43
43
46
48
50
53
61
67
72
78
87
75
80
86
86
93
95
101
105
61
67
72
78
87
75
80
86
86
93
95
101
105
81
87
87
90
93
95
97
100
104
107
108
115
120
123
129
133
141
145

20
22
25
27
31
24
26
28
30
32
34
35
37
40
44
50
54
62
49
53
57
59
64
67
71
75
40
44
50
54
62
49
53
57
59
64
67
71
75
55
58
61
61
65
67
69
71
74
69
76
78
79
85
90
94
98
103

27
30
33
35
40
34
36
39
39
42
43
46
48
55
60
66
71
80
67
72
77
78
84
87
92
96
55
60
66
71
80
67
72
77
78
84
87
92
96
73
78
80
82
85
87
89
91
95
95
98
104
108
112
118
121
128
132

18
20
23
25
29
22
24
26
27
30
31
33
35
36
40
46
50
58
44
48
52
54
59
63
65
69
36
40
46
50
58
44
48
52
54
59
63
65
69
51
53
56
56
60
63
63
66
69
63
70
71
72
77
82
87
91
96

24
26
29
31
35
29
31
34
34
37
39
41
43
48
52
58
63
71
58
63
67
69
74
77
82
85
48
52
58
63
71
58
63
67
69
74
77
82
85
64
68
70
72
75
77
79
81
85
82
87
91
94
98
104
108
113
118

34
36
39
42
47
41
44
47
47
50
52
55
57
67
73
78
85
95
82
88
94
94
101
103
110
114
67
73
78
85
95
82
88
94
94
101
103
110
114
88
94
95
98
101
103
106
108
--117
117
125
131
134
141
144
153
157

16
18
20
22
26
19
21
23
24
26
28
29
31
32
35
41
45
52
38
42
46
48
53
57
59
63
32
35
41
45
52
38
42
46
48
53
57
59
63
45
47
50
50
54
57
57
60
63
55
63
63
63
69
73
79
81
87

22
24
27
30
34
27
30
32
33
35
37
39
41
45
49
55
60
68
55
59
63
66
71
74
78
82
45
49
55
60
68
55
59
63
66
71
74
78
82
61
65
67
68
71
74
75
77
81
78
83
87
89
93
99
103
108
112

25
27
30
33
37
30
33
35
36
39
40
43
44
50
55
60
66
74
61
66
71
72
78
80
85
89
50
55
60
66
74
61
66
71
72
78
80
85
89
67
72
73
75
78
80
82
84
88
87
91
96
98
103
108
112
118
122

30
33
36
38
43
37
40
42
43
46
47
50
52
61
66
72
77
87
74
80
85
86
92
94
100
105
61
66
72
77
87
74
80
85
86
92
94
100
105
80
86
87
90
92
94
97
99
104
106
107
114
119
122
128
132
140
144

17
19
21
23
27
20
22
24
25
28
30
31
33
33
37
43
47
55
41
45
48
51
55
59
61
66
33
37
43
47
55
41
45
48
51
55
59
61
66
47
50
52
52
56
59
59
62
65
58
66
67
67
72
77
83
85
90

20
22
25
28
31
25
27
29
30
33
34
36
38
41
45
51
55
63
50
54
58
60
65
68
72
76
41
45
51
55
63
50
54
58
60
65
68
72
76
56
59
62
62
66
68
70
72
75
71
77
80
81
86
91
96
100
104

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

30

M O D E L S AT/UAT 210-124

TO

112-914
Cooling capacity in l/s*

MODEL
NO.

AT/UAT 210-124
AT/UAT 210-224
AT/UAT 210-324
AT/UAT 210-424
AT/UAT 210-524
AT/UAT 210-624
AT/UAT 210-724
AT/UAT 210-824
AT/UAT 210-924
AT/UAT 210-136
AT/UAT 210-236
AT/UAT 210-336
AT/UAT 210-436
AT/UAT 210-536
AT/UAT 210-636
AT/UAT 210-736
AT/UAT 210-836
AT/UAT 210-936
AT/UAT 310-136
AT/UAT 310-236
AT/UAT 310-336
AT/UAT 310-436
AT/UAT 310-536
AT/UAT 310-636
AT/UAT 310-736
AT/UAT 310-836
AT/UAT 310-936
AT/UAT 310-154
AT/UAT 310-254
AT/UAT 310-354
AT/UAT 310-454
AT/UAT 310-554
AT/UAT 310-654
AT/UAT 310-754
AT/UAT 310-854
AT/UAT 310-954
AT/UAT 112-012
AT/UAT 112-112
AT/UAT 112-212
AT/UAT 112-312
AT/UAT 112-412
AT/UAT 112-512
AT/UAT 112-612
AT/UAT 112-712
AT/UAT 112-812
AT/UAT 112-912
AT/UAT 112-314
AT/UAT 112-414
AT/UAT 112-514
AT/UAT 112-614
AT/UAT 112-714
AT/UAT 112-814
AT/UAT 112-914

EWT
LWT
WB

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

167
179
181
187
192
196
201
206
215
221
223
238
248
254
267
275
290
300
247
265
268
277
284
291
298
306
319
328
332
353
369
378
397
409
432
446
94
101
108
108
113
111
115
122
126
135
124
126
130
133
138
145
151

100
105
110
111
118
124
125
131
136
124
138
141
142
153
163
173
179
189
149
155
163
163
175
184
185
193
202
183
205
209
211
227
241
257
266
281
53
58
63
66
67
70
71
76
80
86
72
77
82
82
87
90
95

156
167
169
174
179
183
188
193
201
204
208
221
230
237
250
257
271
280
231
247
250
258
266
272
279
286
299
303
310
329
342
352
371
382
404
417
87
94
100
101
105
104
108
114
118
126
116
118
121
125
129
136
141

92
96
101
101
109
115
115
122
127
112
128
129
130
140
150
161
165
176
136
141
150
149
161
171
171
180
188
165
190
191
192
208
222
239
245
262
48
53
57
61
61
65
66
70
75
80
66
71
76
76
81
83
89

142
152
154
159
164
168
173
177
185
184
191
202
208
216
228
236
249
257
211
224
229
235
243
250
256
263
274
273
284
300
309
322
339
350
370
382
79
85
91
92
96
95
99
105
109
116
105
108
111
114
118
124
129

83
86
91
91
99
106
105
112
117
98
116
116
115
126
135
147
150
162
122
127
135
134
146
157
155
165
173
145
173
171
171
187
200
219
222
240
43
47
51
55
55
59
59
64
69
73
59
64
70
68
74
76
82

127
134
138
141
147
152
155
160
167
162
172
180
184
193
204
212
223
232
188
199
205
209
219
225
230
237
247
240
255
267
273
287
304
316
332
345
69
75
81
83
85
86
89
94
98
105
93
96
100
103
107
112
117

87
90
96
95
104
110
110
116
122
105
122
122
122
133
142
153
157
169
128
133
142
141
153
163
162
172
180
155
181
181
180
197
210
228
233
250
45
50
54
57
58
62
62
67
71
76
62
67
73
72
77
79
85

161
173
175
181
186
190
195
200
209
213
216
230
239
246
259
266
281
290
239
256
259
268
275
282
289
296
309
316
321
342
356
365
385
396
418
431
91
98
104
105
109
107
112
118
122
131
120
122
126
129
134
140
146

111
117
121
123
130
135
137
142
148
139
151
157
159
169
179
189
197
206
164
172
180
181
192
200
203
211
220
205
225
232
236
251
266
280
292
306
60
65
70
73
74
76
78
83
87
93
81
85
89
90
95
99
104

147
157
159
164
169
173
178
182
190
191
197
208
216
223
236
243
256
265
217
232
236
243
251
257
263
270
282
283
292
310
321
332
350
361
381
394
81
88
94
95
99
98
102
108
112
120
109
111
115
118
122
128
133

102
106
112
112
120
125
126
132
138
125
139
143
144
155
164
175
181
191
150
157
165
165
177
185
187
195
204
185
207
212
214
230
244
260
269
284
54
59
64
67
68
71
72
77
81
86
73
78
83
83
88
91
96

129
137
141
143
150
154
157
162
169
165
174
183
187
196
208
216
227
235
191
202
208
212
222
228
233
240
251
244
259
271
278
292
308
320
337
350
70
77
82
84
87
87
90
96
99
106
95
98
102
104
108
114
118

176
189
190
197
202
206
211
217
--234
235
250
262
267
281
289
305
315
260
280
282
291
299
306
314
322
336
348
349
372
389
397
418
430
454
468
99
107
113
114
119
117
121
128
133
--131
133
137
140
145
152
158

90
94
100
99
107
114
113
120
125
109
126
126
127
137
147
158
162
173
133
139
147
146
158
168
168
177
185
162
187
187
188
204
218
235
241
258
47
52
56
59
60
64
64
69
73
79
65
69
75
74
80
82
87

122
129
134
136
143
147
150
155
162
155
166
173
177
187
197
206
216
225
181
192
198
201
211
218
222
229
240
230
247
257
263
277
293
306
321
334
67
72
78
80
82
83
86
91
95
101
89
93
97
99
103
108
113

135
144
147
150
156
160
164
169
176
173
182
191
197
205
217
225
237
245
200
212
217
222
232
238
243
250
261
257
270
284
292
305
322
334
352
364
74
81
86
88
91
91
94
100
103
111
99
102
106
109
113
118
123

160
172
174
179
184
189
193
198
207
211
214
228
238
244
257
264
279
288
237
255
257
266
273
280
287
294
307
313
319
339
353
363
382
393
415
428
90
97
103
104
109
107
111
117
122
130
119
121
125
128
133
139
145

95
99
105
104
112
118
119
125
130
116
131
133
134
145
154
165
170
181
140
146
155
154
166
175
176
185
193
171
195
198
199
215
229
245
253
269
50
55
59
62
63
67
68
72
76
82
68
73
78
78
83
86
91

113
119
123
125
132
137
139
144
150
141
154
159
162
172
182
191
200
209
167
175
183
184
195
203
206
213
223
209
228
236
240
255
270
284
297
311
61
66
71
74
75
77
79
84
88
94
82
86
90
92
96
100
105

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

31

ENGINEERING

C O O L I N G C A PA C I T Y

ENGINEERING

C O O L I N G C A PA C I T Y
M O D E L S AT/UAT 112-018

TO

312-936

Cooling capacity in l/s*


MODEL
NO.

AT/UAT 112-018
AT/UAT 112-118
AT/UAT 112-218
AT/UAT 112-318
AT/UAT 112-418
AT/UAT 112-518
AT/UAT 112-618
AT/UAT 112-718
AT/UAT 112-818
AT/UAT 112-918
AT/UAT 112-520
AT/UAT 112-620
AT/UAT 112-720
AT/UAT 112-820
AT/UAT 112-920
AT/UAT 212-024
AT/UAT 212-124
AT/UAT 212-224
AT/UAT 212-324
AT/UAT 212-424
AT/UAT 212-524
AT/UAT 212-624
AT/UAT 212-724
AT/UAT 212-824
AT/UAT 212-924
AT/UAT 212-128
AT/UAT 212-228
AT/UAT 212-328
AT/UAT 212-428
AT/UAT 212-528
AT/UAT 212-628
AT/UAT 212-728
AT/UAT 212-828
AT/UAT 212-928
AT/UAT 212-036
AT/UAT 212-136
AT/UAT 212-236
AT/UAT 212-336
AT/UAT 212-436
AT/UAT 212-536
AT/UAT 212-636
AT/UAT 212-736
AT/UAT 212-836
AT/UAT 212-936
AT/UAT 312-036
AT/UAT 312-136
AT/UAT 312-236
AT/UAT 312-336
AT/UAT 312-436
AT/UAT 312-536
AT/UAT 312-636
AT/UAT 312-736
AT/UAT 312-836
AT/UAT 312-936

EWT
LWT
WB

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

147
154
156
164
169
179
185
191
199
206
186
192
201
207
215
203
200
215
216
226
231
239
244
253
270
236
237
248
252
260
267
276
290
301
296
308
320
328
338
358
370
382
397
412
307
303
326
327
336
350
361
370
383
410

84
89
94
100
107
111
117
119
126
131
109
121
124
131
136
117
120
126
132
134
142
151
152
160
171
136
143
145
154
164
164
174
181
191
177
178
201
200
213
221
234
238
252
261
178
182
191
200
212
216
228
230
242
260

136
143
146
153
158
167
173
179
186
193
173
179
188
194
201
188
187
200
202
211
216
223
228
237
253
220
221
231
236
243
249
258
271
282
276
286
299
307
316
335
346
357
372
386
285
283
304
306
314
327
338
346
358
383

76
81
87
92
99
102
109
110
117
122
100
112
115
122
127
106
110
115
121
122
131
140
140
149
160
124
130
132
141
152
151
162
167
178
162
162
186
184
198
205
218
220
235
243
162
167
175
184
197
199
213
212
226
242

123
130
133
140
145
153
159
164
171
177
158
164
172
178
184
171
170
182
185
192
198
205
209
217
232
199
202
210
216
223
228
237
249
259
252
259
274
281
290
307
318
328
341
354
259
258
276
280
288
300
310
317
329
352

68
72
78
83
91
93
100
100
108
112
89
103
104
112
116
95
99
103
109
110
119
129
127
137
147
110
117
118
127
139
137
149
151
163
145
144
170
166
181
185
200
200
216
224
144
150
156
166
180
180
195
193
208
222

109
114
119
126
131
138
143
148
154
160
140
148
155
160
166
151
152
161
165
171
178
185
188
196
209
176
180
186
193
201
205
213
224
233
224
229
247
251
261
276
287
295
308
319
229
230
245
251
260
269
280
285
296
317

72
76
82
87
94
97
104
105
112
117
94
107
109
117
121
100
104
108
115
115
125
134
133
143
153
117
123
124
134
145
144
155
159
170
153
152
178
174
189
194
209
210
224
233
152
158
165
174
188
189
203
202
216
231

142
148
151
159
164
173
179
185
192
200
180
186
194
201
208
196
193
208
209
219
224
231
236
245
262
228
229
240
244
252
258
267
281
292
286
297
309
318
327
347
359
370
385
399
297
293
315
317
325
339
350
358
371
397

94
99
104
110
116
122
127
131
137
142
121
132
136
142
148
130
133
140
145
148
156
164
166
174
186
152
158
161
169
178
180
190
198
207
196
198
219
221
232
243
255
261
274
284
198
201
212
220
231
237
249
252
264
282

128
134
138
145
149
158
164
169
176
182
163
169
177
183
190
176
176
188
190
198
204
211
216
224
239
206
208
217
222
230
236
244
256
266
260
268
282
289
298
316
327
338
351
364
268
266
286
289
297
309
319
327
339
362

85
90
96
101
108
112
118
120
127
132
111
122
126
132
137
118
121
127
133
135
144
152
153
162
173
138
144
147
155
165
166
176
182
193
179
180
203
203
215
224
236
241
254
264
180
184
194
202
214
218
231
232
245
262

111
116
121
128
132
140
145
150
156
162
142
150
157
163
169
153
154
164
168
174
180
187
191
199
212
179
183
189
196
204
208
216
227
237
228
233
250
255
265
280
291
300
312
324
233
234
249
255
264
273
284
289
301
322

155
162
165
173
178
188
195
201
----196
202
211
218
226
214
211
227
227
238
243
251
257
266
--249
249
262
265
273
281
290
305
317
312
325
336
345
355
376
389
402
----324
319
344
344
354
368
380
389
403
---

75
79
85
90
97
100
107
108
115
120
98
111
113
120
125
104
108
113
119
120
129
138
138
147
157
121
128
129
139
150
148
160
164
175
158
158
183
181
195
201
215
217
231
240
158
163
171
180
194
195
209
209
222
238

105
110
115
121
127
133
139
143
149
155
135
144
150
155
161
145
147
156
160
164
172
179
182
190
203
169
174
179
186
195
198
207
217
226
216
220
239
243
253
267
278
286
298
309
220
222
236
242
252
260
271
276
287
307

116
122
127
133
138
146
151
156
163
169
149
157
164
169
176
161
162
172
176
182
188
195
199
207
221
188
191
199
205
212
217
225
237
247
239
245
261
267
276
292
303
312
325
337
244
245
262
266
275
285
296
302
313
335

141
147
150
158
162
172
178
184
191
198
178
184
193
199
206
194
192
207
208
217
222
229
235
243
260
226
227
238
242
250
256
265
279
290
284
295
307
316
325
344
356
367
382
396
294
291
313
315
323
336
347
355
368
394

79
84
89
95
102
105
112
113
120
125
103
115
118
125
130
110
113
119
125
126
135
144
144
153
164
128
135
137
146
156
156
166
172
182
167
167
191
190
203
210
224
227
240
250
167
172
181
189
202
205
218
218
232
248

95
101
106
112
118
123
129
132
139
144
123
133
138
144
150
132
135
142
147
151
159
166
169
176
189
154
160
164
172
181
183
192
201
210
199
201
222
224
235
247
258
265
277
288
201
205
216
223
234
241
252
256
267
286

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

32

M O D E L S AT/UAT 310-042

TO

220-918
Cooling capacity in l/s*

MODEL
NO.

