FORM : YSM/YDM-B-CATL-012007

EXCEED EXPECTATIONS, COMPLETE SOLUTIONS

YSM / YDM B SERIES


AIR HANDLING UNITS

YSM / YDM
The modular air handling unit design concept provides the flexibility to meet the rising demand of indoor air quality consisting of a quality range of 23 units with airflows of 1,800 CMH to 57,600 CMH and up to 1,500Pa total static pressure. Our specially extruded aluminum profile posts, plastic injected corners and flush fitting panels and doors give the building designer and occupier a unit of aesthetic and clean lines unsurpassed in the marketplace. All panels can be removed due to Yorks unique locking device achieved by a special aluminum profile and a safety PVC locking strip. The YSM/YDM range can be manufactured to almost any configuration to meet customers requirements. Chilled water and DX cooling coils are manufactured from copper tubes with aluminum, copper or hydrophilic coated fins. Heating can be hot water coil or electric heaters. AESTHETIC APPEARANCE The state of art design of the YSM/YDM model has a smooth continuous surface with no bolts and nuts. The appearance is further enhanced with color bond panel finishing on the outer skin and galvanized steel inner skin as factory standard. RIGIDITY Manufactured from robust extruded aluminum profile, strong plastic injected corner and double skin panel with injected polyurethane foams insulation adding rigidity to the unit.

YSM / YDM
FLEXIBILITY The major components such as fans, cooling coils, heating coils, electric heater, filters etc can be selected as per design requirement to give complete application flexibility. Unit can be delivered as completely assembled or completely knock down. YOUR CHOICE OF BLOWER You have a choice of blower to meet your design and sound power requirement. IAQ DESIGN COMPATABILITY Double skin panel construction allows easy inspection, cleaning and maintenance of the interior surface. Moisture intrusion and microbial growth are inhibited with non-hydroscopic properties of polyurethane foam. CONDENSATE PAN Three-way pitch drain pan design discharges condensate quickly and prevent microbial growth. AIR TIGHTNESS Provided with a combination of rubber gaskets and silicon seals to ensure an air tight construction. EASY ACCESS An ingenious patented system, using aluminum locking profile and a tubular PVC strip, to ensure fastening and dismantling of all panels for service and maintenance. FILTRATION Various options of flat filter and bag filter media available to meet the different air quality requirement.

YSM / YDM SPECIFICATIONS


CONSTRUCTION Extruded, aluminum profile joined by 3D plastic rounded corners, forming the structural frame to house all internal components. Double skin construction is provided by sandwich type 25mm thick panel comprising 0.5mm thick galvanized steel internal skin with color bond external skin and injected with polyurethane foam of 40 kg/m3 density, providing an overall thermal transmission coefficient of K=0.68 W/M2K for 25mm and 50mm thick panel, K=0.34 W/M2K. Sound reduction effect of the panels (measured under test by R = delta L x 10 log S/A, where delta L is the difference in sound pressure level across wall in dB, S is the panel surface in M2 and A the acoustic absorption of the test room in M2.) will not be less than:Mid Frequency (Hz) Reduction Value (dB) for YSM Reduction Value (dB) for YDM 63 7 8 125 13 14 250 18 18 500 28 36 1000 39 45 2000 40 41 4000 43 43

