H 3-PHASE ONLINE UPS TECHNICAL SPECIFICATION

Table 1. 10KVA ~ 60KVA UPS 3-Phase Input / 3-Phase Output KVA RECTIFIER INPUT VOLTAGE INPUT RANGE INPUT FREQUENCY INPUT POWER FACTOR NORMAL INPUT CURRENT(A) MAXIMUM INPUT CURRENT(A) POWER WALK IN EFFICIENCY VOLTAGE REGULATION CURRENT LIMIT(A) RIPPLE VOLTAGE BATTERY BATTERY TYPE NO. OF CELLS VOLTAGE RANGE MAXIMUM CHARGE CURRENT (ADC) BATTERY LOW VOLTAGE BATTERY LOW STOP VOLTAGE BOOST CHARGE FLOAT CHARGE SEAL LEAD ACID / NiCd 174 / 271 295 410VDC / 285-415VDC 5 10 15 20 25 30
220V / 380V / 460V, 208VY / 380VY / 400VY / 415VY +/- 20%V 50 / 60 Hz +/- 5Hz

10

20

30

40

50

60

0.8 18 24 99% 1% 27 0.5% 54 81 108 135 162 36 45 54 68 72 90 90 113 108 136

0% - 100% : 20 sec

320VDC / 305VDC 295VDC / 285VDC 402VDC / 415VDC 390VDC / 410VDC

KVA INVERTER DC INPUT RANGE WAVE FORM OUTPUT VOLTAGE OUTPUT POWER FACTOR VOLTAGE REGULATION 100% UNBALANCE LOAD FREQUENCY LOCK RANGE OUTPUT FREQUENCY (FREE RUNNING) PHASE SHIFT UNDER 100% UNBALANCE LOAD THD (LINEAR LOAD) <110% 110 125% OVERLOAD 125 150% > 150% EFFICIENCY (100% LOAD) MAXIMUM OUTPUT PEAK CURRENT(A) STATIC SWITCH VOLTAGE RANGE FREQUENCY RANGE EFFICIENCY TRANSFER TIME: - MAINS -> INVERTER - INVERTER -> MAINS 100% OVERLOAD 300% ISOLATION WITH OUTPUT

10

20

30

40

50

60

285 420VDC SINUSOID 380 / 400 / 415 VAC 3 Phase 4 Wire 0.8 +/-1% 45 55 Hz / 55 65 Hz 50 / 60 Hz + / - 0.1 Hz 120 % + / - 0.5 <2% CONTINUOUS 15 min 10 min 60 sec 93% 93% 93.5% 93.5% 94% 87 130 174 218 260

93% 43

173 277 VAC (LINE TO NEUTRAL) 45 55 Hz / 55 65 Hz 99.5% 0 ms 0 ms 30 sec 1 sec YES

KVA OVERALL CHARACTERISTICS OVERALL EFFICIENCY OPERATING ENVIRONMENT: - TEMPERATURE - HUMIDITY - ALTITUDE MAXIMUM HEAT DISSIPATION(KW) WEIGHT(Kg) (No Battery) DIMENSION: - HEIGHT(mm) - WIDTH(mm) - DEPTH(mm) - AUDIBLE NOISE STANDARDS: - EN50091-1,-2 - FCC CLASS A PROTECTIONS: - SHORT CIRCUIT - LIGHTNING - EMC FILTER - GALVANIC ISOLATION DATA DISPLAY BY LCD INDICATIONS & ALARMS: - LED,LCD,BUZZER DRY CONTACT BATTERY START

10 91%

20 91%

30

40

50

60 92%

91% 91.5% 92%

0 40 ( 32 104 ) 0% - 90% ( NONCONDENSING ) <1500 M ABOVE SEA LEVEL 0.65 270 1.3 300 1.9 400 2.6 480 3 550 3.5 680

1600 550 800 < 65 dBA (AT 1 m) YES YES RECTIFIER, RESERVE, BYPASS NFB MOV INPUT & OUTPUT BETWEEN INPUT & OUTPUT YES YES YES YES

All specifications mentioned above are subject to change without prior notice.