AT/UAT 312-042
AT/UAT 312-142
AT/UAT 312-242
AT/UAT 312-342
AT/UAT 312-442
AT/UAT 312-542
AT/UAT 312-642
AT/UAT 312-742
AT/UAT 312-842
AT/UAT 312-942
AT/UAT 312-054
AT/UAT 312-154
AT/UAT 312-254
AT/UAT 312-354
AT/UAT 312-454
AT/UAT 312-554
AT/UAT 312-654
AT/UAT 312-754
AT/UAT 312-854
AT/UAT 312-954
AT/UAT 312-260
AT/UAT 312-360
AT/UAT 312-460
AT/UAT 312-560
AT/UAT 312-660
AT/UAT 312-760
AT/UAT 312-860
AT/UAT 312-960
AT/UAT 220-112
AT/UAT 220-212
AT/UAT 220-312
AT/UAT 220-412
AT/UAT 220-512
AT/UAT 220-612
AT/UAT 220-712
AT/UAT 220-812
AT/UAT 220-912
AT/UAT 220-118
AT/UAT 220-218
AT/UAT 220-318
AT/UAT 220-418
AT/UAT 220-518
AT/UAT 220-618
AT/UAT 220-718
AT/UAT 220-818
AT/UAT 220-918

EWT
LWT
WB

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

335
358
342
359
382
394
404
418
439
456
464
472
504
495
509
540
558
576
599
--476
487
555
557
572
599
618
641
167
179
181
187
192
196
201
206
215
221
223
238
248
254
267
275
290
300

198
207
213
216
233
248
249
264
274
289
268
285
297
302
321
334
353
360
379
394
282
304
326
341
361
371
391
406
100
105
110
111
118
124
125
131
136
124
138
141
142
153
163
173
179
189

312
333
319
335
357
368
378
391
411
427
431
440
469
462
476
505
522
539
560
581
443
455
517
520
535
560
578
600
156
167
169
174
179
183
188
193
201
204
208
221
230
237
250
257
271
280

182
188
198
198
214
231
229
246
253
269
244
262
271
278
298
309
329
333
353
367
258
282
298
313
336
342
364
378
92
96
101
101
109
115
115
122
127
112
128
129
130
140
150
161
165
176

284
302
293
306
327
338
346
358
377
392
391
402
427
423
437
463
479
494
514
533
403
417
470
476
491
514
530
550
142
152
154
159
164
168
173
177
185
184
191
202
208
216
228
236
249
257

163
168
180
178
193
211
208
225
230
247
217
235
243
250
273
280
302
302
325
338
231
257
267
282
307
310
334
347
83
86
91
91
99
106
105
112
117
98
116
116
115
126
135
147
150
162

253
267
263
273
293
304
311
323
339
353
345
359
379
379
394
416
432
445
464
481
359
376
417
427
442
461
478
496
127
134
138
141
147
152
155
160
167
162
172
180
184
193
204
212
223
232

171
177
188
187
203
220
218
235
241
258
230
247
256
263
285
293
314
317
338
351
243
268
281
297
320
325
348
361
87
90
96
95
104
110
110
116
122
105
122
122
122
133
142
153
157
169

323
346
331
347
370
381
391
404
425
442
448
456
487
479
493
522
541
558
580
602
460
472
536
539
554
580
599
621
161
173
175
181
186
190
195
200
209
213
216
230
239
246
259
266
281
290

220
230
233
239
257
270
274
287
300
314
299
315
329
333
350
367
384
394
413
428
313
333
362
375
393
407
425
441
111
117
121
123
130
135
137
142
148
139
151
157
159
169
179
189
197
206

293
312
302
315
337
348
357
369
388
403
404
415
441
436
450
477
493
509
530
549
417
430
486
491
506
529
546
567
147
157
159
164
169
173
178
182
190
191
197
208
216
223
236
243
256
265

201
210
215
219
236
251
252
266
276
292
272
288
300
306
324
338
356
363
383
397
285
307
330
344
364
375
395
410
102
106
112
112
120
125
126
132
138
125
139
143
144
155
164
175
181
191

257
271
267
277
297
309
315
328
344
358
351
365
386
385
399
422
438
452
470
488
365
381
425
433
449
468
485
503
129
137
141
143
150
154
157
162
169
165
174
183
187
196
208
216
227
235

352
378
359
378
402
414
425
439
462
--489
496
530
520
536
567
587
605
----501
512
585
585
602
630
650
674
176
189
190
197
202
206
211
217
--234
235
250
262
267
281
289
305
315

178
184
194
194
211
227
225
242
249
265
239
256
266
273
293
303
323
327
348
361
252
277
292
307
330
336
358
372
90
94
100
99
107
114
113
120
125
109
126
126
127
137
147
158
162
173

244
256
255
264
283
295
301
313
328
342
332
347
365
366
381
402
419
431
449
466
347
364
402
412
429
446
463
481
122
129
134
136
143
147
150
155
162
155
166
173
177
187
197
206
216
225

269
285
279
290
310
322
329
342
359
373
369
382
404
402
416
440
456
471
490
508
382
397
445
452
468
489
506
524
135
144
147
150
156
160
164
169
176
173
182
191
197
205
217
225
237
245

321
343
328
345
367
378
388
402
422
439
444
453
483
476
490
519
537
554
576
597
456
468
532
535
550
576
594
616
160
172
174
179
184
189
193
198
207
211
214
228
238
244
257
264
279
288

187
195
203
205
221
237
236
252
260
276
252
270
280
286
306
317
337
342
362
376
266
289
308
323
345
352
373
388
95
99
105
104
112
118
119
125
130
116
131
133
134
145
154
165
170
181

224
234
237
243
261
274
278
291
304
319
304
320
335
338
355
372
389
399
418
434
318
337
368
380
398
413
431
447
113
119
123
125
132
137
139
144
150
141
154
159
162
172
182
191
200
209

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

33

ENGINEERING

C O O L I N G C A PA C I T Y

ENGINEERING

C O O L I N G C A PA C I T Y
M O D E L S AT/UAT 420-124

TO

424-936

Cooling capacity in l/s*


MODEL
NO.

AT/UAT 420-124
AT/UAT 420-224
AT/UAT 420-324
AT/UAT 420-424
AT/UAT 420-524
AT/UAT 420-624
AT/UAT 420-724
AT/UAT 420-824
AT/UAT 420-924
AT/UAT 420-136
AT/UAT 420-236
AT/UAT 420-336
AT/UAT 420-436
AT/UAT 420-536
AT/UAT 420-636
AT/UAT 420-736
AT/UAT 420-836
AT/UAT 420-936
AT/UAT 224-018
AT/UAT 224-118
AT/UAT 224-218
AT/UAT 224-318
AT/UAT 224-418
AT/UAT 224-518
AT/UAT 224-618
AT/UAT 224-718
AT/UAT 224-818
AT/UAT 224-918
AT/UAT 224-720
AT/UAT 224-820
AT/UAT 224-920
AT/UAT 424-024
AT/UAT 424-124
AT/UAT 424-224
AT/UAT 424-324
AT/UAT 424-424
AT/UAT 424-524
AT/UAT 424-624
AT/UAT 424-724
AT/UAT 424-824
AT/UAT 424-924
AT/UAT 424-028
AT/UAT 424-128
AT/UAT 424-228
AT/UAT 424-328
AT/UAT 424-428
AT/UAT 424-528
AT/UAT 424-628
AT/UAT 424-728
AT/UAT 424-828
AT/UAT 424-928
AT/UAT 424-036
AT/UAT 424-136
AT/UAT 424-236
AT/UAT 424-336
AT/UAT 424-436
AT/UAT 424-536
AT/UAT 424-636
AT/UAT 424-736
AT/UAT 424-836
AT/UAT 424-936

EWT
LWT
WB

32
27
19

36
26
19

32
27
20

36
26
20

32
27
21

36
26
21

32
27
22

37
27
22

35
30
24

40
30
24

35
30
25

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

36
31
27

37
32
27

41
31
27

42
32
27

332
356
359
372
382
391
400
411
429
427
433
461
480
493
519
534
564
582
294
308
313
334
328
338
358
382
397
412
376
406
421
374
403
398
429
430
450
442
460
486
538
441
438
470
471
483
502
517
531
549
600
542
570
607
648
638
656
695
742
772
801

200
209
219
220
235
247
249
260
271
237
267
272
274
295
314
336
347
367
168
178
189
197
200
213
221
238
252
261
237
257
266
212
232
239
250
262
266
278
283
302
341
250
272
271
283
303
305
326
326
347
380
304
323
365
378
387
413
428
462
488
507

310
332
336
346
357
365
374
384
401
394
404
429
445
460
484
499
527
544
273
286
292
311
307
316
335
357
372
386
351
380
394
346
375
371
399
402
419
413
430
454
503
408
409
437
440
452
469
484
496
513
561
501
528
566
603
595
613
650
694
722
749

183
190
202
201
217
230
230
242
253
214
247
248
249
270
288
312
319
342
153
162
173
180
184
198
205
220
235
243
220
239
248
192
211
218
228
241
243
259
261
279
318
226
252
246
259
281
281
303
301
323
354
275
292
334
345
355
383
395
426
455
473

283
302
307
315
327
335
343
352
368
355
370
391
402
419
442
458
483
499
247
259
267
283
281
290
307
328
341
354
322
348
361
312
339
339
362
367
382
379
394
417
462
368
375
395
401
414
429
444
455
471
515
452
476
517
548
544
563
595
636
662
687

164
170
182
180
196
210
208
222
232
187
225
222
221
242
259
285
288
313
136
144
156
161
166
181
185
200
216
224
202
219
228
170
188
196
204
217
218
237
236
253
292
201
230
219
233
257
253
277
272
296
325
242
260
300
309
319
351
357
387
418
434

252
267
275
281
293
302
309
318
332
311
333
347
355
374
396
412
433
450
218
229
238
251
251
261
276
295
308
319
291
314
326
275
300
302
321
329
340
342
353
375
417
324
337
349
358
373
384
400
408
425
464
397
420
461
485
487
507
535
573
597
620

173
180
191
190
206
219
218
231
242
199
235
234
233
255
272
297
303
326
143
152
164
169
174
189
194
210
224
233
210
229
237
180
199
207
215
228
229
247
248
265
304
212
240
232
245
268
266
289
285
308
338
258
275
316
326
336
366
375
405
435
452

321
344
348
359
369
378
388
398
415
411
419
446
463
477
502
517
546
563
284
297
303
323
318
327
347
370
385
399
364
393
408
360
389
385
414
416
435
428
445
470
521
425
424
454
456
468
486
501
514
532
581
522
549
587
626
617
635
673
718
747
775

221
232
242
244
258
268
273
283
295
266
293
302
306
326
347
366
381
400
188
198
209
218
221
232
243
261
274
284
258
279
290
237
259
264
278
289
295
303
311
331
371
280
298
302
313
331
337
355
359
377
413
341
361
403
421
426
450
471
506
531
551

292
312
317
326
337
345
354
363
379
368
382
404
417
433
457
471
498
514
256
268
275
293
289
298
316
338
351
364
332
359
372
324
351
350
375
379
394
390
406
429
476
382
386
409
414
427
442
457
469
485
530
468
493
533
567
561
580
614
656
682
708

202
211
222
222
238
249
251
262
274
240
270
275
277
299
317
339
350
371
170
180
191
199
203
215
224
241
254
264
239
259
269
214
235
242
253
265
269
281
286
305
344
253
275
274
287
306
309
329
330
350
383
308
327
369
383
391
417
433
466
493
512

256
272
280
285
298
306
313
322
337
317
338
353
361
380
402
418
440
456
221
233
242
256
255
265
280
300
312
324
295
319
331
280
305
307
327
334
345
346
359
380
423
330
342
355
364
379
390
406
414
431
471
404
427
469
494
494
514
543
581
606
629

349
376
378
391
401
411
421
432
451
453
455
486
508
519
546
561
593
612
311
325
329
352
345
355
376
402
----395
427
443
395
425
419
452
452
474
465
483
511
--466
460
496
496
508
528
544
558
577
631
574
602
639
683
670
690
731
780
811
---

179
186
198
197
213
226
226
238
249
209
243
243
243
265
282
306
313
336
149
158
170
176
181
195
201
217
231
240
217
235
244
187
207
214
224
236
238
254
256
274
313
221
248
241
254
277
276
298
295
318
348
268
286
327
338
348
377
387
419
448
465

243
257
266
270
284
293
299
308
322
299
321
335
341
361
382
399
419
436
209
220
230
242
243
253
267
286
298
309
282
304
316
264
288
291
309
318
327
331
342
362
404
312
327
336
346
361
371
387
394
411
450
381
403
445
468
470
491
517
554
579
601

268
285
292
299
311
319
327
336
351
334
352
370
380
398
420
436
459
476
233
245
253
268
267
276
292
312
325
337
307
332
344
295
320
321
343
349
362
361
375
397
440
347
357
373
381
395
408
423
432
449
491
426
449
490
518
517
536
567
606
631
655

319
342
345
357
367
375
385
395
412
408
416
442
460
473
498
513
542
559
282
295
300
321
316
325
344
367
382
396
361
390
405
357
386
382
411
413
432
425
442
467
518
421
421
450
453
465
483
497
510
528
577
518
545
583
621
612
631
668
713
742
770

189
197
208
207
223
236
236
248
259
222
254
256
258
278
297
320
329
351
158
167
179
186
190
203
210
227
240
250
226
245
254
199
218
225
236
248
251
265
269
286
326
234
259
255
268
289
289
311
310
331
363
284
303
344
357
366
394
407
438
467
484

224
236
245
248
262
272
277
287
299
271
297
307
311
332
352
371
387
405
191
201
212
222
224
235
247
265
277
288
262
283
294
241
263
268
283
293
300
307
316
336
376
284
302
307
318
336
342
360
364
383
419
347
368
410
428
433
456
478
513
539
559

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

34

M O D E L S AT/UAT 114-0124

428-1248

TO

Cooling capacity in l/s*


MODEL
NO.

