Contents
1. Description...........................................................3 2. Standard configurations.......................................3 3. Protection functions...........................................10 4. Application.........................................................15 5. Supported ABB solutions...................................20 6. Control................................................................22 7. Measurement.....................................................22 8. Disturbance recorder..........................................23 9. Event log.............................................................23 10. Recorded data...................................................23 11. Condition monitoring.........................................23 12. Trip-circuit supervision......................................24 13. Self-supervision.................................................24 14. Fuse failure supervision.....................................24 15. Current circuit supervision................................24 16. Access control...................................................24 17. Inputs and outputs............................................24 18. Communication.................................................26 19. Technical data...................................................28 20. Local HMI..........................................................68 21. Mounting methods............................................69 22. IED case and IED plug-in unit...........................70 23. Selection and ordering data..............................70 24. Accessories and ordering data.........................74 25. Tools..................................................................75 26. Terminal diagrams.............................................78 27. Certificates........................................................84 28. Inspection reports.............................................84 29. References........................................................84 30. Functions, codes and symbols.........................85 31. Document revision history.................................89
Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. Copyright 2010 ABB Oy. All rights reserved. Trademarks ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
ABB
1MRS756379 K Issued: 2010-09-07 Revision: K compensated and solidly earthed networks. Once the standard configuration IED has been given the application-specific settings, it can directly be put into service. The 615 series IEDs support a range of communication protocols including IEC 61850 with GOOSE messaging, IEC 60870-5-103, Modbus and DNP3.
1. Description
REF615 is a dedicated feeder IED (intelligent electronic device) designed for the protection, control, measurement and supervision of utility substations and industrial power systems including radial, looped and meshed distribution networks with or without distributed power generation. REF615 is a member of ABBs Relion product family and part of its 615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable-unit design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices. The IED provides main protection for overhead lines and cable feeders in distribution networks. The IED is also used as back-up protection in applications, where an independent and redundant protection system is required. Depending on the chosen standard configuration, the IED is adapted for the protection of overhead line and cable feeders in isolated neutral, resistance earthed,
2. Standard configurations
REF615 is available in eight alternative standard configurations. The standard signal configuration can be altered by means of the graphical signal matrix or the optional graphical application functionality of the Protection and Control IED Manager PCM600. Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions using various logical elements, including timers and flipflops. By combining protection functions with logic function blocks, the IED configuration can be adapted to user-specific application requirements.
ABB
Table 1. Standard configurations Description Non-directional overcurrent and directional earth-fault protection Non-directional overcurrent and non-directional earth-fault protection Non-directional overcurrent and directional earth-fault protection with phase-voltage based measurements Directional overcurrent and directional earth-fault protection with phase-voltage based measurements, undervoltage and overvoltage protection Directional overcurrent and directional earth-fault protection, phasevoltage based protection and measurement functions, sensor inputs Non-directional overcurrent and non-directional earth-fault protection, phase-voltage and frequency based protection and measurement functions, synchro-check Std. conf. A and B C and D E
F G
ABB
Table 2. Supported functions Functionality Protection1)2) Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 1 Three-phase directional overcurrent protection, low stage, instance 2 Three-phase directional overcurrent protection, high stage Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, instantaneous stage Directional earth-fault protection, low stage, instance 1 A B C D E F G H
4)
4)
4)
4)
4)
4)
4)
4)
4)
4)
4)
4)
3)4)6) 3)4)6)
ABB
Table 2. Supported functions, continued Functionality Directional earth-fault protection, low stage, instance 2 Directional earth-fault protection, high stage Admittance based earthfault protection, instance 1 Admittance based earthfault protection, instance 2 Admittance based earthfault protection, instance 3 Transient / intermittent earth-fault protection Non-directional (crosscountry) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 A B C D E F G H -
3)4)6) 3)4)6)
3)4)6) 3)4)6) 3)4)6) 3)4)6) 3)4)6) 3)4)6) 3)4)6) 3)4)6) 6)8) 6)8)
3)4)5) 3)4)5) 3)4)7) 3)4)5) 3)4)5) 3)4)7) 3)4)5) 3)4)5) 3)4)7) 3)4)5) 3)4)5) 3)4)7) 6)8) 6)8)
9)
9)
9)
9)
9)
6) 6) 6) -
6) 6) 6) -
5) 5) 5) -
5) 5) 5)
7) 7) 7)
5) 5) 5)
ABB
Table 2. Supported functions, continued Functionality Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Positive-sequence undervoltage protection, instance 1 Negative-sequence overvoltage protection, instance 1 Frequency protection, instance 1 Frequency protection, instance 2 Frequency protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector position indication, instance 1 A B C D E F G H
o o o
o o o
o o o
o o o
o o o
o o o
o o o
o o o
ABB
Table 2. Supported functions, continued Functionality Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication Auto-reclosing Synchronism and energizing check Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement A o B o C o D o E o F o G o H o
ABB
Table 2. Supported functions, continued Functionality Three-phase power and energy measurement, including power factor Frequency measurement A B C D E F G H
ABB
3. Protection functions
The IED offers directional and nondirectional overcurrent and thermal overload protection as well as directional and nondirectional earth-fault protection. Depending on the standard configuration, admittancebased earth-fault protection is offered as an alternative to the directional earth-fault protection. Further, the IED features sensitive earth-fault protection, phase discontinuity protection, transient/intermittent earth-fault protection, overvoltage and undervoltage protection, residual overvoltage protection, positive-sequence undervoltage and negativesequence overvoltage protection. Frequency protection, including overfrequency,
underfrequency and frequency rate-of-change protection, is offered in IEDs with standard configuration H. In addition, the IED offers three-pole multi-shot auto-reclose functions for overhead line feeders. Enhanced with optional hardware and software, the IED also features three light detection channels for arc fault protection of the circuit breaker, busbar and cable compartment of metal-enclosed indoor switchgear. The arc-fault protection sensor interface is available on the optional communication module. Fast tripping increases personnel safety and limits switchgear damage, should an arc fault occur.
IECA070911 V4 EN
10
ABB
IECA070912 V4 EN
ABB
11
GUID-91451BCB-E984-4F50-AE18-732D0ED542CF V2 EN
12
ABB
GUID-C5A6DAD5-BC11-4E7B-B0B4-4E9138AD63B4 V2 EN
ABB
13
GUID-E84B7815-9877-4E23-994F-0B2CF2D0F220 V1 EN
14
ABB
GUID-5A8E3AE6-5877-4EC8-B76A-098B5A9EF1ED V1 EN
4. Application
The feeder protection IED REF615 can be supplied either with directional or nondirectional earth-fault protection. Directional earth-fault protection is mainly used in isolated neutral or compensated networks, whereas non-directional earth-fault protection is intended for directly or low impedance earthed neutral networks. The IED can also be used for protection of ring-type and meshed distribution networks as well of radial networks containing distributed power generation.
The standard configurations A and B offer directional earth-fault protection, if the outgoing feeder is equipped with phase current transformers, a core-balance current transformer and residual voltage measurement. The residual current calculated from the phase currents can be used for double (cross country) earth-fault protection. The IED further features transient/ intermittent earth-fault protection. The standard configurations C and D offer nondirectional earth-fault protection for outgoing feeders equipped with phase current transformers. The residual current for the earth-fault protection is derived from the phase currents. When applicable, the corebalance current transformers can be used for
15
ABB
measuring the residual current, especially when sensitive earth-fault protection is required. The standard configurations E and F offer directional earth-fault protection with phase voltage and residual voltage measurement. Furthermore, the two standard configurations E and F include current circuit supervision and fuse failure supervision for incoming feeders provided with busbar voltage measurement. In addition to the functionality of standard configuration E, the standard configuration F offers directional overcurrent protection, overvoltage and undervoltage protection, positive-sequence undervoltage and negative-sequence overvoltage protection and residual voltage protection. The standard configuration G includes one conventional residual current (Io) input and three sensor inputs for the connection of three combi-sensors with RJ-45 connectors. The sensor inputs enable the use of the IED in compact medium voltage switchgear with limited space for conventional measuring transformers, thus requiring the use of sensor technology. Compact medium voltage switchgear, such as ABBs SafeRing and SafePlus, are designed for applications like compact secondary substations, wind turbine power plants, small industry installations and large buildings. As an alternative to combi-
sensors, separate current and voltage sensors can be utilized using adapters. Further, the adapters also enable the use of sensors with Twin-BNC connectors. The standard configuration H includes nondirectional overcurrent and non-directional earth-fault protection, phase-voltage and frequency based protection and measurement functions. The provided functionality supports the use of the standard configuration in industrial power systems, where the power is generated in the plant itself and/or derived from the distribution network. Completed with the synchro-check function, IEDs with standard configuration H ensure a safe interconnection of two networks. For standard configurations A, B, E, F and G admittance-based earth-fault protection, using the neutral admittance (Yo) criterion, is offered as an option to the directional earthfault protection. The admittance-based earthfault protection ensures the correct operation of the earth-fault protection even if the connection status information of the Petersen coil is missing. Furthermore, the admittance based earth-fault protection principle offers high independence of the fault resistance, straightforward setting principles and improved sensitivity of the protection.