Table 2. 80KVA ~ 160KVA UPS 3-Phase Input / 3-Phase Output KVA RECTIFIER INPUT VOLTAGE INPUT RANGE INPUT FREQUENCY INPUT POWER FACTOR NORMAL INPUT CURRENT(A) MAXIMUM INPUT CURRENT(A) POWER WALK IN EFFICIENCY VOLTAGE REGULATION CURRENT LIMIT(A) RIPPLE VOLTAGE BATTERY BATTERY TYPE NO. OF CELLS VOLTAGE RANGE MAXIMUM CHARGE CURRENT (ADC) BATTERY LOW VOLTAGE BATTERY LOW STOP VOLTAGE BOOST CHARGE FLOAT CHARGE SEAL LEAD ACID / NiCd 174 / 271 295 410VDC / 285-415VDC 40 50 60 80 216 270 0.5% 144 180 180 225 99% 1% 324 432 380 / 400 / 415VAC 3 Phase 4 Wire 307 520V 50 / 60 Hz +/- 7% 0.8 216 270 288 360 80 100 120 160

0% - 100% : 20 sec

320VDC / 305VDC 295VDC / 285VDC 402VDC / 415VDC 390VDC / 410VDC

KVA INVERTER DC INPUT RANGE WAVE FORM OUTPUT VOLTAGE OUTPUT POWER FACTOR VOLTAGE REGULATION 100% UNBALANCE LOAD FREQUENCY LOCK RANGE OUTPUT FREQUENCY (FREE RUNNING) PHASE SHIFT UNDER 100% UNBALANCE LOAD THD (LINEAR LOAD) <110% 110 125% OVERLOAD 125 150% > 150% EFFICIENCY (100% LOAD) MAXIMUM OUTPUT PEAK CURRENT(A) STATIC SWITCH VOLTAGE RANGE FREQUENCY RANGE EFFICIENCY TRANSFER TIME: - MAINS -> INVERTER - INVERTER -> MAINS 100% OVERLOAD 300% ISOLATION WITH OUTPUT

80

100

120

160

285 420VDC SINUSOID 380 / 400 / 415 VAC 3 Phase 4 Wire 0.8 +/-1% 45 55 Hz / 55 65 Hz 50 / 60 Hz + / - 0.1 Hz 120 % + / - 0.5 <2% CONTINUOUS 15 min 10min 60 sec 94.5% 95% 432 520

94.5% 348

95% 693

173 277 VAC (LINE TO NEUTRAL) 45 55 Hz / 55 65 Hz 99.5% 0 ms 0 ms 30 sec 1 sec YES

KVA OVERALL CHARACTERISTICS OVERALL EFFICIENCY OPERATING ENVIRONMENT: - TEMPERATURE - HUMIDITY - ALTITUDE MAXIMUM HEAT DISSIPATION(KW) WEIGHT(Kg) (No Battery) DIMENSION: - HEIGHT(mm) - WIDTH(mm) - DEPTH(mm) - AUDIBLE NOISE STANDARDS: - EN50091-1,-2 - FCC CLASS A PROTECTIONS: - SHORT CIRCUIT - LIGHTNING - EMC FILTER - GALVANIC ISOLATION DATA DISPLAY BY LCD INDICATIONS & ALARMS: - LED,LCD,BUZZER DRY CONTACT BATTERY START

80 92.5%

100 92.5%

120 93%

160 93%

0 - 40 ( 32 - 104 ) 0% - 90% ( NONCONDENSING ) <1500 M ABOVE SEA LEVEL 4.6 820 5.4 950 6.5 1180 8.7 1450

1600 1100 800 < 65 dBA (AT 1 m) YES YES RECTIFIER, RESERVE, BYPASS NFB MOV INPUT & OUTPUT BETWEEN INPUT & OUTPUT YES YES YES YES

All specifications mentioned above are subject to change without prior notice.