AT/UAT 114-0124
AT/UAT 114-0224
AT/UAT 114-0324
AT/UAT 114-0424
AT/UAT 114-0524
AT/UAT 114-0624
AT/UAT 114-0724
AT/UAT 114-0824
AT/UAT 114-0924
AT/UAT 114-1024
AT/UAT 114-1124
AT/UAT 114-1224
AT/UAT 214-0148
AT/UAT 214-0248
AT/UAT 214-0348
AT/UAT 214-0448
AT/UAT 214-0548
AT/UAT 214-0648
AT/UAT 214-0748
AT/UAT 214-0848
AT/UAT 214-0948
AT/UAT 214-1048
AT/UAT 214-1148
AT/UAT 314-0172
AT/UAT 314-0272
AT/UAT 314-0372
AT/UAT 314-0472
AT/UAT 314-0572
AT/UAT 314-0672
AT/UAT 314-0772
AT/UAT 314-0872
AT/UAT 314-0972
AT/UAT 314-1072
AT/UAT 314-1172
AT/UAT 314-1272
AT/UAT 228-0124
AT/UAT 228-0224
AT/UAT 228-0324
AT/UAT 228-0424
AT/UAT 228-0524
AT/UAT 228-0624
AT/UAT 228-0724
AT/UAT 228-0824
AT/UAT 228-0924
AT/UAT 428-0148
AT/UAT 428-0248
AT/UAT 428-0348
AT/UAT 428-0448
AT/UAT 428-0548
AT/UAT 428-0648
AT/UAT 428-0748
AT/UAT 428-0848
AT/UAT 428-0948
AT/UAT 428-1048
AT/UAT 428-1148
AT/UAT 428-1248
AT/UAT 428-1348

EWT
LWT
WB

32
27
19

206
220
221
234
230
241
250
255
263
269
278
292
403
432
460
434
453
473
491
516
528
546
574
600
643
684
646
674
704
745
731
769
786
813
856
430
458
432
451
471
498
526
544
572
757
813
867
823
859
895
949
931
979
1001
1036
1090
1176

36
26
19

32
27
20

36
26
20

32
27
21

114 190 103 171


125 204 113 184
137 206 127 189
134 217 122 197
144 215 133 197
145 225 133 205
157 233 146 214
155 238 143 218
166 246 154 225
165 251 152 230
175 260 163 238
185 273 172 251
223 372 202 335
243 399 220 360
262 426 239 385
269 406 250 371
282 423 261 388
284 441 259 402
308 459 286 420
325 483 302 443
324 493 298 451
345 510 321 468
363 537 338 493
331 554 299 498
361 594 326 536
390 634 354 573
401 604 371 553
420 630 389 578
422 656 386 599
452 696 415 636
458 683 425 626
484 719 449 659
482 735 443 672
513 760 477 697
541 800 504 734
242 398 218 359
261 424 237 383
268 404 248 370
281 421 260 386
283 439 258 401
302 465 278 425
322 491 296 450
343 508 319 466
362 535 337 491
413 698 370 626
450 750 407 675
489 802 441 723
508 769 470 704
533 802 493 735
530 834 485 759
570 885 521 808
582 870 539 797
615 916 570 840
607 935 558 854
653 968 606 888
688 1019 640 935
744 1100 693 1009

36
26
21

32
27
22

91
100
116
109
122
119
133
128
141
138
150
158
176
194
212
227
239
233
261
276
269
294
310
262
288
314
338
355
346
373
388
411
400
437
462
193
210
226
238
232
250
267
292
309
324
356
391
428
449
434
468
492
521
502
554
586
636

150
162
170
174
178
183
193
195
203
206
215
226
294
317
340
334
349
359
379
399
405
422
444
436
471
505
498
520
534
569
564
594
603
629
662
315
338
333
348
357
380
403
421
443
548
592
636
632
661
676
721
718
756
764
801
843
910

37
27
22

35
30
24

40
30
24

35
30
25

97 198 129 177


106 212 139 191
121 214 150 195
115 226 150 204
127 223 157 203
126 233 160 212
139 242 171 220
135 246 171 224
147 254 180 232
144 260 182 237
156 269 191 245
165 283 201 258
188 388 251 347
206 416 272 373
224 444 293 399
238 420 295 383
249 438 309 400
246 457 314 415
272 475 336 433
288 500 354 456
283 511 356 466
306 529 375 482
323 556 395 508
278 577 373 516
307 619 404 556
332 660 436 594
354 626 439 570
371 653 460 595
365 681 467 618
392 721 498 656
405 707 501 645
429 744 528 679
420 761 530 693
456 787 559 719
481 828 588 756
205 414 271 372
223 442 292 397
237 418 294 381
248 436 307 398
244 455 312 414
262 482 333 439
281 509 354 464
305 526 374 480
322 554 394 506
345 728 466 651
380 782 507 700
415 835 547 750
447 797 557 726
470 831 583 757
457 865 588 784
493 917 630 833
514 901 636 822
544 948 671 865
528 969 670 882
578 1003 711 915
611 1055 749 963
663 1139 809 1039

40
30
25

35
30
26

37
32
26

40
30
26

42
32
26

116
126
139
136
145
147
158
157
167
167
177
187
226
246
266
272
285
287
311
328
327
348
366
335
366
395
405
425
427
457
463
489
487
518
546
245
264
271
284
286
306
326
346
365
419
456
495
513
538
536
576
587
621
614
659
694
751

153
165
173
177
180
186
196
198
206
209
218
229
299
323
346
339
354
365
384
405
411
428
451
444
480
514
505
527
543
578
572
603
612
638
671
321
344
338
353
363
386
409
427
449
559
603
648
642
671
687
732
728
767
776
812
855
923

218
233
232
247
242
253
263
268
276
282
292
307
427
457
486
456
476
497
516
543
555
574
604
636
680
723
680
709
741
784
768
809
827
855
900
455
483
455
474
496
524
553
572
602
804
861
917
866
903
943
998
979
1030
1053
1089
1146
1236

101
110
125
120
131
130
143
140
151
149
161
169
197
215
233
245
257
254
281
297
292
315
333
291
319
346
365
383
378
406
418
442
435
469
496
214
232
244
256
253
272
291
314
331
360
397
432
462
485
475
511
530
561
547
596
629
682

144
156
165
167
172
177
187
188
197
199
208
219
282
304
327
324
338
346
367
386
391
409
431
419
452
486
482
503
515
549
546
576
582
609
641
303
325
322
337
345
367
390
407
429
525
569
611
611
640
652
695
695
732
738
775
817
882

36
31
27

37
32
27

41
31
27

42
32
27

161 196 107


173 211 117
180 212 131
186 224 126
188 221 137
195 231 137
204 240 149
207 245 147
215 253 158
219 258 157
227 267 168
239 281 177
315 385 209
339 413 228
364 440 247
354 417 256
369 435 269
382 454 268
401 472 293
422 496 310
429 507 307
446 525 329
470 552 347
468 572 310
505 614 338
541 655 367
527 621 382
550 648 400
568 676 398
604 716 428
597 702 437
628 739 461
639 756 456
665 782 490
700 823 516
338 411 226
362 438 246
352 415 255
368 433 267
380 452 266
404 479 286
428 505 305
444 523 328
468 550 345
589 722 385
636 776 422
682 828 458
670 791 484
700 825 507
720 858 500
766 911 538
759 894 554
800 941 586
812 962 576
846 996 622
891 1048 657
962 1131 710

131
142
153
152
160
163
173
173
183
184
194
204
256
277
298
299
313
319
341
359
361
380
401
380
412
443
446
466
474
506
508
535
538
566
597
276
297
298
312
317
339
360
379
399
475
516
557
566
592
598
640
646
680
680
721
759
820

* CE compliant AT/UAT cooling towers require a special protective fan screen. This fan screen reduces the indicated cooling capacity with 2%.
This reduction is incorporated in the CTI certification.
Note: For alternate selections and conditions other than those stated, consult the online selection program or your local EVAPCO representative.

35

ENGINEERING

C O O L I N G C A PA C I T Y

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT 14-64 to 14-912
*14-64 to 14-99
(1) 100 Inlet MPT
(1) 100 Outlet MPT
*14-612 to 14-912
(1) 150 Inlet BFW
(1) 150 Outlet BFW

ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

INLET*

613

AT/UAT
14-64 to 14-96

25 MPT MAKE-UP

AT/UAT
14-69 to 14-912
P

P
50 MPT OVERFLOW

OUTLET*
B

149
127
108

330

502

76
50 MPT DRAIN

613
324

968
1226

Weights (kg)

Dimensions (mm)

Model
No.

Shipping

Operating

Heaviest
Section
(upper)

AT 14-64
AT 14-74
AT 14-84
AT 14-94
AT 14-66
AT 14-76
AT 14-86
AT 14-96
AT 14-69
AT 14-79
AT 14-89
AT 14-99
AT 14-612
AT 14-712
AT 14-812
AT 14-912

490
526
513
549
630
676
640
685
907
980
953
1025
1148
1238
1166
1256

798
835
821
857
1116
1161
1125
1170
1633
1705
1678
1751
2132
2223
2150
2241

330
365
355
390
430
475
440
485
625
700
670
745
805
895
820
910

Fan
Motor
(kW)

Air
Flow
(m3/s)

1,5
1,5
2,2
2,2
2,2
2,2
4,0
4,0
(2)1,5
(2)1,5
(2)2,2
(2)2,2
(2)2,2
(2)2,2
(2)4,0
(2)4,0

4,5
4,4
5,1
5,0
7,2
7,1
8,5
8,3
10,0
9,8
11,3
11,1
14,6
14,3
17,2
16,8

2908
3213
2908
3213
2908
3213
2908
3213
2908
3213
2908
3213
2908
3213
2908
3213

952
952
952
952
952
952
952
952
952
952
952
952
952
952
952
952

1905
2210
1905
2210
1905
2210
1905
2210
1905
2210
1905
2210
1905
2210
1905
2210

1213
1213
1213
1213
1822
1822
1822
1822
2737
2737
2737
2737
3651
3651
3651
3651

NOTE: An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
Unit dimensions and connections are subject to change to meet application requirements and shipping restrions. See factory certified prints for
detailed drawing information.
Height includes fan guard which ships factory mounted.

36

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 18-49 to 18-914

ACCESS DOOR

543

ACCESS
DOOR

51

200 BFW INLET

Swing Out Radius


of Motor Cover
is 777 mm

H
P
50 MPT
MAKE-UP

B
587

200 BFW OUTLET

80 FPT
OVERFLOW

378

133

190

229

92
2388

80 FPT
DRAIN

10

Weights (kg)
Model
No.

AT/UAT 18-49
AT/UAT 18-59
AT/UAT 18-69
AT/UAT 18-79
AT/UAT 18-89
AT/UAT 18-99
AT/UAT 18-511
AT/UAT 18-611
AT/UAT 18-711
AT/UAT 18-811
AT/UAT 18-911
AT/UAT 18-312
AT/UAT 18-412
AT/UAT 18-512
AT/UAT 18-612
AT/UAT 18-712
AT/UAT 18-812
AT/UAT 18-912
AT/UAT 18-214
AT/UAT 18-314
AT/UAT 18-414
AT/UAT 18-514
AT/UAT 18-614
AT/UAT 18-714
AT/UAT 18-814
AT/UAT 18-914

Dimensions (mm)

Heaviest
Section
Shipping Operating (Upper)

1830
1745
1860
1985
1880
2010
2075
2000
2260
2130
2280
2305
2470
2210
2360
2520
2370
2535
2550
2735
2415
2570
2760
2585
2595
2780

3050
2965
3080
3205
3105
3230
3495
3415
3675
3545
3695
3955
4120
3860
4010
4175
4025
4185
4485
4670
4350
4510
4695
4520
4530
4715

1275
1195
1305
1435
1330
1455
1455
1380
1635
1510
1660
1605
1770
1510
1660
1825
1675
1835
1765
1950
1630
1785
1975
1800
1810
1995

Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

7,5
11,0
11,0
11,0
15,0
15,0
7,5
15,0
11,0
15,0
15,0
7,5
7,5
15,0
15,0
15,0
18,5
18,5
11,0
11,0
18,5
15,0
15,0
18,5
22,0
22,0

19,4
22,5
22,0
21,7
24,1
23,7
21,9
27,8
24,5
27,3
26,8
24,4
24,0
31,0
30,4
29,9
32,7
32,1
30,4
29,8
36,3
33,2
32,7
35,6
37,8
37,1

3769
3464
3769
4074
3769
4074
3769
3464
4074
3769
4074
3769
4074
3464
3769
4074
3769
4074
3880
4185
3575
3880
4185
3880
3880
4185

1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1316
1427
1427
1427
1427
1427
1427
1427
1427

2619
2315
2619
2924
2619
2924
2619
2315
2924
2619
2924
2619
2924
2315
2619
2924
2619
2924
2730
3035
2426
2730
3035
2730
2730
3035

2730
2730
2730
2730
2730
2730
3188
3188
3188
3188
3188
3651
3651
3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261
4261
4261

1365
1365
1365
1365
1365
1365
1594
1594
1594
1594
1594
1826
1826
1826
1826
1826
1826
1826
2130
2130
2130
2130
2130
2130
2130
2130

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10mm beyond bottom flange.
Height includes fan guard which ships factory mounted

37

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 28-518 to 28-921
ACCESS DOOR

ACCESS DOOR

543

ACCESS
DOOR

51

Swing Out Radius


of Motor Cover
is 777 mm

ACCESS
DOOR

(2) 200 BFW INLET

H
P
50 MPT
MAKE-UP

80 FPT
OVERFLOW

587
133

378

229

190
2388

Model
No.

AT/UAT 28-518
AT/UAT 28-618
AT/UAT 28-718
AT/UAT 28-818
AT/UAT 28-918
AT/UAT 28-521
AT/UAT 28-621
AT/UAT 28-721
AT/UAT 28-821
AT/UAT 28-921

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

3685
3265
3490
3510
3750
3945
4225
3745
4000
4275

6205
5790
6010
6035
6275
6915
7195
6720
6970
7250

92

10

2605
2185
2410
2430
2670
2760
3040
2565
2815
3095

(2) 200 BFW OUTLET

80 FPT
DRAIN

S
L

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

(2) 5,5
(2) 11,0
(2) 11,0
(2) 15,0
(2) 15,0
(2) 7,5
(2) 7,5
(2) 15,0
(2) 15,0
(2) 15,0

35,2
45,4
44,5
48,8
47,9
44,2
43,4
56,0
54,9
54,0

4286
3677
3981
3981
4286
3981
4286
3677
3981
4286

1529
1529
1529
1529
1529
1529
1529
1529
1529
1529

3137
2527
2832
2832
3137
2832
3137
2527
2832
3137

5486
5486
5486
5486
5486
6401
6401
6401
6401
6401

1372
1372
1372
1372
1372
1600
1600
1600
1600
1600

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10mm beyond bottom flange.
Height includes fan guard which ships factory mounted.

38

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 28-524 to 28-928
ACCESS DOOR

ACCESS DOOR

543

ACCESS
DOOR

51

ACCESS
DOOR

(2) 200 BFW INLET

Swing Out Radius


of Motor Cover
is 777 mm

Q
H
P
B

(2) 50 MPT MAKE-UP

190

92

64

10

Weights (kg)
Model
No.

AT/UAT 28-524
AT/UAT 28-624
AT/UAT 28-724
AT/UAT 28-824
AT/UAT 28-924
AT/UAT 28-428
AT/UAT 28-528
AT/UAT 28-628
AT/UAT 28-728
AT/UAT 28-828
AT/UAT 28-928

Dimensions (mm)

Heaviest
Section
Shipping Operating (Upper)

4925
4410
4710
4735
5060
5125
4855
5200
5215
5570
5590

8230
7710
8010
8040
8365
9000
8725
9070
9090
9445
9460

(2) 200 BFW


OUTLET

(2) 80 FPT DRAIN

378

2388

(2) 80 FPT
OVERFLOW

587

1770
1510
1660
1675
1835
1765
1630
1800
1810
1985
1995

Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

(2) 7,5
(2) 15,0
(2) 15,0
(2) 18,5
(2) 18,5
(2) 11,0
(2) 18,5
(2) 18,5
(2) 22,0
(2) 18,5
(2) 22,0

47,8
61,7
60,5
65,0
63,8
61,7
73,7
72,3
76,7
71,1
75,3

4286
3677
3981
3981
4286
4134
3829
4134
4134
4439
4439

1529
1529
1529
1529
1529
1681
1681
1681
1681
1681
1681

3137
2527
2832
2832
3137
2984
2680
2984
2984
3289
3289

7366
7366
7366
7366
7366
8585
8585
8585
8585
8585
8585

1826
1826
1826
1826
1826
2130
2130
2130
2130
2130
2130

3423
3423
3423
3423
3423
4032
4032
4032
4032
4032
4032

3518
3518
3518
3518
3518
4128
4128
4128
4128
4128
4128

3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
(5) S&Q, N, M and O dimension are similar for both cells.
! Outlet connection extends 10mm beyond bottom flange.
Height includes fan guard which ships factory mounted.

39

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 38-236 to 38-942
ACCESS DOOR

ACCESS DOOR

ACCESS DOOR

543

ACCESS
DOOR

51

ACCESS
DOOR
(3) 200 BFW INLET

Swing Out Radius


of Motor Cover
is 777 mm

ACCESS
DOOR

H
P
B

378
190

10

2388

Model
No.

AT/UAT 38-236
AT/UAT 38-336
AT/UAT 38-436
AT/UAT 38-536
AT/UAT 38-636
AT/UAT 38-736
AT/UAT 38-836
AT/UAT 38-936
AT/UAT 38-442
AT/UAT 38-542
AT/UAT 38-642
AT/UAT 38-742
AT/UAT 38-842
AT/UAT 38-942

11445
11895
12385
11605
11990
12055
12095
12585
13950
13075
13595
13620
14150
14180

1455
1605
1770
1510
1635
1660
1675
1835
1920
1630
1800
1810
1985
1995

(3) 200 BFW OUTLET

(3) 80 FPT DRAIN

(3) 50 MPT MAKE-UP

64

92

Weights (kg)
Heaviest
Sectiont
Shipping Operating (Upper)

6490
6940
7430
6655
7035
7105
7145
7635
8135
7265
7785
7810
8340
8370

(3) 80 FPT
OVERFLOW

587

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

(3) 7,5
(3) 7,5
(3) 7,5
(3) 15,0
(3) 11,0
(3) 15,0
(3) 18,5
(3) 18,5
(3) 7,5
(3) 18,5
(3) 18,5
(3) 22,0
(3) 18,5
(3) 22,0

73,8
72,6
71,3
92,0
82,4
90,2
96,9
95,2
79,4
110,0
107,9
114,4
106,1
112,4

3829
4134
4439
3829
4134
4134
4134
4439
4439
3829
4134
4134
4439
4439

1681
1681
1681
1681
1681
1681
1681
1681
1681
1681
1681
1681
1681
1681

2680
2984
3289
2680
2984
2984
2984
3289
3289
2680
2984
2984
3289
3289

11081
11081
11081
11081
11081
11081
11081
11081
12910
12910
12910
12910
12910
12910

1826
1826
1826
1826
1826
1826
1826
1826
2130
2130
2130
2130
2130
2130

3423
3423
3423
3423
3423
3423
3423
3423
4032
4032
4032
4032
4032
4032

3518
3518
3518
3518
3518
3518
3518
3518
4128
4128
4128
4128
4128
4128

3651
3651
3651
3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as three (3) independent cells with the addition of two flume plates or water tight partition.
(5) S&Q, N, M and O dimensions are similar for all the cells.
! Outlet connection extends 10mm beyond bottom flange.
Height includes fan guard which ships factory mounted.