16
ABB
IECA070905 V4 EN
Figure 7. Substation O/C and E/F protection using the standard configuration A or B with relevant options. In the incoming feeder bay, the protection functions not used are uncoloured and indicated with a dashed block outline. The IEDs are equipped with optional arc protection functions, enabling fast and selective arc protection throughout the switchgear.
ABB
17
IECA070920 V4 EN
Figure 8. Substation O/C and E/F protection using the standard configuration C or D with relevant options. In the incoming feeder bay the unemployed protection functions are uncoloured and indicated with a dashed block outline. The busbar protection is based on the interlocking principle, where the start of the O/C protection of the outgoing feeder sends a blocking signal to the instantaneous O/C stage of the incoming feeder. In the absence of the blocking signal, the O/C protection of the incoming feeder will clear the internal switchgear (busbar) fault.
18
ABB
GUID-28FD0F8B-3D60-4702-A4C2-473A6D4B529B V2 EN
Figure 9. Protection and control of two incoming feeders using IEDs with standard configuration F. The two incoming feeders can be connected in parallel by closing the busbar-sectionalizing breaker. To achieve selective overcurrent protection, directional overcurrent stages are needed. Busbar main and back-up protection for outgoing feeders is implemented using residual overvoltage protection stages. Phase undervoltage and overvoltage protection can be used for tripping or just alarming purposes.
ABB
19
GUID-CAFB8FA9-B405-43FE-867D-8625BEBA82C2 V1 EN
Figure 10. Protection and control of a typical compact medium voltage switchgear using REF615 IEDs with the standard configuration G. The phase currents and phase voltages are measured using combi-sensors supporting the Rogowski current sensor and voltage divider principles. The earth-fault current is measured using a conventional cable current transformer.
The 615 series IEDs offer native support for the IEC 61850 standard also including binary and analog horizontal GOOSE messaging. Compared with traditional hard-wired interdevice signaling, peer-to-peer communication over a switched Ethernet LAN offers an advanced and versatile platform for power system protection. Fast software-based communication, continuous supervision of the integrity of the protection and communication system, and inherent flexibility for reconfiguration and upgrades are among the distinctive features of the protection system approach enabled by the full implementation of the IEC 61850 substation automation standard. At the substation level COM600 uses the data content of the bay level IEDs to offer enhanced substation level functionality. COM600 features a web-browser based HMI providing a customizable graphical display for visualizing single line mimic diagrams for switchgear bay solutions. The SLD feature is
ABB
20
especially useful when 615 series IEDs without the optional single line diagram feature are used. Further, the web HMI of COM600 offers an overview of the whole substation, including IED-specific single line diagrams, thus enabling convenient information accessibility. To enhance personnel safety, the web HMI also enables remote access to substation devices and processes. Furthermore, COM600 can be used as a local data warehouse for technical documentation of the substation and for network data collected by the IEDs. The collected network data facilitates extensive reporting and analyzing of network fault situations using the data historian and event Table 3. Supported ABB solutions Product Station Automation COM600 MicroSCADA Pro System 800xA
handling features of COM600. The data historian can be used for accurate process performance monitoring by following process and equipment performance calculations with real-time and history values. Better understanding of the process behaviour by joining time-based process measurements with production and maintenance events helps the user in understanding the process dynamics. COM600 also features gateway functionality providing seamless connectivity between the substation IEDs and network-level control and management systems such as MicroSCADA Pro and System 800xA
ABB MicroSCADA
IEC 60870-5-104
Ethernet switch Analog and binary horizontal GOOSE communication IEC 61850
PCM600
Ethernet switch Analog and binary horizontal GOOSE communication Binary signal transfer IEC 61850
PCM600
REU615
REF615
RET615
RED615
RED615
RET615
REF615
REU615
GUID-66EB52A0-21A1-4D1F-A1EF-61060B371384 V2 EN
Figure 11. Utility power distribution network example using 615 series IEDs, Station Automation COM600 and MicroSCADA Pro
ABB
21
OPC
Ethernet switch Analog and binary horizontal GOOSE communication IEC 61850
PCM600
Ethernet switch Analog and binary horizontal GOOSE communication Binary signal transfer IEC 61850
PCM600
REU615
REF615
RET615
REM615
RED615
REM615
RET615
REF615
REU615
GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V2 EN
Figure 12. Industrial power system example using 615 series IEDs, Station Automation COM600 and System 800xA
6. Control
The IED offers control of one circuit breaker with dedicated push-buttons for circuit breaker opening and closing. Further, the optional large graphical LCD of the IEDs HMI includes a single-line diagram (SLD) with position indication for the relevant circuit breaker. Interlocking schemes required by the application are configured using the signal matrix or the application configuration feature of PCM600. Depending on the standard configuration, the IED also incorporates a synchro-check function to ensure that the voltage, phase angle and frequency on either side of an open circuit breaker satisfy the conditions for safe interconnection of two networks.
7. Measurement
The IED continuously measures the phase currents, the symmetrical components of the currents and the residual current. If the IED includes voltage measurements it also measures the residual voltage, the phase voltages and the voltage sequence components. Depending on the standard configuration the IED additionally offers frequency measurement. In addition, the IED calculates the demand value of current over a user-selectable pre-set time frames, the thermal overload of the protected object, and the phase unbalance value based on the ratio between the negative sequence and positive sequence current. Further, the IED offers three-phase power and energy measurement including power factor. The values measured can be accessed locally via the user interface on the IED front panel or remotely via the communication interface of the IED. The values can also be accessed
22
ABB
information demand of future network configurations. The SoE information can be accessed locally via the user interface on the IED front panel or remotely via the communication interface of the IED. The information can further be accessed, either locally or remotely, using the web-browser based user interface.
8. Disturbance recorder
The IED is provided with a disturbance recorder featuring up to 12 analog and 64 binary signal channels. The analog channels can be set to record either the waveform or the trend of the currents and voltage measured. The analog channels can be set to trigger the recording function when the measured value falls below or exceeds the set values. The binary signal channels can be set to start a recording on the rising or the falling edge of the binary signal or both. By default, the binary channels are set to record external or internal IED signals, for example the start or trip signals of the IED stages, or external blocking or control signals. Binary IED signals such as a protection start or trip signal, or an external IED control signal over a binary input can be set to trigger the recording. The recorded information is stored in a non-volatile memory and can be uploaded for subsequent fault analysis.
9. Event log
To collect sequence-of-events (SoE) information, the IED incorporates a nonvolatile memory with a capacity of storing 512 events with associated time stamps. The non-volatile memory retains its data also in case the IED temporarily loses its auxiliary supply. The event log facilitates detailed preand post-fault analyses of feeder faults and disturbances. The increased capacity to process and store data and events in the IED offers prerequisites to support the growing
ABB
23
13. Self-supervision
The IEDs built-in self-supervision system continuously monitors the state of the IED hardware and the operation of the IED software. Any fault or malfunction detected will be used for alerting the operator. A permanent IED fault will block the protection functions to prevent incorrect operation.
24
ABB
residual voltage input for directional earthfault protection and directional overcurrent protection. The standard configuration G includes one conventional residual current (Io 0.2/1 A) input and three sensor inputs for the direct connection of three combi-sensors with RJ-45 connectors. As an alternative to combi-sensors, separate current and voltage sensors can be utilized using adapters. Furthermore, the adapters also enable the use of sensors with Twin-BNC connectors. The phase-current inputs are rated 1/5 A. Two optional residual-current inputs are available, i.e. 1/5 A or 0.2/1 A. The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring core-balance current transformers. The three phase-voltage inputs and the residual-voltage input covers the rated voltages 60-210 V. Both phase-to-phase Table 4. Input/output overview Standard configuration A B C D E F G H Analog inputs CT 4 4 4 4 4 4 3+13) 4
voltages and phase-to-earth voltages can be connected. The phase-current input 1 A or 5 A, the residual-current input 1 A or 5 A, alternatively 0.2 A or 1 A, and the rated voltage of the residual voltage input are selected in the IED software. In addition, the binary input thresholds 18176 V DC are selected by adjusting the IEDs parameter settings. All binary inputs and outputs contacts are freely configurable with the signal matrix or application configuration functionality of PCM600. Please refer to the Input/output overview table and the terminal diagrams for more detailed information about the inputs and outputs.
