earth riser point should be connected between main & sub earth at four corners.
75x12
1000mm
40mm MS rod
1.75x12mm GI flat earth raiser should be connected between main and sub earth at four corners. 2.Additional two more earth electrode at another two corners should be provided. 3.Main earth mat 40mm dia MS rod should be laid 1m away from the wall. 4.Provision of Lightning Arrester in cooling tower and its earthing drawing to be shown. 5.In general practice the treated earth pit to be connected with 40mm MS rod only. 6.Vendor should furnish the sectional view of the equipment earthing point,earthing raiser and earthing details. 7.Vendor should be provide general notes. 8.75x12mm GI flat should be included in the Bill of Material. 9.Please provide typical motor earthing section for clarity.
It should be 2500
It should be 65mm dia GI pipe
100 mm