40

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 216-49 to 216-911

(2) ACCESS DOOR

543

51

(2) 200 BFW INLET

1194

Swing Out Radius


of Motor Cover
is 777 mm

ACCESS
DOOR

ACCESS
DOOR

H
P
B

(2) 200 BFW OUTLET


(2) 80 FTP
OVERFLOW
(2) 50 MPT
MAKE-UP

1848

589

2159

(2) 80 FTP
DRAIN

379

2254

190

2280
130

2388

92

10

4905

Weights (kg)
Model
No.

AT/UAT 216-49
AT/UAT 216-59
AT/UAT 216-69
AT/UAT 216-79
AT/UAT 216-89
AT/UAT 216-99
AT/UAT 216-511
AT/UAT 216-611
AT/UAT 216-711
AT/UAT 216-811
AT/UAT 216-911

Dimensions (mm)

Shipping

Operating

(Upper)
Heaviest
Section

3655
3495
3720
3975
3765
4020
4155
4000
4520
4265
4565

6095
5935
6160
6415
6205
6460
6985
6830
7350
7095
7395

1275
1195
1305
1435
1330
1455
1455
1380
1635
1510
1660

Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 7,5
(2) 11,0
(2) 11,0
(2) 11,0
(2) 15,0
(2) 15,0
(2) 7,5
(2) 15,0
(2) 11,0
(2) 15,0
(2) 15,0

38,4
44,5
43,6
43,0
47,9
47,0
44,2
56,0
49,4
55,0
54,0

4048
3743
4048
4353
4048
4353
4048
3743
4353
4048
4353

1529
1529
1529
1529
1529
1529
1529
1529
1529
1529
1529

2899
2594
2899
3204
2899
3204
2899
2594
3204
2899
3204

2730
2730
2730
2730
2730
2730
3188
3188
3188
3188
3188

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (2) independent operating cells. Consult the factory for details.

! Outlet connection extends 10 mm beyond bottom flange.


Height includes fan guard which ships factory mounted.

41

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 216-312 to 216-914

(2) ACCESS DOOR

543

ACCESS
DOOR

51

1194

(2) 200 BFW INLET

Swing Out Radius


of Motor Cover
is 777 mm

ACCESS
DOOR

H
P

B
(2) 200 BFW OUTLET
(2) 80 FPT
OVERFLOW
(2) 50 MPT
MAKE-UP

1848

589

2159

(2) 80 FTP
DRAIN

379

2254

190

2280
130

92

2388

10

4905

Weights (kg)
Model
No.

Shipping

AT/UAT 216-312
AT/UAT 216-412
AT/UAT 216-512
AT/UAT 216-612
AT/UAT 216-712
AT/UAT 216-812
AT/UAT 216-912
AT/UAT 216-214
AT/UAT 216-314
AT/UAT 216-414
AT/UAT 216-514
AT/UAT 216-614
AT/UAT 216-714
AT/UAT 216-814
AT/UAT 216-914

4610
4935
4420
4715
5045
4745
5070
5100
5470
4825
5145
5515
5170
5190
5560

Dimensions (mm)

(Upper)
Heaviest
Operating Section

7910
8235
7720
8020
8345
8045
8375
8970
9345
8700
9015
9390
9045
9065
9435

1605
1770
1510
1660
1825
1675
1835
1765
1950
1630
1785
1975
1800
1810
1995

Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 7,5
(2) 7,5
(2) 15,0
(2) 15,0
(2) 15,0
(2) 18,5
(2) 18,5
(2) 11,0
(2) 11,0
(2) 18,5
(2) 15,0
(2) 15,0
(2) 18,5
(2) 22,0
(2) 22,0

48,0
47,1
60,8
59,6
58,7
64,1
62,9
61,6
60,5
73,6
67,4
66,2
72,2
76,6
75,3

4048
4353
3743
4048
4353
4048
4353
4201
4505
3896
4201
4505
4201
4201
4505

1529
1529
1529
1529
1529
1529
1529
1681
1681
1681
1681
1681
1681
1681
1681

2899
3204
2594
2899
3204
2899
3204
3051
3356
2746
3051
3356
3051
3051
3356

3651
3651
3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261
4261
4261

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (2) independent operating cells. Consult the factory for details.

! Outlet connection extends 10 mm beyond bottom flange.


Height includes fan guard which ships factory mounted.

42

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 19-56 to 19-98
ACCESS DOOR

543

51

ACCESS DOOR

150 BFW INLET

Swing Out Radius


of Motor Cover
is 777 mm

1289

H
P
50 MPT
MAKE-UP

B
587

80 MPT
OVERFLOW

378

133

165
92

Model
No.

AT/UAT 19-56
AT/UAT 19-66
AT/UAT 19-76
AT/UAT 19-86
AT/UAT 19-96
AT/UAT 19-28
AT/UAT 19-38
AT/UAT 19-48
AT/UAT 19-58
AT/UAT 19-68
AT/UAT 19-78
AT/UAT 19-88
AT/UAT 19-98

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

1390
1405
1495
1510
1640
1565
1585
1595
1685
1700
1825
1730
1850

80 FPT
DRAIN

229
1289

10

2315
2330
2420
2435
2565
2665
2680
2695
2785
2800
2920
2825
2950

910
930
1020
1035
1165
1035
1050
1065
1155
1170
1295
1195
1320

150 BFW
OUTLET

2578

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

4,0
5,5
5,5
7,5
11,0
4,0
5,5
7,5
5,5
7,5
7,5
11,0
11,0

12,5
14,2
14,0
15,3
17,1
14,7
16,8
18,5
16,5
18,1
17,8
20,6
20,3

3258
3258
3562
3562
3867
3258
3258
3258
3562
3562
3867
3562
3867

1224
1224
1224
1224
1224
1224
1224
1224
1224
1224
1224
1224
1224

2197
2197
2502
2502
2807
2197
2197
2197
2502
2502
2807
2502
2807

1826
1826
1826
1826
1826
2283
2283
2283
2283
2283
2283
2283
2283

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.

! Outlet connection extends 10 mm beyond bottom flange.


Height includes fan guard which ships factory mounted.

43

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 26-517 to 28-917

ACCESS DOOR

ACCESS DOOR

543

ACCESS
DOOR

ACCESS
DOOR

(2) 150 BFW INLET

1289

51

Swing Out Radius


of Motor Cover
is 777 mm

H
P
B

(2) 150 BFW OUTLET


(2) 80 FPT
OVERFLOW

587

(2) 80 FPT
DRAIN

1289

378

2350

165

137

98

Model
No.

AT/UAT 26-517
AT/UAT 26-617
AT/UAT 26-717
AT/UAT 26-817
AT/UAT 26-917
AT/UAT 28-217
AT/UAT 28-317
AT/UAT 28-417
AT/UAT 28-517
AT/UAT 28-617
AT/UAT 28-717
AT/UAT 28-817
AT/UAT 28-917

10

2775
2810
2995
3020
3285
3130
3165
3195
3375
3400
3645
3455
3700

4625
4665
4845
4870
5135
5325
5360
5390
5570
5595
5840
5650
5895

2578

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

910
930
1020
1035
1165
1035
1050
1065
1155
1170
1295
1195
1320

(2) 50 MPT
MAKE-UP

64
5220

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 4,0
(2) 5,5
(2) 5,5
(2) 7,5
(2) 11,0
(2) 4,0
(2) 5,5
(2) 7,5
(2) 5,5
(2) 7,5
(2) 7,5
(2) 11,0
(2) 11,0

25,1
28,6
28,0
30,7
34,4
29,5
33,7
37,0
33,1
36,3
35,7
41,3
40,6

3350
3350
3654
3654
3959
3461
3461
3461
3766
3766
4070
3766
4070

1318
1318
1318
1318
1318
1429
1429
1429
1429
1429
1429
1429
1429

2289
2289
2594
2594
2918
2400
2400
2400
2705
2705
3010
2705
3010

1826
1826
1826
1826
1826
2283
2283
2283
2283
2283
2283
2283
2283

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (2) independent operating cells. Consult the factory for details.

! Outlet connection extends 10 mm beyond bottom flange.


Height includes fan guard which ships factory mounted.

44

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 212-59 to 212-99

ACCESS DOOR

ACCESS DOOR

543

543

ACCESS
DOOR

ACCESS
DOOR
(2) 150 BFW INLET

1683

Swing Out Radius


of Motor Cover
is 777 mm

51
H
P
1429

(2) 150 BFW OUTLET

(2) 80 FPT
OVERFLOW
(2) 50 MPT
MAKE-UP

587

1286
1597

(2) 80 FPT
DRAIN

378

1689

165

1718
130

92

1825

! 10

3781

2578

Weights (kg)

Dimensions (mm)

Model
No.

Shipping

Operating

Heaviest
Section
(Upper)

AT/UAT 212-59
AT/UAT 212-69
AT/UAT 212-79
AT/UAT 212-89
AT/UAT 212-99

2775
2810
2995
3020
3285

4625
4665
4845
4870
5135

910
930
1020
1035
1165

Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 4,0
(2) 5,5
(2) 5,5
(2) 7,5
(2) 11,0

25,1
28,6
28,0
30,7
34,4

3461
3461
3766
3766
4070

2400
2400
2705
2705
3010

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (2) independent operating cells. Consult the factory for details.

! Outlet connection extends 10 mm beyond bottom flange.


Height includes fan guard which ships factory mounted.

45

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 215-29 to 215-99
ACCESS
DOOR

ACCESS
DOOR

543

543

ACCESS
DOOR

(2) 150 BFW INLET

1140

ACCESS
DOOR

51

Swing Out Radius


of Motor Cover
is 777 mm
H
P

1429

(2) 150 BFW OUTLET

(2) 80 FPT OVERFLOW


(2) 50 MPT MAKE-UP

587

1743
2054

(2) 80 FPT DRAIN

2146
2175

130

2283

378
165
92

4696

! 10

2573

Weights (kg)

Dimensions (mm)

Model
No.

Shipping

Operating

Heaviest
Section
(Upper)

AT/UAT 215-29
AT/UAT 215-39
AT/UAT 215-49
AT/UAT 215-59
AT/UAT 215-69
AT/UAT 215-79
AT/UAT 215-89
AT/UAT 215-99

3130
3165
3195
3375
3400
3645
3455
3700

5325
5360
5390
5570
5595
5840
5650
5895

1035
1050
1065
1155
1170
1295
1195
1320

Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 4,0
(2) 5,5
(2) 7,5
(2) 5,5
(2) 7,5
(2) 7,5
(2) 11,0
(2) 11,0

29,5
33,7
37,0
33,1
36,3
35,7
41,3
40,6

3461
3461
3461
3766
3766
4070
3766
4070

2400
2400
2400
2705
2705
3010
2705
3010

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (2) independent operating cells. Consult the factory for details.

! Outlet connection extends 10 mm beyond bottom flange.


Height includes fan guard which ships factory mounted.

46

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 110-112 to 110-918

Access door swings inside unit


ACCESS DOOR

*AT/UAT 110-112 thru 912


(1) 200mm Inlet
(1) 200mm Outlet

AT/UAT 110-118 thru 918


(1) 250mm Inlet
(1) 250mm Outlet
178

ACCESS
DOOR

51
Q

*BFW INLET

P
50 MPT
MAKE-UP

B
641

80 FPT
OVERFLOW

429

133

80 FPT
DRAIN

229

92

10

2991

Weights (kg)
Model
No.

AT/UAT 110-112
AT/UAT 110-212
AT/UAT 110-312
AT/UAT 110-412
AT/UAT 110-512
AT/UAT 110-612
AT/UAT 110-712
AT/UAT 110-812
AT/UAT 110-912
AT/UAT 110-118
AT/UAT 110-218
AT/UAT 110-318
AT/UAT 110-418
AT/UAT 110-518
AT/UAT 110-618
AT/UAT 110-718
AT/UAT 110-818
AT/UAT 110-918

Dimensions (mm)

Heaviest
Section
Shipping Operating (Upper)

3105
2930
3125
2975
3150
3340
3195
3385
3495
4040
4620
4355
4110
4375
4425
4710
4535
4820

5615
5445
5640
5490
5660
5850
5705
5895
6010
7855
8430
8170
7925
8190
8235
8525
8350
8635

*BFW OUTLET

2155
1980
2175
2030
2200
2390
2245
2435
2550
2615
3190
2925
2680
2950
2995
3280
3105
3395

Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

11,0
18,5
15,0
22,0
18,5
18,5
22,0
22,0
30,0
15,0
11,0
15,0
22,0
18,5
22,0
22,0
30,0
30,0

34,1
40,8
37,3
43,3
40,0
39,4
42,4
41,7
43,8
50,6
44,7
49,8
57,6
53,4
56,5
55,6
61,9
60,9

4401
4096
4401
4096
4401
4705
4401
4705
4705
4096
4705
4401
4096
4401
4401
4705
4401
4705

1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580
1580

2769
2464
2769
2464
2769
3073
2769
3073
3073
2438
3048
2743
2438
2743
2743
3048
2743
3048

3651
3651
3651
3651
3651
3651
3651
3651
3651
5486
5486
5486
5486
5486
5486
5486
5486
5486

1826
1826
1826
1826
1826
1826
1826
1826
1826
2743
2743
2743
2743
2743
2743
2743
2743
2743

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10mm beyond bottom flange.
Height does not includes fan guard.
Fan guard which ships loose for field mounting.

47

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 210-124 to 210-936
Access door swings inside unit

*AT/UAT 210-124 thru 924


(2) 200mm Inlet
(2) 200mm Outlet

ACCESS DOOR

ACCESS DOOR

ACCESS
DOOR

ACCESS
DOOR

*AT/UAT 210-136 thru 936


(2) 250mm Inlet
(2) 250mm Outlet
178

51
Q

*(2) BFW INLET

H
3353
B

(2) 80 FPT
OVERFLOW

641

429

Model
No.

AT/UAT 210-124
AT/UAT 210-224
AT/UAT 210-324
AT/UAT 210-424
AT/UAT 210-524
AT/UAT 210-624
AT/UAT 210-724
AT/UAT 210-824
AT/UAT 210-924
AT/UAT 210-136
AT/UAT 210-236
AT/UAT 210-336
AT/UAT 210-436
AT/UAT 210-536
AT/UAT 210-636
AT/UAT 210-736
AT/UAT 210-836
AT/UAT 210-936

64

92
2991

(2) 50 MPT
MAKE-UP

R
10

Weights (kg)
Heaviest Fan
Section Motor
Shipping Operating (Upper) (kW)

6285
5940
6330
6035
6380
6760
6470
6850
7075
8255
9410
8880
8390
8925
9015
9590
9245
9815

*(2) BFW OUTLET

(2)80 FPT
DRAIN

11315
10970
11360
11060
11405
11785
11495
11875
12100
15880
17030
16505
16015
16550
16640
17215
16870
17440

2155
1980
2175
2030
2200
2390
2245
2435
2550
2615
3190
2925
2680
2950
2995
3280
3105
3395

(2) 11,0
(2) 18,5
(2) 15,0
(2) 22,0
(2) 18,5
(2) 18,5
(2) 22,0
(2) 22,0
(2) 26,0
(2) 15,0
(2) 11,0
(2) 15,0
(2) 22,0
(2) 18,5
(2) 22,0
(2) 22,0
(2) 30,0
(2) 30,0

Dimensions (mm)
Air
Flow
(m3/s)

S&Q

68,2
81,6
74,6
86,5
80,1
78,8
84,8
83,5
87,6
101,2
89,4
99,5
115,1
106,7
113,0
111,2
123,7
121,7

4705
4401
4705
4401
4705
5010
4705
5010
5010
4401
5010
4705
4401
4705
4705
5010
4705
5010

1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884
1884

3073
2769
3073
2769
3073
3378
3073
3378
3378
2743
3353
3048
2743
3048
3048
3353
3048
3353

7366
7366
7366
7366
7366
7366
7366
7366
7366
11036
11036
11036
11036
11036
11036
11036
11036
11036

1826
1826
1826
1826
1826
1826
1826
1826
1826
2743
2743
2743
2743
2743
2743
2743
2743
2743

3423
3423
3423
3423
3423
3423
3423
3423
3423
5258
5258
5258
5258
5258
5258
5258
5258
5258

3518
3518
3518
3518
3518
3518
3518
3518
3518
5353
5353
5353
5353
5353
5353
5353
5353
5353

3651
3651
3651
3651
3651
3651
3651
3651
3651
5486
5486
5486
5486
5486
5486
5486
5486
5486

184
184
184
184
184
184
184
184
184
216
216
216
216
216
216
216
216
216

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
N, "M", O, S&Q dimension are similar for both cells.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.