1) With optional binary I/O module ( ) 2) One of the five inputs is reserved for future applications 3) Support for three Combi Sensors and one conventional Io input or three current sensors, three voltage sensors and one conventional Io input
ABB
25
18. Communication
The IED supports a range of communication protocols including IEC 61850, IEC 60870-5-103, Modbus and DNP3. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the IEDs, is only enabled by the IEC 61850 communication protocol. The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the standard COMTRADE file format. The IED supports simultaneous event reporting to five different clients on the station bus. The IED can send binary signals to other IEDs (so called horizontal communication) using the IEC 61850-8-1 GOOSE (Generic Object Oriented Substation Event) profile. Binary GOOSE messaging can, for example, be employed for protection and interlockingbased protection schemes. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard. Further, the IED supports the sending and receiving of analog values using GOOSE messaging. Analog GOOSE messaging enables fast transfer of analog measurement values over the station bus, thus facilitating for example sharing of RTD input values, such as surrounding temperature values, to other IED applications. The IED offers an optional second Ethernet bus to enable the creation of a self-healing Ethernet ring topology. The IED communication module options include both galvanic and fibre-optic Ethernet combinations. The communication module including one fibre-optic LC port and two galvanic RJ-45 ports is used when the ring
between the IEDs is built using CAT5 STP cables. The LC port can in this case be used for connecting the IED to communication ports outside the switchgear. The communication module including three RJ-45 ports is used when the whole substation bus is based on CAT5 STP cabling. The self-healing Ethernet ring solution enables a cost efficient communication ring controlled by a managed switch with rapid spanning tree protocol (RSTP) support to be created. The managed switch controls the consistency of the loop, routes the data and corrects the data flow in case of a communication disturbance. The IEDs in the ring topology act as unmanaged switches forwarding unrelated data traffic. The Ethernet ring solution supports the connection of up to thirty 615 series IEDs. If more than 30 IEDs are to be connected, it is recommended that the network is split into several rings with no more than 30 IEDs per ring. The self-healing Ethernet ring solution avoids single point of failure concerns and improves the reliability of the communication. The solution can be applied for the Ethernet-based IEC 61850, Modbus and DNP3 protocols. All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The IED can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fibre-optic LC connector (100Base-FX). If connection to a serial bus is required, the 10-pin RS-485 screwterminal or the fibre-optic ST connector can be used. Modbus implementation supports RTU, ASCII and TCP modes. Besides standard Modbus functionality, the IED supports retrieval of time-stamped events, changing the active setting group and uploading of the latest fault records. If a Modbus TCP connection is used, five clients can be connected to the IED simultaneously. Further, Modbus serial and Modbus TCP can be used in parallel, and if
26
ABB
required both IEC 61850 and Modbus protocols can be run simultaneously. The IEC 60870-5-103 implementation supports two parallel serial bus connections to two different masters. Besides basic standard functionality, the IED supports changing of the active setting group and uploading of disturbance recordings in IEC 60870-5-103 format. DNP3 supports both serial and TCP modes for connection to one master. Further, changing of the active setting group is supported. When the IED uses the RS-485 bus for the serial communication, both two- and four wire connections are supported. Termination and pull-up/down resistors can be configured with jumpers on the communication card so external resistors are not needed.
The IED supports the following time synchronization methods with a timestamping resolution of 1 ms: Ethernet-based: SNTP (Simple Network Time Protocol) With special time synchronization wiring: IRIG-B (Inter-Range Instrumentation Group - Time Code Format B) In addition, the IED supports time synchronization via the following serial communication protocols: Modbus DNP3 IEC 60870-5-103
Client A
Client B
Network Network
RED615
REF615
RET615
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V1 EN
REU615
REM615
ABB
27
Table 5. Supported station communication interfaces and protocols Interfaces/ Protocols Ethernet 100BASE-TX RJ-45 100BASE-FX LC Serial RS-232/RS-485 Fibre-optic ST
IEC 61850 MODBUS RTU/ ASCII MODBUS TCP/ IP DNP3 (serial) DNP3 TCP/IP IEC 60870-5-103 = Supported
28
ABB
T4A/250 V
ABB
29
Table 8. Energizing inputs Description Rated frequency Current inputs Rated current, In Thermal withstand capability: Continuously For 1 s Dynamic current withstand: Half-wave value Input impedance Voltage inputs Rated voltage Voltage withstand: Continuous For 10 s Burden at rated voltage
1) Ordering option for residual current input 2) Residual current and/or phase current
4A 100 A
20 A 500 A
1250 A <20 m
30
ABB
Table 9. Energizing inputs Description Current sensor input Value Rated current voltage 75 mV...2812.5 mV1) (in secondary side) Continuous voltage withstand Input impedance at 50/60 Hz Voltage sensor input Rated voltage Continuous voltage withstand Input impedance at 50/60 Hz 125 V 2-3 MOhm2) 6 kV...30 kV3) 50 V 3 MOhm
1) Equals the current range of 40A - 1250A with a 80A, 3mV/Hz Rogowski 2) Depending on the used nominal current (hardware gain) 3) This range is covered (up to 2*rated) with sensor division ratio of 10 000 : 1
Table 10. Binary inputs Description Operating range Rated voltage Current drain Power consumption Threshold voltage Reaction time Table 11. Signal outputs and IRF output Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry 0.5 s Value 250 V AC/DC 5A 10 A 15 A Value 20% of the rated voltage 24...250 V DC 1.6...1.9 mA 31.0...570.0 mW 18...176 V DC 3 ms
Breaking capacity when the control-circuit 1 A/0.25 A/0.15 A time constant L/R<40 ms, at 48/110/220 V DC Minimum contact load 100 mA at 24 V AC/DC
ABB
31
Table 12. Double-pole power output relays with TCS function Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC (two contacts connected in series) Minimum contact load Trip-circuit supervision (TCS): Control voltage range Current drain through the supervision circuit Minimum voltage over the TCS contact Table 13. Single-pole power output relays Description Rated voltage Continuous contact carry Make and carry for 3.0 s Make and carry for 0.5 s Value 250 V AC/DC 5A 15 A 30 A 20...250 V AC/DC ~1.5 mA Value 250 V AC/DC 8A 15 A 30 A 5 A/3 A/1 A
100 mA at 24 V AC/DC
20 V AC/DC (15...20 V)
Breaking capacity when the control-circuit 1 A/0.25 A/0.15 A time constant L/R<40 ms, at 48/110/220 V DC Minimum contact load Table 14. Front port Ethernet interfaces Ethernet interface Front Protocol TCP/IP protocol Cable Standard Ethernet CAT 5 cable with RJ-45 connector Data transfer rate 10 MBits/s 100 mA at 24 V AC/DC
32
ABB
Table 15. Station communication link, fibre-optic Connector LC LC ST Fibre type1) MM 62.5/125 m glass fibre core SM 9/125 m MM 62.5/125 m glass fibre core Wave length 1300 nm 1300 nm 820-900 nm Max. distance 2 km 2-20 km 1 km Permitted path attenuation2) <8 dB <8 dB <11 dB
1) (MM) multi-mode fibre, (SM) single-mode fibre 2) Maximum allowed attenuation caused by connectors and cable together
Table 16. IRIG-B Description IRIG time code format Isolation Modulation Logic level Current consumption Power consumption
1) According to 200-04 IRIG -standard
Value B004, B0051) 500V 1 min. Unmodulated TTL Level 2...4 mA 10...20 mW
