COMPLIANCE ON COMMENTS ON CMCS STRUTURAL DRAWING

DRAWING NO.

SHEET

S.no.
a. b.

COMMENTS
Arrangement of 4-20' + 3-12' bars in section 1-1 shows only 5 bars. Please indicate the bars clearly. PB6 to be revised as per the modification in architectural drwg. Ladies toilet added, pantry size reduced. Plinth beams to be added accordingly Plinth beam top shall be 750mm below GL as per above comment in sheet 03, to prevent overlapping wth cable trench. Please indicate the lengths of the plinth beams in the schedule of beams. In "NOTES", the statement reg. bearing capacity to be modified. Kindly delete the phrase "to be ascertained before concreting". Plinth beam layout to be corrected for toilet area. FGL location to be indicated in the Section A-A for footing and columns.

c. d e.

5708-004-PVC-C-013

a. 2 b.

5708-004-PVC-C-014

a.

Please indicate the length of the lintel beams in the schedule of beams.

5708-004-PVC-C-015

Please indicate the length of the roof beams in the schedule of beams.