48

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 310-136 to 310-954
*AT/UAT 310-136 thru 936
(3) 200mm Inlet
(3) 200mm Outlet
ACCESS DOOR

ACCESS DOOR

ACCESS
DOOR

ACCESS
DOOR

ACCESS DOOR

*AT/UAT 310-154 thru 954


(3) 250mm Inlet
(3) 250mm Outlet

178

51
Q

ACCESS
DOOR

*(3) BFW INLET

H
P
B

N
R

Model
No.

AT/UAT 310-136
AT/UAT 310-236
AT/ UAT 310-336
AT/UAT 310-436
AT/UAT 310-536
AT/UAT 310-636
AT/UAT 310-736
AT/UAT 310-836
AT/UAT 310-936
AT/UAT 310-154
AT/UAT 310-254
AT/UAT 310-354
AT/UAT 310-454
AT/UAT 310-554
AT/UAT 310-654
AT/UAT 310-754
AT/UAT 310-854
AT/UAT 310-954

10

(3) 50 MPT
MAKE-UP

64

92

Weights (kg)
Heaviest Fan
Section Motor
Shipping Operating (Upper) (kW)

9540
9020
9605
9160
9675
10245
9810
10385
10725
12370
14100
13310
12575
13375
13515
14370
13855
14710

*(3) BFW OUTLET

(3) 80 FPT
DRAIN

429

2991

(3) 80 FPT
OVERFLOW

641

17080
16560
17145
16695
17215
17785
17350
17920
18260
23810
25535
24750
24015
24815
24950
25810
25290
26150

2155
1980
2175
2030
2200
2390
2245
2435
2550
2615
3190
2925
2680
2950
2995
3280
3105
3395

(3) 11,0
(3) 18,5
(3) 15,0
(3) 22,0
(3) 18,5
(3) 18,5
(3) 22,0
(3) 22,0
(3) 26,0
(3) 15,0
(3) 11,0
(3) 15,0
(3) 22,0
(3) 18,5
(3) 22,0
(3) 22,0
(3) 30,0
(3) 30,0

Dimensions (mm)
Air
Flow
(m3/s)

S&Q

102,4
122,6
112,1
130,0
120,3
118,5
127,5
125,4
131,6
152,0
134,2
149,5
173,0
160,3
169,8
167,1
185,8
182,9

5010
4705
5010
4705
5010
5315
5010
5315
5315
4705
5315
5010
4705
5010
5010
5315
5010
5315

2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189
2189

3378
3073
3378
3073
3378
3683
3378
3683
3683
3048
3658
3353
3048
3353
3353
3658
3353
3658

11081
11081
11081
11081
11081
11081
11081
11081
11081
16586
16586
16586
16586
16586
16586
16586
16586
16586

1826
1826
1826
1826
1826
1826
1826
1826
1826
2743
2743
2743
2743
2743
2743
2743
2743
2743

3423
3423
3423
3423
3423
3423
3423
3423
3423
5258
5258
5258
5258
5258
5258
5258
5258
5258

3518
3518
3518
3518
3518
3518
3518
3518
3518
5353
5353
5353
5353
5353
5353
5353
5353
5353

3651
3651
3651
3651
3651
3651
3651
3651
3651
5486
5486
5486
5486
5486
5486
5486
5486
5486

184
184
184
184
184
184
184
184
184
216
216
216
216
216
216
216
216
216

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
N, "M", O, S&Q dimension are similar for both cells.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.

49

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 112-012 to 112-914
Access Door Swings Inside Unit
ACCESS DOOR

*AT/UAT 112-012 thru 912


(1) 200 Inlet
(1) 200 Outlet

*AT/UAT 112-314 thru 914


(1) 250 Inlet
(1) 250 Outlet

178

ACCESS
DOOR

51

* BFW INLET

50 MPT
MAKE-UP

P
B

641
429
184
92
133
229

80 FPT
OVERFLOW

* BFW OUTLET

80 FPT DRAIN

! 10

Weights (kg)
Model
No.

AT/UAT 112-012
AT/UAT 112-112
AT/UAT 112-212
AT/UAT 112-312
AT/UAT 112-412
AT/UAT 112-512
AT/UAT 112-612
AT/UAT 112-712
AT/UAT 112-812
AT/UAT 112-912
AT/UAT 112-314
AT/UAT 112-414
AT/UAT 112-514
AT/UAT 112-614
AT/UAT 112-714
AT/UAT 112-814
AT/UAT 112-914

Dimensions (mm)

Heaviest
Section
Shipping Operating (Upper)

3375
3395
3420
3640
3465
3865
3665
3710
3935
4045
3750
4020
4255
4050
4285
4170
4405

6190
6215
6235
6460
6280
6680
6480
6525
6750
6865
7075
7345
7580
7375
7610
7495
7730

3607

2270
2290
2315
2535
2360
2760
2560
2605
2825
2940
2550
2815
3055
2850
3085
2965
3200

Fan
Motor
(kW)

Air
Flow
(m3/s)

11,0
15,0
18,5
15,0
22,0
15,0
18,5
22,0
22,0
30,0
22,0
18,5
18,5
22,0
22,0
30,0
30,0

38,4
42,1
45,2
41,4
47,9
40,7
44,4
47,0
46,2
50,6
52,1
48,3
47,5
51,1
50,3
56,0
55,0

4121
4121
4121
4426
4121
4731
4426
4426
4731
4731
4274
4578
4883
4578
4883
4578
4883

1581
1581
1581
1581
1581
1581
1581
1581
1581
1581
1734
1734
1734
1734
1734
1734
1734

2489
2489
2489
2794
2489
3099
2794
2794
3099
3099
2616
2921
3226
2921
3226
2921
3226

3651
3651
3651
3651
3651
3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261
4261

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

50

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 112-018 to 112-920
Access Door Swings Inside Unit
ACCESS DOOR

178

ACCESS
DOOR

250 BFW INLET


Q

51
H
P
50 MPT
MAKE-UP

1886

80 FPT
OVERFLOW

641
429

133

216
92
3607

10

229

80 FPT
DRAIN
S

Weights (kg)
Model
No.

AT/UAT 112-018
AT/UAT 112-118
AT/UAT 112-218
AT/UAT 112-318
AT/UAT 112-418
AT/UAT 112-518
AT/UAT 112-618
AT/UAT 112-718
AT/UAT 112-818
AT/UAT 112-918
AT/UAT 112-520
AT/UAT 112-620
AT/UAT 112-720
AT/UAT 112-820
AT/UAT 112-920

Shipping Operating

4705
4755
5060
5105
5445
5225
5560
5255
5590
5640
5215
5930
5545
5955
6002

8910
8960
9260
9310
9650
9430
9765
9455
9795
9845
9935
10645
10265
10675
10725

250 BFW OUTLET

Dimensions (mm)
Heaviest
Section
(Upper)

Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

3090
3140
3445
3495
3830
3610
3945
3640
3975
4025
3490
4200
3820
4225
4275

18,5
22,0
18,5
22,0
22,0
30,0
30,0
37,0
37,0
45,0
37,0
30,0
37,0
37,0
45,0

61,2
64,9
60,2
63,7
62,7
69,7
68,6
74,8
73,5
77,9
78,1
70,3
76,6
75,3
79,8

4426
4426
4731
4731
5036
4731
5036
4731
5036
5036
4426
5036
4731
5036
5036

2769
2769
3073
3073
3378
3073
3378
3073
3378
3378
2769
3378
3073
3378
3378

5486
5486
5486
5486
5486
5486
5486
5486
5486
5486
6096
6096
6096
6096
6096

2743
2743
2743
2743
2743
2743
2743
2743
2743
2743
3048
3048
3048
3048
3048

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

51

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 212-024 to 212-928

Access Doors
Swing Inside Unit
ACCESS DOOR

ACCESS DOOR

*AT/UAT 212-024 thru 924


(2) 200 Inlets
(2) 200 Outlets

*AT/UAT 212-128 thru 928


(2) 250 Inlets
(2) 250 Outlets

278

ACCESS
DOOR

51

ACCESS
DOOR

*BFW INLET

Q
H
P
B

*BFW OUTLET
(2) 80 FPT
OVERFLOW

641

(2) 50 MPT
MAKE-UP

429

133

92

Model
No.

AT/UAT 212-024
AT/UAT 212-124
AT/UAT 212-224
AT/UAT 212-324
AT/UAT 212-424
AT/UAT 212-524
AT/UAT 212-624
AT/UAT 212-724
AT/UAT 212-824
AT/UAT 212-924
AT/UAT 212-128
AT/UAT 212-228
AT/UAT 212-328
AT/UAT 212-428
AT/UAT 212-528
AT/UAT 212-628
AT/UAT 212-728
AT/UAT 212-828
AT/UAT 212-928

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

6775
7220
6820
7265
6915
7310
7755
7405
7845
8075
7430
7975
7495
8030
8500
8090
8565
8330
8800

10 !

3607

12410
12855
12455
12900
12545
12945
13390
13035
13480
13710
14080
14625
14145
14680
15150
14740
15215
14980
15450

2290
2515
2315
2535
2360
2560
2780
2605
2825
2940
2515
2790
2550
2815
3055
2850
3085
2965
3200

(2) 80 FPT
DRAIN

64
L

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

(2) 15,0
(2) 11,0
(2) 18,5
(2) 15,0
(2) 22,0
(2) 18,5
(2) 18,5
(2) 22,0
(2) 22,0
(2) 30,0
(2) 18,5
(2) 15,0
(2) 22,0
(2) 18,5
(2) 18,5
(2) 22,0
(2) 22,0
(2) 30,0
(2) 30,0

84,3
75,6
90,4
82,7
95,8
88,7
87,3
93,9
92,4
101,1
98,4
90,1
104,2
96,6
95,1
102,3
100,6
112,0
110,0

4426
4731
4426
4731
4426
4731
5036
4731
5036
5036
4731
5036
4731
5036
5340
5036
5340
5036
5340

1886
1886
1886
1886
1886
1886
1886
1886
1886
1886
2191
2191
2191
2191
2191
2191
2191
2191
2191

2794
3099
2794
3099
2794
3099
3404
3099
3404
3404
3073
3378
3073
3378
3683
3378
3683
3378
3683

7366
7366
7366
7366
7366
7366
7366
7366
7366
7366
8585
8585
8585
8585
8585
8585
8585
8585
8585

3423
3423
3423
3423
3423
3423
3423
3423
3423
3423
4032
4032
4032
4032
4032
4032
4032
4032
4032

3651
3651
3651
3651
3651
3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261
4261
4261
4261

184
184
184
184
184
184
184
184
184
184
216
216
216
216
216
216
216
216
216

1826
1826
1826
1826
1826
1826
1826
1826
1826
1826
2130
2130
2130
2130
2130
2130
2130
2130
2130

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
N, "M", O, S&Q dimension are similar for both cells.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

52

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 212-036 to 212-936
Access Doors
Swing Inside Unit
ACCESS DOOR

ACCESS DOOR

178

ACCESS
DOOR

51

ACCESS
DOOR

2743

(2) 250 BFW INLET

H
P
2191

(2) 80 FPT
OVERFLOW

641
429

5258

216

3607

Model
No.

AT/UAT 212-036
AT/UAT 212-136
AT/UAT 212-236
AT/UAT 212-336
AT/UAT 212-436
AT/UAT 212-536
AT/UAT 212-636
AT/UAT 212-736
AT/UAT 212-836
AT/UAT 212-936

10

5486

64
11036

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

10190
9625
10905
10335
11005
10570
11240
10625
11295
11395

(2) 80 FPT
DRAIN

133

92

(2) 250 BFW OUTLET

(2) 50 MPT
MAKE-UP

2743

18595
18035
19315
18740
19415
18980
19650
19035
19705
19805

3420
3140
3780
3495
3830
3610
3945
3640
3975
4025

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 15,0
(2) 22,0
(2) 18,5
(2) 22,0
(2) 22,0
(2) 30,0
(2) 30,0
(2) 37,0
(2) 37,0
(2) 45,0

112,1
129,8
118,5
127,5
125,4
139,5
137,2
149,7
147,0
155,7

5036
4731
5340
5036
5340
5036
5340
5036
5340
5340

3378
3073
3683
3378
3683
3378
3683
3378
3683
3683

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

53

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 312-036 to 312-942

Access Doors
Swing Inside Unit
ACCESS DOOR

ACCESS DOOR

ACCESS DOOR

*AT/UAT 312-036 thru 936


(3) 200 Inlets
(3) 200 Outlets

*AT/UAT 312-042 thru 942


(3) 250 Inlets
(3) 250 Outlets
178

ACCESS
DOOR

51

ACCESS
DOOR

ACCESS
DOOR

*BFW INLET

Q
H
P
B

229

641

*BFW OUTLET

(3) 80 FPT
OVERFLOW

133

429

(3) 80 FPT
DRAIN

O
92

(3) 50 MPT
MAKE-UP

S
N
M

3607

Model
No.

AT/UAT 312-036
AT/UAT 312-136
AT/UAT 312-236
AT/UAT 312-336
AT/UAT 312-436
AT/UAT 312-536
AT/UAT 312-636
AT/UAT 312-736
AT/UAT 312-836
AT/UAT 312-936
AT/UAT 312-042
AT/UAT 312-142
AT/UAT 312-242
AT/UAT 312-342
AT/UAT 312-442
AT/UAT 312-542
AT/UAT 312-642
AT/UAT 312-742
AT/UAT 312-842
AT/UAT 312-942

10

64
L

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

10095
10765
10165
10830
11500
10900
11565
11035
11705
12045
12150
11415
12860
12235
12315
13025
12410
13120
12765
13470

133

18545
19215
18615
19280
19950
19350
20015
19485
20155
20495
22125
21390
22835
22210
22290
22995
22385
23090
22740
23445

2290
2515
2315
2535
2760
2560
2780
2605
2825
2940
2760
2515
3000
2790
2815
3055
2850
3085
2965
3200

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

(3) 15,0
(3) 11,0
(3) 18,5
(3) 15,0
(3) 15,0
(3) 18,5
(3) 18,5
(3) 22,0
(3) 22,0
(3) 30,0
(3) 11,0
(3) 18,5
(3) 11,0
(3) 15,0
(3) 18,5
(3) 18,5
(3) 22,0
(3) 22,0
(3) 30,0
(3) 30,0

127,6
114,5
137,0
125,3
123,4
134,4
132,2
142,3
139,9
153,2
124,5
148,9
122,4
136,3
146,2
143,9
154,8
152,3
169,5
166,5

4731
5036
4731
5036
5340
5036
5340
5036
5340
5340
5340
5036
5645
5340
5340
5645
5340
5645
5340
5645

2191
2191
2191
2191
2191
2191
2191
2191
2191
2191
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496

3099
3404
3099
3404
3708
3404
3708
3404
3708
3708
3683
3378
3988
3683
3683
3988
3683
3988
3683
3988

11081
11081
11081
11081
11081
11081
11081
11081
11081
11081
12910
12910
12910
12910
12910
12910
12910
12910
12910
12910

3423
3423
3423
3423
3423
3423
3423
3423
3423
3423
4032
4032
4032
4032
4032
4032
4032
4032
4032
4032

3651
3651
3651
3651
3651
3651
3651
3651
3651
3651
4261
4261
4261
4261
4261
4261
4261
4261
4261
4261

1826
1826
1826
1826
1826
1826
1826
1826
1826
1826
2130
2130
2130
2130
2130
2130
2130
2130
2130
2130

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
N, "M", O, S&Q dimension are similar for both cells.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

54

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 312-054 to 312-960

Access Doors
Swing Inside Unit
ACCESS DOOR

ACCESS DOOR

ACCESS DOOR

*AT/UAT 312-054 thru 960


(3) 250 Inlets
(3) 250 Outlets

178

ACCESS
DOOR

51

ACCESS
DOOR

ACCESS
DOOR

*(3) BFW INLET

H
P
2191

641

*(3) BFW OUTLET

229
133

429

(3) 80 FPT
DRAIN

216
92

(3) 50 MPT
MAKE-UP

S
N

3607

Model
No.