Table 17. Lens sensor and optical fibre for arc protection Description Fibre-optic cable including lens Value 1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40...+100C Maximum service temperature range of the lens, max 1 h Minimum permissible bending radius of the connection fibre +140C 100 mm
Table 18. Degree of protection of flush-mounted IED Description Front side Rear side, connection terminals Value IP 54 IP 20
ABB
33
Table 19. Environmental conditions Description Operating temperature range Short-time service temperature range Relative humidity Atmospheric pressure Altitude Transport and storage temperature range Value -25...+55C (continuous) -40...+85C (<16h)1)2) <93%, non-condensing 86...106 kPa Up to 2000 m -40...+85C
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C 2) For IEDs with an LC communication interface the maximum operating temperature is +70 C
Table 20. Environmental tests Description Dry heat test (humidity <50%) Dry cold test Type test value 96 h at +55C 16 h at +85C1) 96 h at -25C 16 h at -40C Reference IEC 60068-2-2
IEC 60068-2-1
6 cycles (12 h + 12 h) at IEC 60068-2-30 +25C+55C, humidity >93% 96 h at -40C 96 h at +85C IEC 60068-2-48
Storage test
1) For IEDs with an LC communication interface the maximum operating temperature is +70oC
34
ABB
Table 21. Electromagnetic compatibility tests Description 1 MHz/100 kHz burst disturbance test: Common mode Differential mode Electrostatic discharge test: 2.5 kV 2.5 kV IEC 61000-4-2 IEC 60255-22-2 IEEE C37.90.3-2001 8 kV 15 kV Type test value Reference IEC 61000-4-18 IEC 60255-22-1, class III IEEE C37.90.1-2002
10 V (rms) f=150 kHz-80 MHz 10 V/m (rms) f=80-2700 MHz 10 V/m f=900 MHz 20 V/m (rms) f=80-1000 MHz Fast transient disturbance tests: All ports Surge immunity test: Communication Other ports Power frequency (50 Hz) magnetic field: Continuous 1-3 s 300 A/m 1000 A/m 1 kV, line-to-earth 4 kV, line-to-earth 2 kV, line-to-line 4 kV
IEC 61000-4-6 IEC 60255-22-6, class III IEC 61000-4-3 IEC 60255-22-3, class III ENV 50204 IEC 60255-22-3, class III IEEE C37.90.2-2004 IEC 61000-4-4 IEC 60255-22-4 IEEE C37.90.1-2002
IEC 61000-4-8
ABB
35
Table 21. Electromagnetic compatibility tests, continued Description Voltage dips and short interruptions Type test value 30%/10 ms 60%/100 ms 60%/1000 ms >95%/5000 ms Binary inputs only 300 V rms Reference IEC 61000-4-11
Power frequency immunity test: Common mode Differential mode Emission tests: Conducted 0.15-0.50 MHz 0.5-30 MHz Radiated 30-230 MHz 230-1000 MHz
< 79 dB(V) quasi peak < 66 dB(V) average < 73 dB(V) quasi peak < 60 dB(V) average
< 40 dB(V/m) quasi peak, measured at 10 m distance < 47 dB(V/m) quasi peak, measured at 10 m distance
36
ABB
Table 22. Insulation tests Description Dielectric tests Test voltage Impulse voltage test Test voltage 5 kV, 1.2/50 s, 0.5 J 1 kV, 1.2/50 s, 0.5 J, communication IEC 60255-5 and IEC 60255-27 >100 M, 500 V DC IEC 60255-27 <0.1 , 4 A, 60 s 2 kV, 50 Hz, 1 min 500 V, 50 Hz, 1 min, communication IEC 60255-5 and IEC 60255-27 Type test value Reference IEC 60255-5 and IEC 60255-27
Insulation resistance measurements Isolation resistance Protective bonding resistance Resistance Table 23. Mechanical tests Description Vibration tests (sinusoidal) Shock and bump test Reference IEC 60068-2-6 (test Fc) IEC 60255-21-1 IEC 60068-2-27 (test Ea shock) IEC 60068-2-29 (test Eb bump) IEC 60255-21-2 IEC 60255-21-3
Class 2
ABB
37
Table 25. EMC compliance Description EMC directive Standard Reference 2004/108/EC EN 50263 (2000) EN 60255-26 (2007)
Table 26. RoHS compliance Description Complies with RoHS directive 2002/95/EC
38
ABB
Protection functions
Table 27. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Operation accuracy PHLPTOC PHHPTOC and PHIPTOC Value Depending on the frequency of the current measured: fn 2 Hz 1.5% of the set value or 0.002 x In 1.5% of set value or 0.002 x In (at currents in the range of 0.110 x In) 5.0% of the set value (at currents in the range of 1040 x In) Minimum PHIPTOC: IFault = 2 x set Start value IFault = 10 x set Start value PHHPTOC and PHLPTOC: IFault = 2 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics 16 ms 11 ms Typical 19 ms 12 ms Maximum 23 ms 14 ms
Start time
1)2)
24 ms
25 ms
RMS: No suppression DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, Peak-to-Peak: No suppression P-to-P+backup: No suppression
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Includes the delay of the heavy-duty output contact
ABB
39
Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Start Value Function PHLPTOC PHHPTOC PHIPTOC Time multiplier PHLPTOC PHHPTOC Operate delay time PHLPTOC PHHPTOC PHIPTOC Operating curve type1) PHLPTOC Value (Range) 0.05...5.00 x In 0.10...40.00 x In 1.00...40.00 x In 0.05...15.00 0.05...15.00 40...200000 ms 40...200000 ms 20...200000 ms Step 0.01 0.01 0.01 0.05 0.05 10 10 10
Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 Definite time
PHHPTOC PHIPTOC
40
ABB
Table 29. Three-phase directional overcurrent protection (DPHxPDOC) Characteristic Operation accuracy DPHLPDOC Value Depending on the frequency of the current/ voltage measured: fn 2 Hz Current: 1.5% of the set value or 0.002 x In Voltage: 1.5% of the set value or 0.002 x Un Phase angle: 2 Current: 1.5% of the set value or 0.002 x In (at currents in the range of 0.110 x In) 5.0% of the set value (at currents in the range of 1040 x In) Voltage: 1.5% of the set value or 0.002 x Un Phase angle: 2 Minimum IFault = 2.0 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics 37 ms < 40 ms Typical 0.96 < 35 ms 1.0% of the set value or 20 ms 5.0% of the theoretical value or 20 ms3) DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, Typical 40 ms Maximum 42 ms
DPHHPDOC
Start time1)2)
1) Measurement mode and Pol quantity = default, current before fault = 0.0 x In, voltage before fault = 1.0 x Un, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 x In, Start value multiples in range of 1.5 to 20
ABB
41
Table 30. Three-phase directional overcurrent protection (DPHxPDOC) main settings Parameter Start value Function DPHLPDOC DPHHPDOC Time multiplier Operate delay time Directional mode DPHxPDOC DPHxPDOC DPHxPDOC Value (Range) 0.05...5.00 x In 0.10...40.00 x In 0.05...15.00 40...200000 ms 1 = Non-directional 2 = Forward 3 = Reverse -179...180 deg 1 Step 0.01 0.01 0.05 10
DPHxPDOC DPHLPDOC
Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17
DPHHPDOC
42
ABB
Table 31. Non-directional earth-fault protection (EFxPTOC) Characteristic Operation accuracy EFLPTOC EFHPTOC and EFIPTOC Value Depending on the frequency of the current measured: fn 2 Hz 1.5% of the set value or 0.002 x In 1.5% of set value or 0.002 x In (at currents in the range of 0.110 x In) 5.0% of the set value (at currents in the range of 1040 x In) Minimum EFIPTOC: IFault = 2 x set Start value IFault = 10 x set Start value EFHPTOC and EFLPTOC: IFault = 2 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics 16 ms 11 ms Typical 19 ms 12 ms Maximum 23 ms 14 ms
Start time
1)2)
22 ms
24 ms
25 ms
< 40 ms Typical 0.96 < 30 ms 1.0% of the set value or 20 ms 5.0% of the theoretical value or 20 ms
3)
1) Measurement mode = default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 x In, Start value multiples in range of 1.5 to 20
ABB
43
Table 32. Non-directional earth-fault protection (EFxPTOC) main settings Parameter Start value Function EFLPTOC EFHPTOC EFIPTOC Time multiplier EFLPTOC EFHPTOC Operate delay time EFLPTOC EFHPTOC EFIPTOC Operating curve type1) EFLPTOC Value (Range) 0.010...5.000 x In 0.10...40.00 x In 1.00...40.00 x In 0.05...15.00 0.05...15.00 40...200000 ms 40...200000 ms 20...200000 ms Step 0.005 0.01 0.01 0.05 0.05 10 10 10
Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 Definite or inverse time Curve type: 1, 3, 5, 9, 10, 12, 15, 17 Definite time
EFHPTOC EFIPTOC
44
ABB
