1 of 15
Pressure
0.5000 in. w.c.
TOTAL GAINS ( Sum of positive pressure differentials) TOTAL LOSSES ( Sum of negative pressure differentials) FACTOR OF SAFETY (note: e.g. 10% is to be entered as 1.1) 8 Net available draft: (TOTAL GAINS) - (TOTAL LOSSES) x (FACTOR OF SAFETY): If line 8 is positive the stack is adequate. If line 8 is negative and an I.D. fan is to be used to convert net loss to equivalent loss at 70 deg. F and size I.D. fan accordingly; 9 Conclusion: The Stack is adequate
Stack Adequacy
9/3/2013
169278644.xlsx.ms_office
2 of 15
520 R
Formula Constant 1 Assumed flue gas temp. where breeching joins chimney (Tbc): Assumed flue gas temp. at top of stack (Ts): Average stack flue gas temperature (Te): Flue gas volume rate (1) Boiler:
177,500,000 430 F 370 F 400 F 43 cfs 2,575 cfm 4 (4) Boilers 172 cfs 10,299 cfm
60 GPH 4
USE:
1 boiler 4 boilers
Flue CFM
9/3/2013
169278644.xlsx.ms_office
3 of 15
Flue CFM
9/3/2013
169278644.xlsx.ms_office
4 of 15
Chimney Height
Refer to dwg. Elevations, Original Design, A-8, Sheet 8, Nov. 6,1956 Elev. (ft) Finished Cellar Fl Bottom of Steel Breeching Finished First Fl Finished Second Fl Finished Third Fl Finished Fourth Fl Top of Roof Slab Tof of Penthouse Roof Slab Top of Brick Chimney Chimney total height 44' - 0" 60'-0" 66' - 0"
Height of Chimney (H) Barometric pressure (Bo) Weight of air at 0F and sea level pressure (Wo) Weight of stack gases at 0F and sea level pressure (Wc) Absolute temperature of outside air in worst condition (To) Average stack flue gas temperature (Tc): Weight of gases generated by boiler (W) Coefficient of friction (F) Stack Inside diameter (D) Cross sectional dimensions of stack (W x H) Width: Height:
60 in 60 in
5.00 5.00
9/3/2013
169278644.xlsx.ms_office
5 of 15
ft ft
9/3/2013
169278644.xlsx.ms_office
6 of 15
One boiler
Straight Run location: Type of duct: Breeching equivalent diameter: Straight Duct Length Exhaust gas flow Flue velocity Straight Run Friction Losses: Friction Loss Correction for temperature Correction for roughness Corrected Friction loss Friction Loss:
One boiler
0.015 in. w.c. /100ft 0.74 at 400 deg F 0.98 medium smooth 0.011 in. w.c. /100ft 0.0006 in. w.c.
from Fig.C-9, Calculation notes, GK from Fig.C-5, Calculation notes, GK from Fig.C-3C, Calculation notes, GK
9/3/2013
169278644.xlsx.ms_office
7 of 15
Straight Run location: Type of duct: Breeching equivalent diameter: Straight Duct Length Exhaust gas flow Flue velocity Straight Run Friction Losses: Friction Loss Correction for temperature Correction for roughness Corrected Friction loss Friction Loss:
One boiler
0.017 in. w.c. /100ft 0.7 at 400 deg F 0.98 medium smooth 0.012 in. w.c. /100ft 0.001 in. w.c.
from Fig.C-9, Calculation notes, GK from Fig.C-5, Calculation notes, GK from Fig.C-3C, Calculation notes, GK
Straight Run location: Type of duct: Breeching equivalent diameter: Straight Duct Length Exhaust gas flow Flue velocity Straight Run Friction Losses: Friction Loss Correction for temperature Correction for roughness Corrected Friction loss Friction Loss:
One boiler
0.01 in. w.c. /100ft 0.7 at 400 deg F 0.98 medium smooth 0.007 in. w.c. /100ft 0.0007 in. w.c.
from Fig.C-9, Calculation notes, GK from Fig.C-5, Calculation notes, GK from Fig.C-3C, Calculation notes, GK
9/3/2013
169278644.xlsx.ms_office
8 of 15
Straight Run location: Type of duct: Breeching equivalent diameter: Straight Duct Length Exhaust gas flow Equivalent diameter Flue velocity
Straight Run Friction Losses: Friction Loss Correction for temperature Correction for roughness Corrected Friction loss Friction Loss: 0.01 in. w.c. /100ft 0.7 at 400 deg F 0.98 medium smooth 0.007 in. w.c. /100ft 0.0002 in. w.c. from Fig.C-9, Calculation notes, GK from Fig.C-5, Calculation notes, GK from Fig.C-3C, Calculation notes, GK
9/3/2013
169278644.xlsx.ms_office
9 of 15
32.79 in R (ft) W (ft) 2.50 H (ft) 2.50 R/W 0.000 H/W 1 L/W L (ft)
Rectangular breeching: Exhaust gas flow Equivalent diameter Flue velocity Bend Loss: Elbow Loss Coefficent Velocity Pressure Pressure Loss: Bend location: Type of bend: Breeching equivalent diameter: C Rectangular 0.1
W=
34 in
H=
26 in
32.43 in R (ft) W (ft) 2.83 H (ft) 2.17 R/W H/W L/W 0.000 0.764706 0.176471 L (ft) 0.5
Rectangular breeching: Exhaust gas flow Equivalent diameter Flue velocity Bend Loss: Elbow Loss Coefficent Velocity Pressure Pressure Loss: 1.104
from Table CR3-8, Pag 200, Duct Fitting Loss Coefficient Tables, ASHRAE
Bend Losses
9/3/2013
169278644.xlsx.ms_office
10 of 15
F-G Rectangular W= 50 in H= 28 in
40.48 in R (ft) 5.41 W (ft) 4.17 H (ft) 2.33 H/W (ft) 0.6 R/W (ft) 1.30
Rectangular breeching: Exhaust gas flow Equivalent diameter Flue velocity Bend Loss: Elbow Loss Coefficent Velocity Pressure Pressure Loss:
H Rectangular W= 50 in H= 28 in
40.48 in R (ft) 5.41 W (ft) 4.17 H (ft) 2.33 H/W (ft) 0.6 R/W (ft) 1.30
Rectangular breeching: Exhaust gas flow Equivalent diameter Flue velocity Bend Loss: Elbow Loss Coefficent Velocity Pressure Pressure Loss:
from Table CR3-6, Pag 198, Duct Fitting Loss Coefficient Tables, ASHRAE
Bend Losses
9/3/2013
169278644.xlsx.ms_office
11 of 15
Exhaust gas flow Flue velocity at Do Flue velocity at D1 Transition Friction Losses: Loss Coefficent Velocity Pressure (at D1) Pressure Loss:
9/3/2013
in