AT/UAT 312-054
AT/UAT 312-154
AT/UAT 312-254
AT/UAT 312-354
AT/UAT 312-454
AT/UAT 312-554
AT/UAT 312-654
AT/UAT 312-754
AT/UAT 312-854
AT/UAT 312-954
AT/UAT 312-260
AT/UAT 312-360
AT/UAT 312-460
AT/UAT 312-560
AT/UAT 312-660
AT/UAT 312-760
AT/UAT 312-860
AT/UAT 312-960

10

64
L

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

14640
15555
14995
15705
16710
16055
17065
16140
17145
17295
16465
17690
16055
16970
18195
17050
18275
18425

133

(3) 80 FPT
OVERFLOW

27255
28170
27610
28320
29325
28670
29680
28755
29760
29910
30615
31840
30210
31120
32345
31205
32425
32575

3140
3445
3255
3495
3830
3610
3945
3640
3975
4025
3625
4030
3490
3790
4200
3820
4225
4275

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

S&Q

(3) 22,0
(3) 18,5
(3) 30,0
(3) 22,0
(3) 22,0
(3) 30,0
(3) 30,0
(3) 37,0
(3) 37,0
(3) 45,0
(3) 18,5
(3) 18,5
(3) 37,0
(3) 30,0
(3) 30,0
(3) 37,0
(3) 37,0
(3) 45,0

194,8
180,6
213,4
191,3
188,3
209,3
205,9
224,6
220,6
233,7
184,3
181,3
233,2
213,3
209,9
228,6
224,9
238,4

5036
5340
5036
5340
5645
5340
5645
5340
5645
5645
5340
5645
5036
5340
5645
5340
5645
5645

3378
3683
3378
3683
3988
3683
3988
3683
3988
3988
3683
3988
3378
3683
3988
3683
3988
3988

16586
16586
16586
16586
16586
16586
16586
16586
16586
16586
18415
18415
18415
18415
18415
18415
18415
18415

5258
5258
5258
5258
5258
5258
5258
5258
5258
5258
5867
5867
5867
5867
5867
5867
5867
5867

5486
5486
5486
5486
5486
5486
5486
5486
5486
5486
6096
6096
6096
6096
6096
6096
6096
6096

2743
2743
2743
2743
2743
2743
2743
2743
2743
2743
3048
3048
3048
3048
3048
3048
3048
3048

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
N, "M", O, S&Q dimension are similar for both cells.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

55

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 220-112 to 220-918
*AT/UAT 220-112 thru 912
(2) 200mm Inlet
(2) 200mm Outlet

ACCESS DOOR

*AT/UAT 220-118 thru 918


(2) 250mm Inlet
(2) 250mm Outlet

Access Doors
Swing Inside Unit
ACCESS DOOR

178

ACCESS
DOOR

ACCESS
DOOR

*BFW INLET

51

1495
H
P
B

*BFW OUTLET

(2) 80 FPT OVERFLOW


(2) 50 MPT MAKE-UP

641

2378
2762

(2) 80 FPT DRAIN

2858
2883
130

2948

429
216
95

6112

10

Weights (kg)
Model
No.

AT/UAT 220-112
AT/UAT 220-212
AT/UAT 220-312
AT/UAT 220-412
AT/UAT 220-512
AT/UAT 220-612
AT/UAT 220-712
AT/UAT 220-812
AT/UAT 220-912
AT/UAT 220-118
AT/UAT 220-218
AT/UAT 220-318
AT/UAT 220-418
AT/UAT 220-518
AT/UAT 220-618
AT/UAT 220-718
AT/UAT 220-818
AT/UAT 220-918

Dimensions (mm)

Heaviest
Section
Shipping Operating (Upper)

6350
6005
6395
6095
6440
6820
6530
6915
7140
8190
9345
8820
8330
8865
8955
9525
9180
9750

11375
11030
11420
11120
11465
11850
11560
11940
12165
15815
16970
16445
15955
16490
16580
17150
16805
17375

2155
1980
2175
2030
2200
2390
2245
2435
2550
2615
3190
2925
2680
2950
2995
3280
3105
3395

Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 11,0
(2) 18,5
(2) 15,0
(2) 22,0
(2) 18,5
(2) 18,5
(2) 22,0
(2) 22,0
(2) 26,0
(2) 15,0
(2) 11,0
(2) 15,0
(2) 22,0
(2) 18,5
(2) 22,0
(2) 22,0
(2) 30,0
(2) 30,0

67,9
81,3
74,3
86,2
79,8
78,5
84,5
83,2
87,3
100,8
89,0
99,1
114,7
106,3
112,6
110,8
123,2
121,2

4705
4401
4705
4401
4705
5010
4705
5010
5010
4705
5315
5010
4705
5010
5010
5315
5010
5315

1886
1886
1886
1886
1886
1886
1886
1886
1886
2191
2191
2191
2191
2191
2191
2191
2191
2191

3073
2769
3073
2769
3073
3378
3073
3378
3378
3048
3658
3353
3048
3353
3353
3658
3353
3664

3651
3651
3651
3651
3651
3651
3651
3651
3651
5486
5486
5486
5486
5486
5486
5486
5486
5486

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

56

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 420-124 to 420-936

Access Doors
Swing Inside Unit
ACCESS DOOR

ACCESS DOOR

*AT/UAT 420-124 thru 924


(4) 200 mm Inlet
(2) 300 mm Outlet
(2) 80 FPT Overflow
(2) 50 MPT Make-Up
(2) 80 FPT Drain
*AT/UAT 420-136 thru 936
(4) 250 mm Inlet
(4) 250 mm Outlet
(4) 80 FPT Overflow
(4) 50 MPT Make-Up
(4) 80 FPT Drain
178

ACCESS DOOR

ACCESS
DOOR

* BFW INLET

ACCESS DOOR

ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

51

1495
H
P
B

* BFW OUTLET

* OVERFLOW
* MAKE-UP

2378
2762
2858
2883
2391

* DRAIN

130

641
429
241
95

! 10

6112

Weights (kg)
Model
No.

AT/UAT 420-124
AT/UAT 420-224
AT/UAT 420-324
AT/UAT 420-424
AT/UAT 420-524
AT/UAT 420-624
AT/UAT 420-724
AT/UAT 420-824
AT/UAT 420-924
AT/UAT 420-136
AT/UAT 420-236
AT/UAT 420-336
AT/UAT 420-436
AT/UAT 420-536
AT/UAT 420-636
AT/UAT 420-736
AT/UAT 420-836
AT/UAT 420-936

Dimensions (mm)

Heaviest
Shipping Operating Section !

12565
11875
12655
12055
12745
13510
12925
13690
14145
16230
18535
17480
16500
17570
17755
18895
18205
19350

22605
21920
22700
22100
22790
23550
22970
23730
24185
31635
33940
32885
31905
32975
33160
34300
33610
34755

U 2155
U 1980
U 2175
U 2030
U 2200
U 2390
U 2245
U 2435
U 2550
L 2890
U 3190
U 2925
L 2890
U 2950
U 2995
U 3280
U 3105
U 3395

Fan
Motor
(kW)

Air
Flow
(m3/s)

(4) 11,0
(4) 18,5
(4) 15,0
(4) 22,0
(4) 18,5
(4) 18,5
(4) 22,0
(4) 22,0
(4) 26,0
(4) 15,0
(4) 11,0
(4) 15,0
(4) 22,0
(4) 18,5
(4) 22,0
(4) 22,0
(4) 30,0
(4) 30,0

135,2
161,9
148,0
171,6
158,8
156,4
168,3
165,6
173,7
194,6
171,9
191,5
221,5
205,4
217,5
214,0
238,1
234,2

5315
5010
5315
5010
5315
5620
5315
5620
5620
5010
5620
5315
5010
5315
5315
5620
5315
5620

2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496
2496

3683
3378
3683
3378
3683
3988
3683
3988
3988
3353
3962
3658
3353
3658
3658
3962
3658
3962

7360
7360
7360
7360
7360
7360
7360
7360
7360
11036
11036
11036
11036
11036
11036
11036
11036
11036

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
! Outlet connection extends 10mm beyond bottom flange.
! L = Lower Section, U = Upper Section
Height does not include fan guard. Fan Guard ships loose for field mounting.

57

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 224-018 to 224-920

Access Doors
Swing Inside Unit

ACCESS
DOOR

ACCESS
DOOR

178

ACCESS
DOOR

71

(2) 250 BFW INLET

ACCESS
DOOR

51

H
P
2496

(2) 80 FPT
OVERFLOW

(2) 250 BFW OUTLET

641
429

2994

(2) 50 MPT
MAKE-UP

3378

(2) 80 FPT
DRAIN

216
95

3473
3499
3607

130

! 10

7344

Weights (kg)
Model
No.

AT/UAT 224-018
AT/UAT 224-118
AT/UAT 224-218
AT/UAT 224-318
AT/UAT 224-418
AT/UAT 224-518
AT/UAT 224-618
AT/UAT 224-718
AT/UAT 224-818
AT/UAT 224-918
AT/UAT 224-720
AT/UAT 224-820
AT/UAT 224-920

Dimensions (mm)

Heaviest
Section
Shipping Operating (Upper)

9555
9650
10260
9890
10360
11030
10595
10650
11320
11420
11975
12030
12130

17960
18060
18670
18300
18770
19440
19005
19060
19730
19830
21410
21465
21565

3090
3140
3445
3255
3495
3830
3610
3640
3975
4025
4200
4225
4275

Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 18,5
(2) 22,0
(2) 18,5
(2) 30,0
(2) 22,0
(2) 22,0
(2) 30,0
(2) 37,0
(2) 37,0
(2) 45,0
(2) 30,0
(2) 37,0
(2) 45,0

122,0
129,3
119,9
141,7
127,0
125,0
138,9
149,1
149,4
155,1
138,6
148,5
157,4

5036
5036
5340
5036
5340
5645
5340
5340
5645
5645
5645
5645
5645

3378
3378
3683
3378
3683
3988
3683
3683
3988
3988
3988
3988
3988

5486
5486
5486
5486
5486
5486
5486
5486
5486
5486
6096
6096
6096

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) Unit can operate as two (2) independent cells with the addition of a flume plate or water tight partition.
! Outlet connection extends 10mm beyond bottom flange.
Height does not include fan guard.
Fan Guard ships loose for field mounting.

58

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 424-024 to 424-928
*AT/UAT 424-024 thru 924
(4) 200 mm Inlet
(2) 300 mm Outlet
(2) 80 mm Overflow
(2) 80 mm Drain
(2) 50 mm Make-up

Access Doors
Swing Inside Unit

ACCESS
DOOR

ACCESS
DOOR

*AT/UAT 424-028 thru 928


(4) 250 mm Inlet
(4) 250 mm Outlet
(4) 80 mm Overflow
(4) 80 mm Drain
(4) 50 mm Make-up

ACCESS
DOOR

ACCESS
DOOR
178

ACCESS
DOOR

ACCESS
DOOR

*(4) BFW INLET

ACCESS
DOOR

ACCESS
DOOR

51

1803
H
P

2496

*FPT OVERFLOW

*BFW OUTLET

641

2994
3378
3473

*MPT MAKE-UP
*FPT DRAIN

429
216

3499
3607

130

95

7344

10

Weights (kg)

Dimensions (mm)

Model
No.

Shipping

Operating

Heaviest
Section!

Fan
Motor
(kW)

AT/UAT 424-024
AT/UAT 424-124
AT/UAT 424-224
AT/UAT 424-324
AT/UAT 424-424
AT/UAT 424-524
AT/UAT 424-624
AT/UAT 424-724
AT/UAT 424-824
AT/UAT 424-924
AT/UAT 424-028
AT/UAT 424-128
AT/UAT 424-228
AT/UAT 424-328
AT/UAT 424-428
AT/UAT 424-528
AT/UAT 424-628
AT/UAT 424-728
AT/UAT 424-828
AT/UAT 424-928

13625
13715
14605
13805
14695
13990
15585
14785
14970
16310
15185
17220
15295
16385
17325
16495
17435
16620
17565
18035

24900
24995
25880
25085
25975
25265
26860
26065
26245
27585
28550
30580
28660
29745
30690
29855
30800
29980
30925
31400

L 2275
U 2290
U 2515
U 2315
U 2535
U 2360
U 2760
U 2560
U 2605
U 2940
L 2615
U 3000
L 2615
U 2790
U 3025
U 2815
U 3055
U 2850
U 3085
U 3200

(4) 11,0
(4) 15,0
(4) 11,0
(4) 18,5
(4) 15,0
(4) 22,0
(4) 15,0
(4) 18,5
(4) 22,0
(4) 30,0
(4) 15,0
(4) 11,0
(4) 18,5
(4) 15,0
(4) 15,0
(4) 18,5
(4) 18,5
(4) 22,0
(4) 22,0
(4) 30,0

Air
Flow
(m3/s)

152,1
166,8
149,6
179,1
164,0
189,7
161,4
175,8
186,1
200,4
176,0
155,6
188,9
173,0
170,2
185,8
182,8
196,4
193,5
211,6

5036
5036
5340
5036
5340
5036
5645
5340
5340
5645
5036
5645
5036
5340
5645
5340
5645
5340
5645
5645

3461
3461
3771
3461
3771
3461
4081
3771
3771
4081
3378
3988
3378
3683
3988
3683
3988
3683
3988
3988

7360
7360
7360
7360
7360
7360
7360
7360
7360
7360
8579
8579
8579
8579
8579
8579
8579
8579
8579
8579

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (4) independent operating cells. Consult the factory for details.

! Outlet connection extends 10 mm beyond bottom flange.


! L = Lower Section, U = Upper Section
Height does not include Fan Guard. Fan Guard ships loose for field mounting.

59

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 424-036 to 424-936
ACCESS
DOOR

ACCESS
DOOR

178

(4) 250 BFW INLET

ACCESS
DOOR
1803

Access Doors
Swing Inside Unit

ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

51
H
P
2496

(4) 80 FPT OVERFLOW

(4) 250 BFW OUTLET

2994
3378
3433

(4) 50 MPT MAKE-UP


(4) 80 FPT DRAIN

95

3499
3607

130

641
429
216

! 10

7344

Weights (kg)

Dimensions (mm)

Model
No.

Shipping

Operating

Heaviest
Section!

Fan
Motor
(kW)

AT/UAT 424-036
AT/UAT 424-136
AT/UAT 424-236
AT/UAT 424-336
AT/UAT 424-436
AT/UAT 424-536
AT/UAT 424-636
AT/UAT 424-736
AT/UAT 424-836
AT/UAT 424-936

19050
19140
20555
19815
20755
22100
21230
21335
22680
22880

35960
36050
37465
36725
37665
39010
38140
38245
39590
39790

L 3395
L 3395
U 3445
L 3395
U 3495
U 3830
U 3610
U 3640
U 3975
U 4025

(4) 15,0
(4) 18,5
(4) 18,5
(4) 30,0
(4) 22,0
(4) 22,0
(4) 30,0
(4) 37,0
(4) 37,0
(4) 45,0

Air
Flow
(m3/s)

218,7
235,0
231,1
273,0
245,0
241,1
268,0
287,5
282,6
299,5

5036
5036
5340
5036
5340
5645
5340
5340
5645
5645

3378
3378
3683
3378
3683
3988
3683
3683
3988
3988

11030
11030
11030
11030
11030
11030
11030
11030
11030
11030

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
(4) These models are available as (4) independent operating cells. Consult the factory for details.
! Outlet connection extends 10 mm beyond bottom flange.
! L = Lower Section, U = Upper Section
Height does not include fan guard. Fan guard ships loose for field mounting.

60

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 114-0124 to 114-1224
Access Doors
Swing Inside Unit
ACCESS
DOOR

178

ACCESS
DOOR

350 BFW INLET


3620

51
H
P
2524

100 FPT
OVERFLOW

660

10

441

229

229

Model
No.

AT/UAT 114-0124
AT/UAT 114-0224
AT/UAT 114-0324
AT/UAT 114-0424
AT/UAT 114-0524
AT/UAT 114-0624
AT/UAT 114-0724
AT/UAT 114-0824
AT/UAT 114-0924
AT/UAT 114-1024
AT/UAT 114-1124
AT/UAT 114-1224

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

7490
7555
8425
7715
8430
8030
8500
8185
8660
8265
8735
8845

14680
14745
15615
14905
15620
15220
15690
15375
15850
15455
15925
16035

4840
4910
5775
5065
5785
5380
5850
5540
6010
5615
6085
6195

80 MPT
MAKE-UP

350 BFW OUTLET

1835
3620

92

4248

100 FPT
DRAIN

7296

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

22,0
30,0
18,5
37,0
22,0
30,0
30,0
37,0
37,0
45,0
45,0
55,0

85,1
93,3
77,0
100,2
81,8
91,6
90,1
98,4
96,7
104,1
102,5
112,3

5324

3451
3451
4061
3451
4061
3756
4061
3756
4061
3756
4061
4061

5324

5934
5324

5934
5629
5934
5629
5934
5629
5934
5934

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10 mm beyond bottom flange.
Height does not include fan guard.
Fan guard is factory mounted.