Table 33. Directional earth-fault protection (DEFxPDEF) Characteristic Operation accuracy DEFLPDEF Value Depending on the frequency of the current measured: fn 2 Hz Current: 1.5% of the set value or 0.002 x In Voltage 1.5% of the set value or 0.002 x Un Phase angle: 2 Current: 1.5% of the set value or 0.002 x In (at currents in the range of 0.110 x In) 5.0% of the set value (at currents in the range of 1040 x In) Voltage: 1.5% of the set value or 0.002 x Un Phase angle: 2 Minimum DEFHPDEF IFault = 2 x set Start value DEFLPDEF IFault = 2 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics 42 ms 61ms Typical 44 ms 64 ms Maximum 46 ms 66 ms
DEFHPDEF
Start time
1)2)
< 40 ms Typical 0.96 < 30 ms 1.0% of the set value or 20 ms 5.0% of the theoretical value or 20 ms
3)
1) Set Operate delay time = 0.06 s,Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 x In, Start value multiples in range of 1.5 to 20
ABB
45
Table 34. Directional earth-fault protection (DEFxPDEF) main settings Parameter Start Value Function DEFLPDEF DEFHPDEF Directional mode DEFLPDEF and DEFHPDEF DEFLPDEF DEFHPDEF Operate delay time DEFLPDEF DEFHPDEF Operating curve type1) DEFLPDEF Value (Range) 0.010...5.000 x In 0.10...40.00 x In 1=Non-directional 2=Forward 3=Reverse 0.05...15.00 0.05...15.00 60...200000 ms 40...200000 ms 0.05 0.05 10 10 Step 0.005 0.01
Time multiplier
Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19 Definite or inverse time Curve type: 1, 3, 5, 15, 17 1=Phase angle 2=IoSin 3=IoCos 4=Phase angle 80 5=Phase angle 88
Table 35. Transient/intermittent earth-fault protection (INTRPTEF) Characteristic Operation accuracy (Uo criteria with transient protection) Value Depending on the frequency of the current measured: fn 2 Hz 1.5% of the set value or 0.002 x Uo Operate time accuracy Suppression of harmonics 1.0% of the set value or 20 ms DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5
46
ABB
Table 36. Transient/intermittent earth-fault protection (INTRPTEF) main settings Parameter Directional mode Function INTRPTEF Value (Range) 1=Non-directional 2=Forward 3=Reverse 40...1200000 ms 0.01...0.50 x Un Step -
Operate delay time Voltage start value (voltage start value for transient EF) Operation mode Peak counter limit (Min requirement for peak counter before start in IEF mode)
INTRPTEF INTRPTEF
10 0.01
INTRPTEF INTRPTEF
Table 37. Admittance-based earth-fault protection (EFPADM) Characteristic Operation accuracy1) Value At the frequency f = fn 1.0% or 0.01 mS (In range of 0.5 - 100 mS) Start time2) Minimum 56 ms Reset time Operate time accuracy Suppression of harmonics 40 ms 1.0% of the set value of 20 ms -50 dB at f = n x fn, where n = 2, 3, 4, 5, Typical 60 ms Maximum 64 ms
1) Uo = 1.0 x Un 2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
ABB
47
Table 38. Admittance-based earth-fault protection (EFPADM) main settings Parameter Voltage start value Directional mode Values (Range) 0.05...5.00 1=Nondirectional 2=Forward 3=Reverse 1=Yo 2=Go 3=Bo 4=Yo, Go 5=Yo, Bo 6=Go, Bo 7=Yo, Go, Bo 60...200000 0.05...500.00 ms mS 10 0.01 0.01 Unit xUn Step 0.01 Default 0.05 2=Forward Description Voltage start value Directional mode
Operation mode
1=Yo
Operation criteria
60 1.00 0.00
Operate delay time Admittance circle radius Admittance circle midpoint, conductance Admittance circle midpoint, susceptance Conductance threshold in forward direction Conductance threshold in reverse direction Tilt angle of conductance boundary line
-500.00...500.00 mS
Circle susceptance
-500.00...500.00 mS
0.01
0.00
Conductance forward
-500.00...500.00 mS
0.01
1.00
-500.00...500.00 mS
0.01
-1.00
-30...30
deg
48
ABB
Table 38. Admittance-based earth-fault protection (EFPADM) main settings, continued Parameter Susceptance forward Values (Range) Unit Step 0.01 Default 1.00 Description Susceptance threshold in forward direction Susceptance threshold in reverse direction Tilt angle of susceptance boundary line
-500.00...500.00 mS
0.01
-1.00
deg
Table 39. Three-phase overvoltage protection (PHPTOV) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz 1.5% of the set value or 0.002 x Un Start time1)2) UFault = 1.1 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics Minimum 22 ms < 40 ms Depends of the set Relative hysteresis < 35 ms 1.0% of the set value or 20 ms 5.0% of the theoretical value or 20 ms3) DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, Typical 24 ms Maximum 26 ms
1) Start value = 1.0 x Un, Voltage before fault = 0.9 x Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 1.20 x Un, Start value multiples in range of 1.10 to 2.00
ABB
49
Table 40. Three-phase overvoltage protection (PHPTOV) main settings Parameter Start value Time multiplier Operate delay time Operating curve type1) Function PHPTOV PHPTOV PHPTOV PHPTOV Value (Range) 0.05...1.60 x Un 0.05...15.00 40...300000 ms Step 0.01 0.05 10
Table 41. Three phase undervoltage protection (PHPTUV) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz 1.5% of the set value or 0.002 x Un Start time1)2) UFault = 0.9 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics Minimum 62 ms < 40 ms Depends on the set Relative hysteresis < 35 ms 1.0% of the set value or 20 ms 5.0% of the theoretical value or 20 ms3) DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, Typical 64 ms Maximum 66 ms
1) Start value = 1.0 x Un, Voltage before fault = 1.1 x Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20
50
ABB
Table 42. Three-phase undervoltage protection (PHPTUV) main settings Parameter Start value Time multiplier Operate delay time Operating curve type1) Function PHPTUV PHPTUV PHPTUV PHPTUV Value (Range) 0.05...1.20 x Un 0.05...15.00 60...300000 ms Step 0.01 0.05 10
Table 43. Positive sequence undervoltage protection (PSPTUV) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz 1.5% of the set value or 0.002 x Un Start time1)2) UFault = 0.99 x set Start value UFault = 0.9 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Suppression of harmonics Minimum 51 ms 43 ms < 40 ms Depends of the set Relative hysteresis < 35 ms 1.0% of the set value or 20 ms DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, Typical 53 ms 45 ms Maximum 54 ms 46 ms
1) Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x Un, fn = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact
Table 44. Positive sequence undervoltage protection (PSPTUV) main settings Parameter Start value Operate delay time Voltage block value Function PSPTUV PSPTUV PSPTUV Value (Range) 0.010...1.200 x Un 40...120000 ms 0.01...1.0 x Un Step 0.001 10 0.01
ABB
51
Table 45. Frequency protection (FRPFRQ) Characteristic Operation accuracy f>/f< df/dt Value 10 mHz 100 mHz/s (in range |df/ dt| < 5 Hz/s) 2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s) < 80 ms < 120 ms < 150 ms 1.0% of the set value or 30 ms
Start time
f>/f< df/dt
52
ABB
Table 46. Frequency protection (FRPFRQ) main settings Parameter Operation mode Values (Range) 1=Freq< 2=Freq> 3=df/dt 4=Freq< + df/dt 5=Freq> + df/dt 6=Freq< OR df/ dt 7=Freq> OR df/ dt 0.900...1.200 xFn 0.001 Unit Step Default 1=Freq< Description Frequency protection operation mode selection
1.050
Frequency start value overfrequency Frequency start value underfrequency Frequency start value rate of change Operate delay time for frequency Operate delay time for frequency rate of change
0.800...1.100
xFn
0.001
0.950
-0.200...0.200
xFn /s
0.005
0.010
Operate Tm Freq
80...200000
ms
10
200
Operate Tm df/dt
120...200000
ms
10
400
ABB
53
Table 47. Negative sequence overvoltage protection (NSPTOV) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz 1.5% of the set value or 0.002 Un Start time1)2) UFault = 1.1 set Start value UFault = 2.0 set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Suppression of harmonics Minimum 33 ms 24 ms < 40 ms Typical 0.96 < 35 ms 1.0% of the set value or 20 ms DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5, Typical 35 ms 26 ms Maximum 37 ms 28 ms
1) Negative-sequence voltage before fault = 0.0 Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact
Table 48. Negative sequence overvoltage protection (NSPTOV) main settings Parameter Start value Operate delay time Function NSPTOV NSPTOV Value (Range) 0.010...1.000 x Un 40...120000 ms Step 0.001 1