Pre-filters of washable type (75%, 85% or 95% arrestence) or disposable type (95% arrestence) to be arranged in aluminium sliding rails for side removal. Main filters, of bag type with 85% or 95% efficiency and 533.4mm (21) deep housing. The section shall be accessible from either side with access door. Besides, filters such as carbon filter, chemical filter, electronic filter, HEPA filter and roll filter can be offered as option. COILS Cooling and heating coils are manufactured from copper tubes with aluminum fins bonded to the tubes through mechanical expansion and all housed in galvanized steel frames. Headers come with threaded male pipe connections and include drain and vent. Coils shall be tested to 2,400 kPa, with a maximum design operating pressure of 1,700 kPa. Condensate pans will be of the dry pan design to ensure complete condensate removal and made of powder coated galvanized steel with 12mm closed cell insulation. FAN MOTOR ASSEMBLY Fan section shall be fitted with double inlet, double width, forward curved or backward inclined centrifugal fan (air foil as option), depending upon air volume and static pressure requirements. Fan inlets are aerodynamically designed and wheels statically and dynamically balanced according to rated air flow and speed. Bearings range from either sealed for life ball bearings for smaller fans, block type with self aligning ball journals and split pillow blocks with grease points for larger fans. Fan drives (V belt) shall be factory selected and installed to meet the required performances. Motor shall be TEFC type, class F insulation, IP55 protection. Total fan motor assembly shall be installed on a separate base frame supported and isolated from the unit structure by spring or rubber isolators. Flexible connections shall be provided between fan discharge and casing. Options: - Double speed motors (2/4, 4/8, 4/6, 6/8 poles) - Fan inlet vanes and frequency inverter drive for V.A.V applications. - Variable motor voltage and frequency.

Panels are removable from the frame by means of patented locking system made out of an extruded aluminum profile, held in place with one locking strip. This fastening method, together with an enhanced framework gasket ensures air tightness. Unit sections are mounted on a thick galvanized steel bolted base frame, to assure stability and permit easy lifting, handling and positioning on site. Unit with sectional split(s), shall be provided with gaskets and sealing material as well as connection clamps, to permit quick and air tight site assembly. CONTROL DAMPERS Air intake, mixing box dampers have contra-rotating blades (on request parallel operation) with driving shaft for servo-motor operation or level actuator for manual control. The standard galvanized steel blades will turn in counter-action providing a smooth operation requiring no lubrication. FILTRATION Filter sections are provided to house the following options:

YSM / YDM SPECIFICATIONS


OPTIONAL a) COLD BRIDGE FREE DESIGN The frame of the York Air Handling Unit is manufactured with bi-material. Internal structure made of extruded fiberglass frame couple with thermal break property. It was tested up to 8.5C off coil temperature without sweating. Thermal Bridging Factor at class TBI (CEN prEN 1886i1997) b) POSITIVE PRESSURISED SECTION York had come up with a brand new design which is the Positive Pressurized Section to meet the precise environmental demands of high technology processes used in advanced commercial and industrial applications. Positive Pressurized Sections are meant to couple with Yorks AHU after the blower section. Units with Positive Pressurized Section are ideal for clean rooms, clean benches, semiconductor, hospital surgical theatres, food processing, pharmaceuticals, bio tech and chemical industries in which airborne contaminants must be carefully controlled. Positive Pressurized Section is a unique family of Diffuser and HEPA Filter Section. The Diffuser increases the pressure of a fluid by slowing it down and it will help to spread the air evenly to the HEPA Filter. All HEPA Filter are leak tested and are scanned with laser spectrometer with PSL particles to determine the overall efficiency in accordance with IES-RPCCO34-1. There are wide ranges of efficiencies of HEPA Filters available ranging from 99.99% at 0.3 m to 99.999995% at 0.12 m. Casing leakage level (max. leak rate /sm2) rated as class B.