Table 3. 200KVA ~ 320KVA UPS 3-Phase Input / 3-Phase Output KVA RECTIFIER INPUT VOLTAGE INPUT RANGE INPUT FREQUENCY INPUT POWER FACTOR NORMAL INPUT CURRENT(A) MAXIMUM INPUT CURRENT(A) POWER WALK IN EFFICIENCY VOLTAGE REGULATION CURRENT LIMIT(A) RIPPLE VOLTAGE BATTERY BATTERY TYPE NO. OF CELLS VOLTAGE RANGE MAXIMUM CHARGE CURRENT (ADC) BATTERY LOW VOLTAGE BATTERY LOW STOP VOLTAGE BOOST CHARGE FLOAT CHARGE SEAL LEAD ACID / NiCd 174 / 271 295 410VDC / 285-415VDC 100 120 150 160 525 630 0.5% 350 437 420 525 99% 1% 788 840 380 / 400 / 415VAC 3 Phase 4 Wire 307 520V 50 / 60 Hz +/- 7% 0.8 525 656 560 700 200 240 300 320

15% - 100% : 15 sec

320VDC / 305VDC 295VDC / 285VDC 402VDC / 415VDC 390VDC / 410VDC

KVA INVERTER DC INPUT RANGE WAVE FORM OUTPUT VOLTAGE OUTPUT POWER FACTOR VOLTAGE REGULATION 0-100% LOAD FREQUENCY LOCK RANGE OUTPUT FREQUENCY (FREE RUNNING) PHASE DIFFERENCE WITH RESERVE INPUT THD (LINEAR LOAD) <110% OVERLOAD 110 125% 125 150% > 150% EFFICIENCY(100% LOAD) MAXIMUM OUTPUT PEAK CURRENT(A) STATIC SWITCH VOLTAGE RANGE FREQUENCY RANGE EFFICIENCY TRANSFER TIME: - MAINS -> INVERTER - INVERTER -> MAINS OVERLOAD 100% 300%

200

240

300

320

285 420VDC SINUSOID 380 / 400 / 415 V 3 Phase 4 Wire 0.8 +/-1% 45 55 Hz / 55 65 Hz 50 / 60 Hz + / - 0.1 Hz 120+ / - 0.5 <5% CONTINUOUS 15 min 10 min 60 sec 95% 800 95% 1000 95% 1250 95% 1300

173 277 VAC (LINE TO NEUTRAL) 45 55 Hz / 55 65 Hz 99.5% 0 ms 0 ms 30 sec 1 sec YES

ISOLATION WITH OUTPUT

KVA OVERALL CHARACTERISTICS OVERALL EFFICIENCY OPERATING ENVIRONMENT: - TEMPERATURE - HUMIDITY - ALTITUDE MAXIMUM HEAT DISSIPATION(KW) WEIGHT(Kg) (No Battery) DIMENSION: - HEIGHT(mm) - WIDTH(mm) - DEPTH(mm) - AUDIBLE NOISE STANDARDS: -EN50091-12 -FCC CLASS A PROTECTIONS: - SHORT CIRCUIT - LIGHTNING - EMC FILTER - GALVANIC ISOLATION DATA DISPLAY BY LCD INDICATIONS & ALARMS: - LED,LCD,BUZZER DRY CONTACT BATTERY START

200 93%

240 93%

300 93%

320 93%

0 - 40 ( 32 - 104 ) 0% - 90% ( NONCONDENSING ) <1500 M ABOVE SEA LEVEL 11.5 2500 13 2700 16.3 3000 1600 2200 800 < 67 dBA (AT 1 m) YES YES RECTIFIER, RESERVE, BYPASS NFB MOV INPUT & OUTPUT BETWEEN INPUT & OUTPUT YES YES YES YES 17.4 3100

All specifications mentioned above are subject to change without prior notice.