54
ABB
Table 49. Residual overvoltage protection (ROVPTOV) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz 1.5% of the set value or 0.002 x Un Start time1)2) UFault = 1.1 x set Start value Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Suppression of harmonics Minimum 55 ms < 40 ms Typical 0.96 < 35 ms 1.0% of the set value or 20 ms DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, Typical 56 ms Maximum 58 ms
1) Residual voltage before fault = 0.0 x Un, fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact
Table 50. Residual overvoltage protection (ROVPTOV) main settings Parameter Start value Operate delay time Function ROVPTOV ROVPTOV Value (Range) 0.010...1.000 x Un 40...300000 ms Step 0.001 1
ABB
55
Table 51. Negative phase-sequence overcurrent protection (NSPTOC) Characteristic Operation accuracy Value Depending on the frequency of the current measured: fn 2 Hz 1.5% of the set value or 0.002 x In Start time
1)2)
Typical 24 ms 16 ms
Maximum 25 ms 17 ms
Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Operate time accuracy in inverse time mode Suppression of harmonics
< 40 ms Typical 0.96 < 35 ms 1.0% of the set value or 20 ms 5.0% of the theoretical value or 20 ms
3)
1) Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements 2) Includes the delay of the signal output contact 3) Maximum Start value = 2.5 x In, Start value multiples in range of 1.5 to 20
Table 52. Negative phase-sequence overcurrent protection (NSPTOC) main settings Parameter Start value Time multiplier Operate delay time Operating curve type1) Function NSPTOC NSPTOC NSPTOC NSPTOC Value (Range) 0.01...5.00 x In 0.05...15.00 40...200000 ms Step 0.01 0.05 10
Definite or inverse time Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
56
ABB
Table 53. Phase discontinuity protection (PDNSPTOC) Characteristic Operation accuracy Value Depending on the frequency of the current measured: fn 2 Hz 2% of the set value Start time Reset time Reset ratio Retardation time Operate time accuracy in definite time mode Suppression of harmonics < 70 ms < 40 ms Typical 0.96 < 35 ms 1.0% of the set value or 20 ms DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
Table 54. Phase discontinuity protection (PDNSPTOC) main settings Parameter Start value (Current ratio setting I2/I1) Operate delay time Min phase current Function PDNSPTOC PDNSPTOC PDNSPTOC Value (Range) 10...100 % 100...30000 ms 0.05...0.30 x In Step 1 1 0.01
Table 55. Circuit breaker failure protection (CCBRBRF) Characteristic Operation accuracy Value Depending on the frequency of the current measured: fn 2 Hz 1.5% of the set value or 0.002 x In Operate time accuracy 1.0% of the set value or 20 ms
ABB
57
Table 56. Circuit breaker failure protection (CCBRBRF) main settings Parameter Current value (Operating phase current) Current value Res (Operating residual current) CB failure mode (Operating mode of function) CB fail trip mode Function CCBRBRF Value (Range) 0.05...1.00 x In Step 0.05
CCBRBRF
0.05...1.00 x In
0.05
CCBRBRF
1=Current 2=Breaker status 3=Both 1=Off 2=Without check 3=Current check 0...60000 ms 0...60000 ms 0...60000 ms
CCBRBRF
10 10 10
Table 57. Three-phase thermal overload protection for feeders (T1PTTR) Characteristic Operation accuracy Value Depending on the frequency of the current measured: fn 2 Hz Current measurement: 1.5% of the set value or 0.002 x In (at currents in the range of 0.01...4.00 x In) Operate time accuracy1)
1) Overload current > 1.2 x Operate level temperature
58
ABB
Table 58. Three-phase thermal overload (T1PTTR) main settings Parameter Function Value (Range) -50...100C Step 1
Env temperature Set T1PTTR (Ambient temperature used when the AmbSens is set to Off) Current multiplier (Current multiplier when function is used for parallel lines) Current reference Temperature rise (End temperature rise above ambient) Time constant (Time constant of the line in seconds) Maximum temperature (temperature level for operate) Alarm value (Temperature level for start (alarm) Reclose temperature (Temperature for reset of block reclose after operate) Initial temperature (Temperature raise above ambient temperature at startup) T1PTTR
1...5
T1PTTR T1PTTR
0.05...4.00 x In 0.0...200.0C
0.01 0.1
T1PTTR
60...60000 s
T1PTTR
20.0...200.0C
0.1
T1PTTR
20.0...150.0C
0.1
T1PTTR
20.0...150.0C
0.1
T1PTTR
-50.0...100.0C
0.1
ABB
59
Table 59. Three-phase inrush current detection (INRPHAR) Characteristic Operation accuracy Value At the frequency f = fn Current measurement: 1.5% of the set value or 0.002 x In Ratio I2f/I1f measurement: 5.0% of the set value Reset time Reset ratio Operate time accuracy +35 ms / -0 ms Typical 0.96 +35 ms / -0 ms
Table 60. Three-phase inrush detection (INRPHAR) main settings Parameter Start value (Ratio of the 2nd to the 1st harmonic leading to restraint) Operate delay time Function INRPHAR Value (Range) 5...100 % Step 1
INRPHAR
20...60000 ms
Table 61. Arc protection (ARCSARC) Characteristic Operation accuracy Operate time Operation mode = "Light+current"1)2) Operation mode = "Light only"2) Reset time Reset ratio Value 3% of the set value or 0.01 x In Minimum 9 ms 9 ms < 40 ms Typical 0.96 Typical 12 ms 10 ms Maximum 15 ms 12 ms
1) Phase start value = 1.0 x In, current before fault = 2.0 x set Phase start value, fn = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements 2) Includes the delay of the heavy-duty output contact
60
ABB
Table 62. Arc protection (ARCSARC) main settings Parameter Phase start value (Operating phase current) Ground start value (Operating residual current) Operation mode Function ARCSARC Value (Range) 0.50...40.00 x In Step 0.01
ARCSARC
0.05...8.00 x In
0.01
ARCSARC
Table 63. Operation characteristics Parameter Operating curve type Values (Range) 1=ANSI Ext. inv. 2=ANSI Very. inv. 3=ANSI Norm. inv. 4=ANSI Mod inv. 5=ANSI Def. Time 6=L.T.E. inv. 7=L.T.V. inv. 8=L.T. inv. 9=IEC Norm. inv. 10=IEC Very inv. 11=IEC inv. 12=IEC Ext. inv. 13=IEC S.T. inv. 14=IEC L.T. inv 15=IEC Def. Time 17=Programmable 18=RI type 19=RD type 5=ANSI Def. Time 15=IEC Def. Time 17=Inv. Curve A 18=Inv. Curve B 19=Inv. Curve C 20=Programmable 21=Inv. Curve A 22=Inv. Curve B 23=Programmable
ABB
61
Control functions
Table 64. Autoreclosure (DARREC) Characteristic Operate time accuracy Table 65. Synchrocheck (SECRSYN) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 1 Hz Voltage: 3.0% of the set value or 0.01 x Un Frequency: 10 mHz Phase angle: 3 Reset time Reset ratio Operate time accuracy in definite time mode < 50 ms Typical 0.96 1.0% of the set value or 20 ms Value 1.0% of the set value or 20 ms
62
ABB
Table 66. Synchronism and energizing check (SECRSYN) main settings Parameter Live dead mode Values (Range) -1=Off 1=Both Dead 2=Live L, Dead B 3=Dead L, Live B 4=Dead Bus, L Any 5=Dead L, Bus Any 6=One Live, Dead 7=Not Both Live 0.01...0.50 xUn 0.01 Unit Step Default 1=Both Dead Description Energizing check mode
Difference voltage
0.05
Maximum voltage difference limit Maximum frequency difference limit Maximum angle difference limit Synchrocheck operation mode Selection of the synchrocheck command or continuous control mode Voltage lowlimit line for energizing check Voltage highlimit line for energizing check
Difference frequency
0.001...0.100
xFn
0.001
0.001
Difference angle
5...90
deg
2=Synchronous
1=Continuous
0.1...0.8
xUn
0.1
0.2
xUn
0.1
0.5
ABB
63
Table 66. Synchronism and energizing check (SECRSYN) main settings, continued Parameter Close pulse Values (Range) 200...60000 Unit ms Step 10 Default 200 Description Breakerclosing pulse duration Maximum voltage for energizing Correction of phase difference between measured U_BUS and U_LINE Minimum time to accept synchronizing Maximum time to accept synchronizing Time delay for energizing check Closing time of the breaker
0.50...1.15
xUn
0.01
1.05
-180...180
deg
180
0...60000
ms
10
ms
10
2000
ms
10
100
40...250
ms
10
60