61

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 214-0148 to 214-1148
Access Doors
Swing Inside Unit
ACCESS
DOOR

ACCESS
DOOR

178

ACCESS
DOOR

ACCESS
DOOR

(2) 350 BFW INLET

51

3620

3620

H
P
2524

660

10 !

3620

229
92

(2) 100 FPT


OVERFLOW

5401

441

(2) 100 FPT


DRAIN

7007
14535

4251

Model
No.

AT/UAT 214-0148
AT/UAT 214-0248
AT/UAT 214-0348
AT/UAT 214-0448
AT/UAT 214-0548
AT/UAT 214-0648
AT/UAT 214-0748
AT/UAT 214-0848
AT/UAT 214-0948
AT/UAT 214-1048
AT/UAT 214-1148

(2) 350 BFW OUTLET


(2) 80 MPT
MAKE-UP

64
14535

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

14870
15005
15320
16740
16755
15950
16890
17210
16420
17365
17580

29250
29385
29700
31115
31135
30325
31270
31590
30800
31740
31960

4840
4910
5065
5775
5785
5380
5850
6010
5615
6085
6195

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 22,0
(2) 30,0
(2) 37,0
(2) 18,5
(2) 22,0
(2) 30,0
(2) 30,0
(2) 37,0
(2) 45,0
(2) 45,0
(2) 55,0

168,5
184,6
198,4
152,5
162,0
181,4
178,4
191,6
206,1
202,9
222,4

5324

3451
3451
3451
4061
4061
3756
4061
4061
3756
4061
4061

5324
5324

5934
5934
5629
5934
5934
5629
5934
5934

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10 mm beyond bottom flange.
Height does not include fan guard.
Fan guard is factory mounted.

62

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 314-0172 to 314-1272

Access Doors
Swing Inside Unit
ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

178

ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

(3) 350 BFW INLET

3620

51
H
P
2524
660

3620
10 !

441

7007

229
4251

Model
No.

AT/UAT 314-0172
AT/UAT 314-0272
AT/UAT 314-0372
AT/UAT 314-0472
AT/UAT 314-0572
AT/UAT 314-0672
AT/UAT 314-0772
AT/UAT 314-0872
AT/UAT 314-0972
AT/UAT 314-1072
AT/UAT 314-1172
AT/UAT 314-1272

(3) 80 MPT
MAKE-UP
(3) 100 FPT
OVERFLOW

229
1895

5401

7236

92

(3) 350 BFW OUTLET

(3) 100 FPT


DRAIN

64
21834

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

24290
24495
24970
27095
27120
25910
26385
27325
27800
26615
28030
28360

45860
46060
46540
48660
48690
47480
47955
48895
49370
48185
49600
49925

4840
4910
5065
5775
5785
5380
5540
5850
6010
5615
6085
6195

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

(3) 22,0
(3) 30,0
(3) 37,0
(3) 18,5
(3) 22,0
(3) 30,0
(3) 37,0
(3) 30,0
(3) 37,0
(3) 45,0
(3) 45,0
(3) 55,0

250,2
274,2
294,6
226,4
240,6
269,3
289,3
264,9
284,4
306,1
301,2
323,4

5324

3451
3451
3451
4061
4061
3756
3756
4061
4061
3756
4061
4061

5324
5324

5934
5934
5629
5629
5934
5934
5629
5934
5934

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10 mm beyond bottom flange.
Height does not include fan guard.
Fan guard is factory mounted.

63

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 228-0124 to 228-0924

Access Doors
Swing Inside Unit
ACCESS
DOOR

ACCESS
DOOR

178

ACCESS
DOOR

ACCESS
DOOR

(2) 350 BFW INLET

51

3616
H
P
2524
660

(2) 100 FPT


OVERFLOW

(2) 350 BFW OUTLET

(2) 80
MPT MAKE-UP

3505
3994

(2) 100
FPT DRAIN

441

4102

229

4128
130

108

4248

! 10

8626

Model
No.

AT/UAT 228-0124
AT/UAT 228-0224
AT/UAT 228-0324
AT/UAT 228-0424
AT/UAT 228-0524
AT/UAT 228-0624
AT/UAT 228-0724
AT/UAT 228-0824
AT/UAT 228-0924

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

14860
15175
16590
16610
15805
16120
16275
17220
17435

29240
29555
30970
30990
30180
30500
30655
31595
31815

4910
5065
5775
5785
5380
5540
5615
6085
6195

7233

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

(2) 30,0
(2) 37,0
(2) 18,5
(2) 22,0
(2) 30,0
(2) 37,0
(2) 45,0
(2) 45,0
(2) 55,0

183,8
197,4
152,1
161,5
180,5
193,7
205,2
201,9
221,3

5324
5324
5934
5934
5629
5629
5629
5934
5934

3451
3451
4061
4061
3756
3756
3756
4061
4061

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10 mm beyond bottom flange.
Height does not include fan guard.
Fan guard is factory mounted.

64

ENGINEERING

ENGINEERING DATA & DIMENSIONS


MODELS: AT/UAT 428-0148 to 428-1248

Access Doors
Swing Inside Unit
ACCESS
DOOR

ACCESS
DOOR

ACCESS
DOOR

178

ACCESS
DOOR

ACCESS
DOOR
51

ACCESS
DOOR
(4) 350 BFW INLET

3616
H
P
2524
660

(4) 350 BFW OUTLET

(4) 100 FPT


OVERFLOW
(4) 80 MPT
MAKE-UP

3505
3994

(4) 100 FPT


DRAIN

4102
4128

(4) 300 BFW EQUALIZER


IN-LINE WITH OUTLETS

441
229
108
7233

4248

130

8626

Model
No.

AT/UAT 428-0148
AT/UAT 428-0248
AT/UAT 428-0348
AT/UAT 428-0448
AT/UAT 428-0548
AT/UAT 428-0648
AT/UAT 428-0748
AT/UAT 428-0848
AT/UAT 428-0948
AT/UAT 428-1048
AT/UAT 428-1148
AT/UAT 428-1248

Weights (kg)
Heaviest
Section
Shipping Operating (Upper)

29740
30010
30645
33475
33510
31895
32530
33785
34420
32840
34725
35160

58495
58765
59400
62235
62270
60655
61290
62540
63175
61600
63485
63920

4840
4910
5065
5775
5785
5380
5540
5850
6010
5615
6085
6195

1092

10

15558

Dimensions (mm)
Fan
Motor
(kW)

Air
Flow
(m3/s)

(4) 22,0
(4) 30,0
(4) 37,0
(4) 18,5
(4) 22,0
(4) 30,0
(4) 37,0
(4) 30,0
(4) 37,0
(4) 45,0
(4) 45,0
(4) 55,0

323,5
354,9
380,9
293,1
311,5
348,9
348,7
342,9
368,2
396,6
389,9
427,1

5324
5324
5324
5934
5934
5629
5629
5934
5934
5629
5934
5934

3451
3451
3451
4061
4061
3756
3756
4061
4061
3756
4061
4061

NOTE: (1) An adequately sized bleed line must be installed in the cooling tower system to prevent build-up of impurities in the recirculated water.
(2) Do not use catalog drawings for certified prints. Dimensions and weights are subject to change.
(3) Adequate spacing must be allowed for access to the cooling tower.
! Outlet connection extends 10 mm beyond bottom flange.
Height does not include fan guard.
Fan guard is factory mounted.

65

ENGINEERING
Notes:

66

ENGINEERING

D RAIN D OWN V OLUME FOR


R EMOTE S UMP A PPLICATIONS
The following chart provides the maximum drain down volume allowable per AT/UAT model number. Use this chart
when sizing indoor or outdoor remote sumps tanks. Remote sump applications are commonly used whenever a cooling tower is idle during sub-freezing weather to protect the water in the basin from freezing or for large multi-tower
industrial applications. Either application allows the circulating water to gravity drain into a remote sump tank
indoors or a large outdoor concrete basin located underneath the cooling tower.
The water volume provided is the cooling tower portion of the remote sump tank only. The tank should allow for
drain down water from external piping and pump suction coverage.

AT/UAT Model No.


AT/UAT 14-64
14-66
14-69
14-612
18-49
18-511
18-312
18-214
28-518
28-521
28-524
28-428
38-236
38-442
216-49
216-511
216-312
216-214
19-56
19-28
26-517
28-217
212-59
215-29
110-112
110-118
210-124
210-136
310-136
310-154
112-012
112-314
112-018
112-520
212-024
212-128
212-036
312-036
312-042
312-054
312-260

to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to

94
96
99
912
99
911
912
914
918
921
924
928
936
942
99
911
912
914
96
98
917
917
99
99
912
918
924
936
936
954
912
914
918
920
924
928
936
936
942
954
960

Maximum Liters
of drain down
341
530
833
1041
1442
1692
1945
2279
2945
3444
3891
4557
5836
6836
2884
3217
3690
4353
1056
1245
2112
24191
2112
2491
3149
4769
6298
9538
9447
14307
3149
3687
4769
5303
6298
7373
9538
9447
11060
14307
15908

AT/UAT Model No.


220-112
220-118
420-124
420-136
224-018
224-720
424-024
424-028
424-036
114-0124
214-0148
314-0172
228-0124
428-0148

to
to
to
to
to
to
to
to
to
to
to
to
to
to

912
918
924
936
918
920
924
928
936
1224
1148
1272
924
1248

Maximum Liters
of drain down
6298
9538
12839
19076
9538
10606
12839
14939
19311
8274
16548
24822
16548
33096

67

ENGINEERING

S TRUCTURAL S TEEL S UPPORT


Models AT/UAT 14-64 to 314-1272
Suggested Two I Beam Arrangement
L
W

End Elevation

Plan View

Models AT/UAT 14-64 through 110-912

Models AT/UAT 110-918 through 314-1272

Two I Beams Required (by Others)

Two I Beams Required (by Others)

Model No.

Dimensions (mm)
W

4-64 to 94
14-66 to 96
14-69 to 99
14-612 to 912
26-517 to 917
28-217 to 917
19-56 to 96
19-28 to 98
18-49 to 99
18-511 to 911
18-312 to 912
18-214 to 914
28-518 to 918
28-521 to 921
28-524 to 924
28-428 to 928
38-236 to 936
38-442 to 942
110-112 to 912

1321
1321
1321
1321
1826
2283
1826
2283
2388
2388
2388
2388
2388
2388
2388
2388
2388
2388
2991

Dimensions (mm)
W

Model No.

1213
1822
2737
3651
5220
5220
2578
2578
2731
3188
3654
4261
5486
6401
7366
8585
11081
12910
3651

110-118 to 918
210-124 to 924
210-136 to 936
310-136 to 936
310-154 to 954
112-012 to 912
112-314 to 914
112-018 to 918
112-520 to 920
212-024 to 924
212-128 to 928
212-036 to 936
312-036 to 936
312-042 to 942
312-054 to 954
312-260 to 960
114-0124 to 1224
214-0148 to 1148
314-0172 to 1272

2991
2991
2991
2991
2991
3607
3607
3607
3607
3607
3607
3607
3607
3607
3607
3607
4248
4248
4248

5486
7366
11036
11081
16586
3651
4261
5486
6096
7366
8585
11036
11081
12910
16586
18415
7239
14535
21834

Notes:
Models AT/UAT 14-64 through 314-1272
1. These are suggested arrangements for preliminary layout purposes. Consult your EVAPCO representative or www.evapco.eu for
factory certified steel support drawings.
2. The recommended support for the AT/UAT Cooling Tower is structural I beams located under the outer flanges and running the entire
length of the unit. The unit should be elevated to allow access underneath the unit and to the roof below. Mounting holes, 19 mm in
diameter, are located in the bottom flanges of the pan to provide for bolting to the structural steel.
3. Beams should be sized in accordance with accepted structural practices. Maximum deflection of beam under unit to be 1/360 of the unit
length, not to exceed 13 mm.
4. For these models where two support beams are required, deflection may be calculated by using 55% of the operating weight as a uniform
load on each beam.
5. Beams should be level before setting the unit in place. Do not level the unit by shimming between it and the I beams.
6. Support beams and Anchor bolts are to be furnished by others.
7. Dimensions, weights and data are subject to change without notice. Refer to the factory certified drawings for exact dimensions.
8. For alternate layout arrangements please consult the factory. NOTE: OPTIONAL BOTTOM CONNECTIONS WILL REQUIRE THE UNIT TO BE
ELEVATED TO ALLOW FOR PIPING.

68

ENGINEERING

S TRUCTURAL S TEEL S UPPORT


Models AT/UAT 212-059 to 428-1248
Suggested Three I Beam Arrangement

130
Gap
Dimension

3632 End Elevation


End Elevators
Plan View

Models AT/UAT 212-059 through 428-1248


Three I Beams Required (by Others)

Model No.

Dimensions (mm)
W

212-59 to 99
215-29 to 99
216-49 to 99
216-511 to 911
216-312 to 912
216-214 to 914
220-112 to 912
220-118 to 918
420-124 to 924
420-136 to 936
224-018 to 918
224-720 to 920
424-024 to 924
424-028 to 928
424-036 to 936
228-0124 to 0924
428-0148 to 1248

378
4696
5286
5286
5286
5286
6112
6112
6112
6112
7344
7344
7344
7344
7344
8626
8626

2578
2578
2731
3188
3651
4261
3651
5486
7360
11036
5486
6096
7360
8579
11030
7239
15570

Notes:
Models AT/UAT 220-112 through 424-936
1. These are suggested arrangements for preliminary layout purposes. Consult your EVAPCO representative or www.evapco.eu for
factory certified steel support drawings.
2. The recommended support for the AT/UAT Cooling Tower is structural I beams located under the outer flanges and running the entire
length of the unit. The unit should be elevated to allow access underneath the unit and to the roof below. Mounting holes, 19mm in
diameter are located in the bottom flanges of the pan to provide for bolting to the structural steel.
3. Beams should be sized in accordance with accepted structural practices. Maximum deflection of beam under unit to be 1/360 of the unit
length, not to exceed 13mm.
4. For these models only where three support beams are required, deflection may be calculated using 56% of the operating weight on the
CENTER BEAM and 27% on each OUTBOARD beam.
5. Beams should be level before setting the unit in place. Do not level the unit by shimming between it and the I beams.
6. Support beams and Anchor bolts are to be furnished by others.
7. Dimensions, weights and data are subject to change without notice. Refer to the factory certified drawings for exact dimensions.
8. For alternate layout arrangements please consult the factory. NOTE: OPTIONAL BOTTOM CONNECTIONS WILL REQUIRE THE UNIT TO BE
ELEVATED TO ALLOW FOR PIPING.