YSM / YDM SPECIFICATIONS


Model YSM/YDM 20 x 20 20 x 30 20 x 40 20 x 50 30 x 30 30 x 40 30 x 50 30 x 60 30 x 70 40 x 40 40 x 50 40 x 60 40 x 70 40 x 80 50 x 50 50 x 60 50 x 70 50 x 80 60 x 60 60 x 70 60 x 80 70 x 70 70 x 80 Coil Area (m2) 0.250 0.424 0.597 0.771 0.741 1.045 1.350 1.654 1.958 1.419 1.831 2.244 2.657 3.069 2.313 2.835 3.356 3.877 3.425 4.055 4.685 4.754 5.492 Estimated Section Weight (kg) 24 24 28 28 28 28 35 35 35 39 39 39 33 33 33 33 41 41 41 41 44 44 44 Air Volume (CMH) 2250 3812 5378 6941 6674 9410 12146 14882 17618 12769 16484 20196 23911 27623 20822 25513 30204 34895 30827 36493 42163 42786 49432 Ext. Pre Filter Section Weight (kg) 10 13 15 18 16 17 22 25 33 22 29 33 40 44 33 36 44 52 50 58 61 60 63 Cooling Capacity (kw) 16 30 42 56 52 69 92 117 134 98 131 161 181 215 165 199 229 270 241 275 326 326 383 Maximum Fan Outlet Area (m2) 0.104 0.163 0.163 0.163 0.257 0.324 0.324 0.324 0.324 0.511 0.642 0.642 0.642 0.642 0.642 0.865 1.014 1.014 1.014 1.277 1.277 1.277 1.277 Bag Filter Section Weight (kg) 33 40 51 60 49 67 72 85 96 77 92 104 119 132 104 121 132 152 138 157 173 176 196 Unit Height (Module) 2 2 2 2 3 3 3 3 3 4 4 4 4 4 5 5 5 5 6 6 6 7 7 Unit Width (Module) 2 3 4 5 3 4 5 6 7 4 5 6 7 8 5 6 7 8 6 7 8 7 8 Extremities Wight (kg) 11 13 16 19 17 22 26 30 35 30 47 52 58 63 44 50 57 63 59 67 74 79 86 Mixing Box Length Weight 'X' (kg) (Module) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 4 4 38 46 57 64 56 70 77 86 99 82 107 118 132 143 139 154 171 185 170 190 205 256 275 Mixing Box with Pre-filter Length 'X' (Module) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 4 4 Weight (kg) 48 59 72 83 72 88 99 112 132 104 137 151 172 187 172 190 215 238 221 248 267 316 338

Model YSM/YDM 20 x 20 20 x 30 20 x 40 20 x 50 30 x 30 30 x 40 30 x 50 30 x 60 30 x 70 40 x 40 40 x 50 40 x 60 40 x 70 40 x 80 50 x 50 50 x 60 50 x 70 50 x 80 60 x 60 60 x 70 60 x 80 70 x 70 70 x 80

Pre & Bag Filter Section Weight (kg) 42 43 67 79 66 84 94 111 129 99 122 137 160 176 137 157 176 205 189 215 236 236 260

Coil Section Weight (kg) 1 Row 26 33 40 47 40 52 57 64 74 58 69 77 88 96 78 88 100 108 97 111 122 124 136 2 Row 29 37 47 55 47 62 71 81 94 72 86 100 114 127 101 116 133 148 132 151 168 171 191 3 Row 31 41 52 62 55 73 84 97 113 86 105 122 141 158 124 144 167 187 166 192 215 220 246 4 Row 34 45 59 70 62 83 97 114 133 101 124 145 168 189 147 172 200 225 201 233 261 267 301 5 Row 36 49 64 78 70 94 111 130 152 115 141 167 194 220 170 210 234 264 235 272 309 267 301 6 Row 39 53 71 85 77 104 125 147 172 128 160 189 221 250 193 229 267 303 269 313 356 361 411 8 Row 44 62 82 101 92 125 151 180 211 157 196 234 273 311 239 286 334 270 337 394 449 457 521 10 Row 49 71 94 116 106 146 129 213 250 185 234 279 327 372 286 343 401 458 407 476 543 552 631

YSM / YDM SPECIFICATIONS

Note : 1. Air Volume is based on face velocity of 2.5 m/s. 2. Cooling capacity is based on air on coil of 26.7CDB/19.4 CWB, chilled water temperature of 6.7/12.2C at 2.5 m/s face velocity. 3. To Calculate Unit Dimension, "Module" = 342mm ie YSM 40 X 60 Height : (4 X 342 + 58 + 100) mm Width : (6 X 342 + 58) mm For YDM 40 X 60

Height : (4 X 342 + 108 + 100) mm Width : (6 X 342 + 108) mm 4. Maximum Shipping Length : 60 Wide Unit = 8 Module Long, > 60 Wide Unit = 6 Module Long. 5. Overall installed length for each section split add 58 mm for YSM and 108 mm for YDM to above dimensions.