Measurement functions
Table 67. Three-phase current measurement (CMMXU) Characteristic Operation accuracy Value Depending on the frequency of the current measured: fn 2 Hz 0.5% or 0.002 x In (at currents in the range of 0.01...4.00 x In) Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, RMS: No suppression
64
ABB
Table 68. Current sequence components (CSMSQI) Characteristic Operation accuracy Value Depending on the frequency of the current measured: f/fn = 2 Hz 1.0% or 0.002 x In at currents in the range of 0.01...4.00 x In Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
Table 69. Three-phase voltage measurement (VMMXU) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz At voltages in range 0.011.15 x Un 0.5% or 0.002 x Un Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, RMS: No suppression
Table 70. Voltage sequence components (VSMSQI) Characteristic Operation accuracy Value Depending on the frequency of the voltage measured: fn 2 Hz At voltages in range 0.011.15 x Un 1.0% or 0.002 x Un Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
Table 71. Residual current measurement (RESCMMXU) Characteristic Operation accuracy Value Depending on the frequency of the current measured: f/fn = 2 Hz 0.5% or 0.002 x In at currents in the range of 0.01...4.00 x In Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, RMS: No suppression
ABB
65
Table 72. Residual voltage measurement (RESVMMXU) Characteristic Operation accuracy Value Depending on the frequency of the current measured: f/fn = 2 Hz 0.5% or 0.002 x Un Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5, RMS: No suppression
Table 73. Three-phase power and energy (PEMMXU) Characteristic Operation accuracy Value At all three currents in range 0.101.20 x In At all three voltages in range 0.501.15 x Un At the frequency fn 1 Hz Active power and energy in range |PF| > 0.71 Reactive power and energy in range |PF| < 0.71 1.5% for power (S, P and Q) 0.015 for power factor 1.5% for energy Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
Table 74. Frequency measurement (FMMXU) Characteristic Operation accuracy Value 10 mHz (in measurement range 35 - 75 Hz)
Supervision functions
Table 75. Current circuit supervision (CCRDIF) Characteristic Operate time1)
1) Including the delay of the output contact.
Value < 30 ms
66
ABB
Table 76. Current circuit supervision (CCRDIF) main settings Parameter Start value Values (Range) 0.05...0.20 Unit x In Description Minimum operate current differential level Block of the function at high phase current
1.00...5.00
x In
Table 77. Fuse failure supervision (SEQRFUF) Characteristic Operate time1) NPS function UFault = 1.1 x set Neg Seq voltage Lev UFault = 5.0 x set Neg Seq voltage Lev Delta function U = 1.1 x set Voltage change rate U = 2.0 x set Voltage change rate < 33 ms < 18 ms < 30 ms < 24 ms Value
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
ABB
67
configuration, the IED displays the related measuring values, apart from the default single line diagram. The SLD view can also be accessed using the web-browser based user interface. The default SLD can be modified according to user requirements by using the graphical display editor in PCM600. The local HMI includes a push button (L/R) for local/remote operation of the IED. When the IED is in the local mode, the IED can be operated only by using the local front panel user interface. When the IED is in the remote mode, the IED can execute commands sent from a remote location. The IED supports the remote selection of local/remote mode via a binary input. This feature facilitates, for example, the use of an external switch at the substation to ensure that all IEDs are in the local mode during maintenance work and that the circuit breakers cannot be operated remotely from the network control centre.
IECA070904 V3 EN
IECA070901 V3 EN
Figure 14. Small display Table 78. Small display Character size1) Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels)
1) Depending on the selected language
68
ABB
Table 79. Large display Character size1) Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels)
1) Depending on the selected language
type RTXP 18, which can be mounted side by side with the IED cases. Mounting methods: Flush mounting Semi-flush mounting Semi-flush mounting in a 25 tilt Rack mounting Wall mounting Mounting to a 19" equipment frame Mounting with a RTXP 18 test switch to a 19" rack Panel cut-out for flush mounting: Height: 161.51 mm Width: 165.51 mm
190
186
177
25
160
160
177
177
98
10 7
1 03
153
48
13 3
IECA070903 V3 EN
IECA070902 V3 EN
IECA070900 V3 EN
ABB
230
69
placed above the HMI on the upper part of the plug-in-unit. An order number label is placed on the side of the plug-in unit as well as inside the case. The order number consists of a string of codes generated from the IED's hardware and software modules. Use the ordering key information to generate the order number when ordering complete IEDs.
2 3
Standard
IEC B F
IECA070913 V6 EN
Main application
Feeder protection and control
70
ABB
H B F FA E A G B C C 1 B B A 1 X D # DESCRIPTION 4-8
A = Non-directional O/C and directional E/F protection. B = Non-directional O/C and directional E/F protection, CB condition monitoring C = Non-directional O/C and non-directional E/F protection D = Non-directional O/C and non-directional E/F protection, CB condition monitoring E = Non-directional O/C and directional E/F protection with phase-voltage based measurements, CB condition monitoring F = Directional O/C and directional E/F protection with phasevoltage based measurements, undervoltage and overvoltage protection, CB condition monitoring G = Directional O/C and directional E/F protection, phase-voltage based protection and measurement functions, CB condition monitoring, (sensor inputs) H = Non-directional O/C and non-directional E/F protection, voltage and frequency based protection and measurement functions, synchro-check and CB condition monitoring Std. conf A: 4I + Uo (Io 1/5 A) + 3 BI + 6 BO Std. conf A: 4I + Uo (Io 0.2/1 A) + 3 BI + 6 BO Std. conf B: 4I +Uo (Io 1/5 A) + 11 BI + 10 BO Std. conf B: 4I +Uo (Io 1/5 A) + 17 BI + 13 BO Std. conf B: 4I +Uo (Io 0.2/1 A) + 11 BI + 10 BO Std. conf B: 4I +Uo (Io 0.2/1 A) + 17 BI + 13 BO Std. conf C: 4I (Io 1/5 A) + 4 BI + 6 BO Std. conf C: 4I (Io 0.2/1 A) + 4 BI + 6 BO Std. conf D: 4I (Io 1/5 A) + 12 BI + 10 BO Std. conf D: 4I (Io 1/5 A) + 18 BI + 13 BO Std. conf D: 4I (Io 0.2/1 A) + 12 BI + 10 BO Std. conf D: 4I (Io 0.2/1 A) + 18 BI + 13 BO Std. conf E: 4I (Io 1/5 A) + 5U + 16 BI + 10 BO Std. conf E: 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO Std. conf F: 4I (Io 1/5 A) + 5U + 16 BI + 10 BO Std. conf F: 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO Std. conf G: 3Is + 3Us +Io (Io 0.2/1 A) + 8 BI + 10 BO Std. conf H: 4I (Io 1/5 A) + 5U + 16 BI + 10 BO Std. conf H: 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO
IECA070915 V7 EN
AAAAA AABAA BAAAC BAAAE BABAC BABAE CACAB CADAB DACAD DACAF DADAD DADAF EAEAG EAFAG FAEAG FAFAG GDAAH HAEAG HAFAG
ABB
71
The communication module hardware determines the available communication protocols. H B F FA E A G B C C 1 B B A 1 X D # 9 10 DESCRIPTION
Communication modules (Serial/Ethernet)
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX (1 x LC) Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-TX (1 x RJ-45) Serial RS-485, incl. an input for IRIG-B tor and an input for IRIG-B (cannot be combined with arc protection) (1 x RJ-45) + Serial RS-485 connector, RS232/485 D-Sub 9 connector + input for IRIG-B (cannot be combined with arc protection) (3 x RJ-45) and -FX (2 x RJ-45 + 1 x LC) Ethernet 100Base-FX (1 x LC) Ethernet 100Base-TX (1 x RJ-45) Ethernet 100Base-TX (2 x RJ-45 + 1 x LC) Ethernet 100Base-TX (3 x RJ-45) No communication module
AA AB AN BN
BB
BD BC NA NB NC ND NN
If serial communication is chosen, please choose a serial communication module including Ethernet (for example BC) if a service bus for PCM600 or the WebHMI is required.