69

ENGINEERING

M ECHANICAL S PECIFICATIONS
FACTORY ASSEMBLED INDUCED DRAFT AT/UAT COOLING TOWER
Furnish and install factory assembled cooling tower of induced
draft counterflow design with a horizontal multiple side air entry
and a vertical air discharge. The unit shall be completely factory
assembled and conform to the specifications and schedules.
The total fan power should not exceed ____ kW and the total
overall unit dimensions should not exceed the following:
Length:_____ mm; Width: _____ mm; Height:_____ mm
The unit will be delivered in two parts: the bottom basin louver
section and the heat transfer fan section.
The unit (top and bottom section) shall be joined together with
elastic sealer and bolted together with corrosion resistant fasteners. Approved manufacturer: EVAPCO Model __________.
Thermal Performance Performance Warranty
l be capable of performing the thermal duties as shown in the
schedule and on the drawings, and its design thermal rating shall
be certified by the Cooling Technology Institute (CTI).
Only models with performance certified by CTI will be approved.
Manufacturers performance guarantee without CTI certification
for the proposed model or an independent field performance
test shall not be accepted.
Applicable Standards
CTI STD 201 Standard Fan Thermal Performance certification of
Cooling Towers - CTI CODE ATC 105 Acceptance Test Code
Quality Assurance
a) The manufacturer shall have a quality assurance system in
place which is certified by an accredited registrar and complying with the requirements of ISO 9001:2000. This is to guarantee a consistant level of product and service quality.
b) Manufacturers without ISO 9001:2000 certification are not
acceptable.
AT COOLING TOWER: Material of Construction and Corrosion
Resistance
a) The structure and all steel elements of the pan and casing
shall be constructed of Z 725 hot dip galvanized steel for long
life and durability. Alternatives with lower zinc layer thickness
and external paint or coating are not accepted as equal.
b) The strainer shall be made of stainless steel type 304.
c) During fabrication all panel edges shall be coated with a 95 %
pure zinc compound.
d) Casing materials shall be of non flammable construction.
AT COOLING TOWER: OPTIONAL Material of Construction Basin
in SST 304
a) The structure and all steel elements of the Basin and Louver
section up to the water level shall be made of SST 304.
b) Alternatives with hot dip galvanized steel and epoxy coatings
in lieu of the SST 304 are not considered to be equal and are
not accepted.
c) All other steel components of the casing shall be constructed
of Z 725 hot dip galvanized steel for long life and durability.
Alternatives with lower zinc layer thickness and external paint
or coating or made of FRP are not accepted as equal.
d) The strainer shall be made of stainless steel type 304.
e) During fabrication all galvanized steel panel edges shall be
coated with a 95 % pure zinc compound.
f) Casing materials shall be of non flammable construction.
Ultra-AT (UAT) COOLING TOWER: Material of Construction and
Corrosion Resistance
a) The structure and all steel elements of the entire Basin and
Louver section shall be made of SST 316.
b) The structure and all steel elements of the heat transfer fan
section (except the moving parts) shall be made of SST 304.
c) Alternatives with hot dip galvanized steel and epoxy coatings
in lieu of the SST or made of FRP are not considered to be
equal and are not accepted.
d) The strainer shall be made of stainless steel type 304.
e) Casing materials shall be of non flammable construction.
f) The assembly material shall be SST bolt and nuts.
Cooling Tower Basin
a) Standard basin accessories include: overflow, drain, anti vor-

70

tex hood and brass make up with plastic float ball.


b) The entire pan area shall incorporate a stepped configuration
for reduced water volume and easier maintenance.
c) Upper and lower basin bottoms shall be sloped to provide
drainage of the complete basin section.
d) Depressed side outlet sumps which are not an integral part of
the basin shall not be accepted.
Air Inlet Louvers
a) The air inlet louver screens shall be constructed of PVC
(polyvinyl chloride), mounted in easily removable frames.
b) The louvers shall be at four sides to provide easy access to the
basin interior.
c) The louvers shall have a minimum of two changes in air direction to prevent splash out and block direct sunlight from
entering the basin.
d) The louvers will have a 19 mm opening to prevent debris to
enter the basin.
Casing Section
Heat transfer
a) The cooling tower fill shall be PVC (Polyvinyl Chloride) of cross
fluted design for optimum heat transfer and efficiency.
b) The cross fluted sheets shall be bonded together for maximum strength and durability. Fill packs which are not bonded
are not allowed. The fill sheets will be bonded together in
such a way that the structural integrity of the fill makes the
fill useable as a working platform.
c) The PVC fill shall be self extinguishing for fire resistance with
a flame spread rating of 5 per ASTM E 84 81a.
d) The fill shall be resistant to rot, decay or biological attack.
e) The fill shall be able to withstand a water temperature of 55
C.
f) The cooling tower manufacturer shall be responsible for the
manufacturing and performance testing of the fill. This is to
assure single source responsibility.
g) The casing shall totally encase the complete fill section to protect the complete fill from direct atmosphere contact.
h) The construction of the unit shall allow easy removal of the
fill bundles for maintenance purposes.
Water Distribution
a) The spray header and branches shall be constructed of
Schedule 40, Polyvinyl Chloride (PVC) pipe for corrosion resistance and shall have a steel connection to attach the external
piping.
b) The internal tower water distribution piping shall be easily
removable for cleaning purposes.
c) The branches have end caps to assist with debris removal.
d) The water shall be distributed over the fill by precision molded ABS spray nozzles with large minimum 25mm orifice openings to eliminate clogging.
e) The nozzles shall be threaded into the water distribution piping to assure positive positioning. The nozzles are located on
the side of the header to allow the larger debris to flows easily through the water distribution system.
f) Each cell shall have only one hot water return inlet, otherwise
the cooling tower manufacturer shall provide the necessary
extra provisions (piping, balancing valves,..) to achieve the
same at no extra cost.
Drift Eliminators
a) The drift eliminators shall be constructed entirely inert PVC
(Polyvinyl Chloride) that has been specially treated to resist
ultra violet light.
b) Assembled in easily handled sections, the eliminator blades
shall be spaced on 25mm centers and shall incorporate three
changes in air direction to assure efficient removal of
entrained moisture from the discharge air stream.
c) The maximum drift rate shall not exceed 0,001 % of the circulating water rate.
Access Door
Provide a large access door with quick release latch to provide
access to the fan section for maintenance.

ENGINEERING

M ECHANICAL S PECIFICATIONS
Mechanical Equipment
Axial Propeller Fan(s) (Standard execution)
a) Fan shall be heavy duty wide chord axial propeller type, statically balanced and constructed of extruded aluminum alloy
blades.
b) Fans shall be installed in a closely fitted cowl with venturi air
inlet for maximum fan efficiency.
c) The fans shall utilize a soft connect blade to hub design to
avoid transmission of vertical forces to the unit structure.
d) Each fan blade shall be individually adjustable.
e) The fan cowl shall be covered with a heavy gauge hot dip galvanized wire fan guard.
f) The fan drive system (fan drive motor) shall be factory
mounted, adjusted and undergo a trial run in the factory
before shipment.
Axial Propeller Fan(s) - Low Sound Fan (Optional)
a) Fan shall be extremely wide chord blade axial design, statically balanced and constructed of extruded aluminum alloy
blades.
b) Fans shall be installed in a closely fitted cowl with venturi air
inlet for maximum fan efficiency.
c) The fans shall utilize a soft connect blade to hub design to
avoid transmission of vertical forces to the unit structure.
d) Each fan blade shall be individually adjustable.
e) The fan cowl shall be covered with a heavy gauge hot dip galvanized wire fan guard.
f) The fan drive system (fan drive motor) shall be factory
mounted, adjusted and undergo a trial run in the factory
before shipment.
Axial Propeller Fan(s) - Super Low Sound Fan (Optional)
a) Fan shall be extremely wide chord blade axial design, one
piece heavy duty propeller type, statically balanced and made
of FRP.
b) Fans will be installed in a closely fitted cowl with venturi air
inlet for maximum fan efficiency.
c) The fan cowl shall be covered with a heavy gauge hot dip galvanized wire fan guard.
d) The fan drive system (fan drive motor) shall be factory
mounted, adjusted and undergo a trial run in the factory
before shipment.
Bearings and Drive
a) The fan shaft(s) shall be supported by heavy duty, self aligning ball type bearings with cast iron housings and lubrication
fittings for maintenance.
b) The grease fittings shall be extended to the outside of the unit.
c) The bearings shall be rated for an L-10 life of 75000 to 135000
hours.
d) The fan sheave shall be aluminum alloy.
e) The belt shall be a multigroove belt system, constructed of
neoprene with polyester cords and designed for 150 % of the
motor nameplate horsepower.
Motor (Models AT 14-64 to AT 14-912 and Models AT 19-56 to AT 38942)
a) The fan motor shall be Totally Enclosed Fan Cooled (TEFC),
squirrel cage, ball bearing type motor.
b) The motor shall be specially designed for cooling tower use
with moisture protection on the windings, shaft and bearings.
c) The motor shall be minimum IP 55 degree of protection, Class
F insulation, Service Factor 1 and selected for the appropriate
cooling tower duty and the correct ambient temperature but
minimum 40C.
d) Motor bearings shall be greased for life or external grease
nipples shall be provided.
e) The motor shall be mounted on an adjustable heavy duty
steel motor base.
f) A protective cover shall shield the motor and sheave from the
weather.
g) The motor power supply shall be _____ volts, _____ hertz and
_____ phase.

b) The motor shall be specially designed for cooling tower use


with moisture protection on the winding, shaft and bearings.
c) The motor shall be minimum IP 55 degree of protection, Class
F insulation, Service Factor 1 and selected for the appropriate
cooling tower duty and the correct ambient temperature but
minimum 40C.
d) Motors bearings shall be greased for life or external grease
nipples shall be provided.
e) The motor shall be mounted on an adjustable heavy duty
steel motor base.
f) The motor base shall be able to swing to the outside of the
unit for repair or removal.
g) The motor power supply shall be volts, .. hertz and ..
phase.
Sound Levels
The maximum sound pressure levels (dB) measured 15 m from
the cooling tower operating at full fan speed shall not exceed
the sound levels detailed below:
Location
Discharge
Air inlet

63

125 250 500 1000 2000 4000 8000 dB(A)

ACCESSORIES
Electric Heaters
a) The cooling tower cold water basin shall be provided with an
electric heater package to prevent freezing of the water in
the cold water basin.
b) The electric heater package includes: electric heater elements
and a combination of thermostat and low water level cutoff.
c) The heaters shall be selected to maintain 4C basin water temperature at ____C ambient
d) The heater(s) shall be ___V /____ phase / ____ Hz electric
power supply.
Three Probe Electric Water Level Control Package
a) The cooling tower manufacturer shall provide an electric
water level control package instead of the mechanical float
valve arrangement.
b) The package consist of the following elements :
Multiple heavy duty stainless steel 316 static sensors
mounted in a stilling chamber outside the unit. Electrodes
or sensors mounted inside the unit are not accepted
because the functionality will be disturbed by the moving
water in the basin.
An ABS, IP 56 case contains all the contactors for the different level probes and will provide an output signal of a
relay for automatic filling and one relay for alarm level.
The power supply to the control package is 24 Vac / 230
Vac - _____ Hz.
A weather protected solenoid valve (PN16) for the water
make up ready for piping to a water supply with pressure
between 140 kPa and 340 kPa.
Vibration switch
a) A vibration limit switch shall be installed on the mechanical
equipment support and wired into the control panel. The purpose of this switch will be interrupt power to the motor in the
event of excessive vibration.
b) The switch shall be adjustable for sensitivity, and shall require
manual reset.
Water Silencer
a) The water silencers are located in the falling water area of the
cold water basin.
b) The water silencers will reduce the overall sound levels 4 dB
(A) to 7 dB (A) measured at 1.5m from the side or end of the
unit; when the fans are running and 9 dB (A) to 12 dB (A)
when fans are off.
c) The water silencers are constructed of lightweight PVC sections and can be easily removed for access to the basin area.
d) The water silencers will have no impact on the units thermal
performance.

Motor (Models AT 110-112 to AT 428-1248)


a) The fan motor shall be Totally Enclosed Air Over (TEAO),
squirrel cage, ball bearing type motor.

71

Evapco Products are Manufactured Worldwide

World Headquarters /
Research and
Development Center
EVAPCO Manufacturing
Facilities

EVAPCO, Inc. World Headquarters & Research/Development Center


EVAPCO, Inc. P.O. Box 1300 Westminster, MD 21158 USA
Phone: +1 410-756-2600 Fax: +1 410-756-6450 E-mail: marketing@evapco.com
EVAPCO North America

EVAPCO, Inc.
World Headquarters
P.O. Box 1300
Westminster, MD 21158 USA
Phone: 410-756-2600
Fax: 410-756-6450
E-mail: marketing@evapco.com
EVAPCO East
5151 Allendale Lane
Taneytown, MD 21787 USA
Phone: 410-756-2600
Fax: 410-756-6450
E-mail: marketing@evapco.com
EVAPCO Midwest
1723 York Road
Greenup, IL 62428 USA
Phone: 217-923-3431
Fax: 217-923-3300
E-mail: evapcomw@evapcomw.com
EVAPCO West
1900 West Almond Avenue
Madera, CA 93637 USA
Phone: 559-673-2207
Fax: 559-673-2378
E-mail: contact@evapcowest.com
EVAPCO Iowa
925 Quality Drive
Lake View, IA 51450 USA
Phone: 712-657-3223
Fax: 712-657-3226
EVAPCO Iowa
Sales & Engineering
1234 Brady Boulevard
Owatonna, MN 55060 USA
Phone: 507-446-8005
Fax: 507-446-8239
E-mail: evapcomn@evapcomn.com

EVAPCO Europa
Refrigeration Valves &
Systems Corporation
A wholly owned subsidiary of EVAPCO, Inc.

1520 Crosswind Dr.


Bryan, TX 77808 USA
Phone: 979-778-0095
Fax: 979-778-0030
E-mail: rvs@rvscorp.com
McCormack Coil Company, Inc.
A wholly owned subsidiary of EVAPCO, Inc.

P.O. Box 1727


6333 S.W. Lakeview Boulevard
Lake Oswego, OR 97035 USA
Phone: 503-639-2137
Fax: 503-639-1800
E-mail: mail@mmccoil.com
EvapTech, Inc.
A wholly owned subsidiary of EVAPCO, Inc.

8331 Nieman Road


Lenexa, KS 66214 USA
Phone: 913-322-5165
Fax: 913-322-5166
E-mail: marketing@evaptechinc.com
Tower Components, Inc.
A wholly owned subsidiary of EVAPCO, Inc.

5960 US HWY 64E


Ramseur, NC 27316
Phone: 336-824-2102
Fax: 336-824-2190
E-mail: mail@towercomponentsinc.com
EVAPCO Newton
701 East Jourdan Street
Newton, IL 62448 USA
Phone: 618-783-3433
Fax: 618-783-3499
E-mail: evapcomw@evapcomw.com

EVAPCO Asia / Pacific

EVAPCO Europe, N.V.


European Headquarters
Industrieterrein Oost 4010
3700 Tongeren, Belgium
Phone: (32) 12-395029
Fax: (32) 12-238527
E-mail: evapco.europe@evapco.be

EVAPCO Asia/Pacific Headquarters


1159 Luoning Rd. Baoshan Industrial Zone
Shanghai, P. R. China, Postal Code: 200949
Phone: (86) 21-6687-7786
Fax: (86) 21-6687-7008
E-mail: marketing@evapcochina.com

EVAPCO Europe, S.r.l.


Via Ciro Menotti 10
I-20017 Passirana di Rho, Milan, Italy
Phone: (39) 02-939-9041
Fax: (39) 02-935-00840
E-mail: evapcoeurope@evapco.it

Evapco (Shanghai) Refrigeration


Equipment Co., Ltd.
1159 Louning Rd., Baoshan Industrial Zone
Shanghai, P.R. China, Postal Code: 200949
Phone: (86) 21-6687-7786
Fax: (86) 21-6687-7008
E-mail: marketing@evapcochina.com

EVAPCO Europe, S.r.l.


Via Dosso 2
23020 Piateda Sondrio, Italy
Flex Coil a/s
A subsidiary of Evapco, Inc.

Knsgrdvej 115
9440 Aabybro, Denmark
Phone: (45) 9824-4999
Fax: (45) 9824-4990
E-mail: flexcoil@flexcoil.dk
EVAPCO Europe, GmbH
Bovert 22
D-40670 Meerbusch, Germany
Phone: (49) 2159-69560
Fax: (49) 2159-695611
E-mail: info@evapco.de
EVAPCO S.A. (Pty.) Ltd.
A licensed manufacturer of Evapco, Inc.

18 Quality Road
Isando 1600, Republic of South Africa
Phone: (27) 11 392-6630
Fax: (27) 11-392-6615
E-mail: evapco@evapco.co.za
Tiba Engineering Industries Co.
A licensed manufacturer of Evapco, Inc.

5 Al Nasr Road St.


Nasr City, Cairo, Egypt
Phone: (20) 2-290-7483/ (20) 2-291-3610
Fax: (20) 2-404-4667/ (20) 2-290-0892
E-mail: manzgroup@tedata.net.eg

Beijing EVAPCO Refrigeration


Equipment Co., Ltd.
Yan Qi Industrial Development District
Huai Rou County
Beijing, P.R. China, Postal Code: 101407
Phone: (86) 10 6166-7238
Fax: (86) 10 6166-7395
E-mail: evapcobj@evapcochina.com
EVAPCO Australia Pty Ltd..
A licensed manufacturer of Evapco, Inc.

34-42 Melbourne St.


P.O. Box 436
Riverstone, N.S.W. Australia 2765
Phone: (61) 29 627-3322
Fax: (61) 29 627-1715
E-mail: sales@evapco.com.au
EvapTech Asia Pacific Sdn. Bhd
A wholly owned subsidiary of EvapTech, Inc.

IOI Business Park, 2/F Unit 21


Persiaran Puchong Jaya Selatan
Bandar Puchong Jaya,
47170 Puchong, Selangor, Malaysia
Phone: +(60-3) 8070 7255
Fax: +(60-3) 8070 5731
E-mail: evaptechinc.com

EVAPCO... Specialists in Heat Transfer Products and Services.


Visit EVAPCOs Website at: http://www.evapco.eu

Bulletin 331-E Metric 1109

You might also like