YSM / YDM SPECIFICATIONS


Fan Section Model YSM/YDM 20 x 20 20 x 30 Available Fan Size 250 250 280 315 20 x 40 250 280 315 20 x 50 250 280 315 30 x 30 30 x 40 30 x 50 30 x 60 30 x 70 40 x 40 40 x 50 40 x 60 280 315 315 400 450 400 450 400 450 400 450 500 500 560 630 40 x 70 500 560 630 40 x 80 50 x 50 50 x 60 50 x 70 560 630 500 560 630 630 710 800 50 x 80 630 710 800 60 x 60 60 x 70 60 x 80 560 630 710 800 710 800 900 70 x 70 70 x 80 710 800 710 800 900 Fan Discharge Size (mm) 330 330 370 415 330 370 415 330 370 415 370 415 415 520 580 520 580 520 580 520 580 650 650 730 815 650 730 815 730 815 650 730 815 815 910 1020 815 910 1020 730 815 910 1020 910 1020 1145 910 1020 910 1020 1145 Maximum Motor Size (kW) 4 4 7.5 7.5 4 7.5 7.5 4 7.5 7.5 7.5 7.5 7.5 15 15 15 15 15 15 15 15 15 15 22 22 15 22 22 22 22 15 22 22 22 30 30 22 30 30 22 22 30 30 30 30 45 30 30 30 30 45 Motor Mounting Position REAR REAR REAR REAR REAR REAR REAR REAR REAR REAR REAR REAR REAR SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE SIDE R/RI Discharge Length 'Y' (Module) 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 4M 3M 3M 3M 3M 4M 3M 3M 4M 3M 4M 3M 3M 4M 4M 4M 5M 4M 4M 5M 3M 4M 4M 5M 4M 5M 5M 4M 5M 4M 5M 5M Weight (kg) 102 108 151 158 118 161 168 125 168 174 158 165 174 268 286 275 292 284 302 290 295 313 320 415 465 330 425 478 432 487 320 422 474 487 708 816 496 717 827 429 482 717 827 726 838 966 730 843 739 854 943 T/TI Discharge Length 'Y' (Module) 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 3M 4M 3M 3M 3M 4M 4M 3M 4M 4M 4M 4M 3M 4M 4M 4M 5M 5M 4M 5M 5M 4M 4M 5M 5M 5M 5M 6M 5M 5M 5M 5M 6M Weight (kg) 102 108 151 158 118 161 168 125 168 174 158 165 174 268 286 275 292 284 302 290 295 313 320 443 465 330 456 478 465 483 320 452 474 487 741 816 496 752 827 460 482 752 827 763 838 1004 768 843 779 854 1024 Vertical Unit Height Fan + Coil (Module) 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 2M 2M + 3M 2M + 3M 2M + 3M 3M + 3M 3M + 3M 3M + 3M 3M + 3M 3M + 3M 3M + 3M 3M + 4M 3M + 4M 4M + 4M 4M + 4M 4M + 4M 4M + 4M 4M + 4M 4M + 4M 4M + 4M 4M + 4M 4M + 4M -

YSM / YDM SPECIFICATIONS

Jalan Pengapit 15/19, P.O Box 7196, 40706 Slenagor Darul Ehsan Malaysia Copyright by OYL Condair Industries Sdn Bhd 2007. All rights reserved. FORM : YSM/YDM-B-CATL-012007

Subject to change without prior notice