GUID-2B09FD03-F732-4AF6-BCC1-D3473FA2667C V1 EN
72
ABB
H B F FA E A G B C C 1 B B A 1 X D # 11 DESCRIPTION
Communication protocols
IEC 61850 (for Ethernet communication modules and IEDs without a communication module ) Modbus (for Ethernet/serial or Ethernet + serial communication modules) IEC 61850 + Modbus (for Ethernet or serial + Ethernet communication modules) IEC 60870-5-103 (for serial or Ethernet + serial communication modules) DNP3 (for Ethernet/serial or Ethernet + serial communication modules)
GUID-45F9436D-9C24-48C1-A5F5-77B0EA230FB2 V1 EN
ABB
73
H B F FA E A G B C C 1 B B A 1 X D # 12 DESCRIPTION Language
English English and German English and Swedish English and Spanish English and Russian English and Portuguese (Brazilian) 1 3 4 5 6 8 A B A B
13
Front panel
Small LCD Large LCD with single line diagram (SLD)
14
Option 1
Auto-reclosing Arc protection (requires a communication module, cannot be combined with communication modules BN or BB) Arc protection and auto-reclosing (requires a communication module, cannot be combined with communication modules BN, BB) None
C N A B N 1 2 X D
15
Option 2
ration: A, B, E, F, G) Admittance based earth-fault protection (only for std None
16
Power supply
48...250 V DC, 100...240 V AC 24...60 V DC
17 18
Vacant digit
Vacant
Version
Version 3.0
IECA070914 V7 EN
IECA070917 V7 EN
10
11
12
13
14
15
16
17
18
74
ABB
25. Tools
The IED is delivered as a pre-configured unit. The default parameter setting values can be changed from the front-panel user interface, the web-browser based user interface (WebHMI) or the PCM600 tool in combination with the IED-specific connectivity package. The Protection and Control IED Manager PCM600 is available in three different variants, that is PCM600, PCM600 Engineering and PCM600 Engineering Pro. Depending on the chosen variant, PCM600
ABB
offers extensive IED configuration functions such as IED signal configuration, application configuration, graphical display configuration including single line diagram configuration, and IEC 61850 communication configuration including horizontal GOOSE communication. When the web-browser based user interface is used, the IED can be accessed either locally or remotely using a web browser (IE 7.0 or later). For security reasons, the webbrowser based user interface is disabled by default. The interface can be enabled with the PCM600 tool or from the front panel user interface. The functionality of the interface
75
can be limited to read-only access by means of PCM600. The IED connectivity package is a collection of software and specific IED information, which enable system products and tools to connect and interact with the IED. The connectivity packages reduce the risk of errors in system integration, minimizing device configuration and set-up times. Table 82. Tools Configuration and setting tools PCM600 Web-browser based user interface REF615 Connectivity Package
Further, the Connectivity Packages for the 615 series IEDs include a flexible update tool for adding one additional local HMI language to the IED. The update tool is activated using PCM600 and enables multiple updates of the additional HMI language, thus offering flexible means for possible future language updates.
76
ABB
Table 83. Supported functions Function WebHMI PCM600 PCM600 Engineering PCM600 Engineering Pro
IED parameter setting Saving of IED parameter settings in the IED Signal monitoring Disturbance recorder handling Alarm LED viewing Access control management IED signal configuration (signal matrix) Modbus communication configuration (communication management) DNP3 communication configuration (communication management) IEC 60870-5-103 communication configuration (communication management) Saving of IED parameter settings in the tool Disturbance record analysis XRIO parameter export/import Graphical display configuration
ABB
77
Table 83. Supported functions, continued Function WebHMI PCM600 PCM600 Engineering PCM600 Engineering Pro
Application configuration IEC 61850 communication configuration, GOOSE (communication configuration) Phasor diagram viewing Event viewing Saving of event data on the user's PC = Supported
78
ABB
IECA070918 V6 EN
ABB
79
IECA070919 V6 EN
80
ABB
GUID-FA7A5888-5288-4969-84D0-00354EAB3997 V4 EN
ABB
81
GUID-88778A7A-2A9B-46BF-AC33-075626A03AC8 V1 EN
82
ABB
GUID-F4CCBBC7-41DD-4E1C-99E8-69029EC6933C V1 EN
ABB
83
27. Certificates
KEMA has issued an IEC 61850 Certificate Level A1 for REF615. Certificate number: 30710144-Consulting 08-0115.
29. References
The www.abb.com/substationautomation portal offers you information about the distribution automation product and service range. You will find the latest relevant information on the REF615 protection IED on the product page. The download area on the right hand side of the web page contains the latest product documentation, such as technical reference manual, installation manual, operators manual, etc. The selection tool on the web page helps you find the documents by the document category and language. The Features and Application tabs contain product related information in a compact format.
84
ABB
GUID-7538BF96-88EE-413C-86C7-FC91CC8AD358 V3 EN
ABB
85
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
PHIPTOC1
3I>>> (1)
50P/51P (1)
DPHLPDOC1
67-1 (1)
DPHLPDOC2
67-1 (2)
3I>> -> Io> (1) Io> (2) Io>> (1) Io>>> Io> -> (1) Io> -> (2) Io>> ->
67-2 51N-1 (1) 51N-1 (2) 51N-2 (1) 50N/51N 67N-1 (1) 67N-1 (2) 67N-2
86
ABB
Table 84. REF615 Functions, codes and symbols, continued Function Admittance based earth-fault protection, instance 1 Admittance based earth-fault protection, instance 2 Admittance based earth-fault protection, instance 3 Transient / intermittent earth-fault protection Non-directional (cross-country) earth fault protection, using calculated Io Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Residual overvoltage protection, instance 3 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase undervoltage protection, instance 3 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase overvoltage protection, instance 3 Positive-sequence undervoltage protection, instance 1 IEC 61850 EFPADM1 EFPADM2 EFPADM3 INTRPTEF1 IEC 60617 Yo> -> (1) Yo> -> (2) Yo> -> (3) Io> -> IEF IEC-ANSI 21YN (1) 21YN (2) 21YN (3) 67NIEF
EFHPTOC1
Io>> (1)
51N-2 (1)
NSPTOC1 NSPTOC2 PDNSPTOC1 ROVPTOV1 ROVPTOV2 ROVPTOV3 PHPTUV1 PHPTUV2 PHPTUV3 PHPTOV1 PHPTOV2 PHPTOV3 PSPTUV1
I2> (1) I2> (2) I2/I1> Uo> (1) Uo> (2) Uo> (3) 3U< (1) 3U< (2) 3U< (3) 3U> (1) 3U> (2) 3U> (3) U1< (1)
46 (1) 46 (2) 46PD 59G (1) 59G (2) 59G (3) 27 (1) 27 (2) 27 (3) 59 (1) 59 (2) 59 (3) 47U+ (1)
ABB
87
Table 84. REF615 Functions, codes and symbols, continued Function Negative-sequence overvoltage protection, instance 1 Frequency protection, instance 1 Frequency protection, instance 2 Frequency protection, instance 3 Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Circuit-breaker control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication Auto-reclosing Synchronism and energizing check Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 CBCM TCS (1) TCS (2) MCS 3I CBCM TCM (1) TCM (2) MCS 3I CBXCBR1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 DARREC1 SECRSYN1 I <-> O CB I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES O -> I SYNC I <-> O CB I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES 79 25 IEC 61850 NSPTOV1 FRPFRQ1 FRPFRQ2 FRPFRQ3 T1PTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 IEC 60617 U2> (1) f>/f<,df/dt (1) f>/f<,df/dt (2) f>/f<,df/dt (3) 3Ith>F 3I>/Io>BF 3I2f> Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3) IEC-ANSI 47O- (1) 81 (1) 81 (2) 81 (3) 49F 51BF/51NBF 68 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)
88
ABB
Table 84. REF615 Functions, codes and symbols, continued Function Fuse failure supervision Measurement Disturbance recorder Three-phase current measurement, instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement, including power factor Frequency measurement RDRE1 CMMXU1 CSMSQI1 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 FMMXU1 3I I1, I2, I0 Io 3U Uo U1, U2, U0 P, E f 3I I1, I2, I0 In 3U Vn U1, U2, U0 P, E f IEC 61850 SEQRFUF1 IEC 60617 FUSEF IEC-ANSI 60
ABB
89
90
ABB
91