You are on page 1of 5

PROJECT:

20 MW PV SOLAR PLANT AT PHALODI, RAJASTHAN

Sr. No.

Cable
Tag

P1

P2

P3

P4

P5

P6

P7

P8

P9

LT CABLE SCHEDULE
MEPC-1146(A)-T-EN-E-1-CBL-06

From

To

Core Nos.

Location

Equipment

Term.
No.

Location

Equipment

Term.
No.

car port

cluster-1

car port

ACDB

car port

WALK WAY

WALK WAY

WALK WAY

WALK WAY

WALK WAY

WALK WAY

WALK WAY

ACDB

SUB ACDB-1

SUB ACDB-2

SUB ACDB-6

SUB ACDB-5

SUB ACDB-4

SUB ACDB-3

ACDB

car port

WALK WAY

TRANSFO

SUB ACDB-2

WALK WAY

WALK WAY

ACDB

SUB ACDB-5

WALK WAY

WALK WAY

SUB ACDB-4

SUB ACDB-3

R
Y

WALK WAY

WALK WAY

ACDB

TRAFO

Cable Size
(C x Sq. mm)

RUN

MAHINDRA EPC

Length per run Total Length


(Mtr.)
(Mtr.)

Load

Voltage

Kw

kV

Pf

Full load Derating Cable current Design Resistance at 90


Current Factor
Rating
current
deg C

Reactance

Voltage drop

cable
suitability

Amp

Amp

Amp

R (ohm/km)

R (ohm/km)

Id>Ifl

3.5C X 300 AL

350

350

120.000

0.415

0.90

185.5

0.60

371

223

0.128

0.071

3.96%

ok

3.5C X 300 AL

35

140

450.000

0.415

0.90

695.6

0.60

1484

890

0.128

0.071

0.37%

ok

3.5C X 300 AL

275

275

100.000

0.415

0.90

154.6

0.60

371

223

0.128

0.071

2.59%

ok

3.5C X 300 AL

317

634

200.000

0.415

0.90

309.2

0.60

742

445

0.128

0.071

2.99%

ok

3.5C X 300 AL

277

277

100.000

0.415

0.90

154.6

0.60

371

223

0.128

0.071

2.61%

ok

3.5C X 300 AL

275

550

200.000

0.415

0.90

309.2

0.60

742

445

0.128

0.071

2.59%

ok

3.5C X 300 AL

272

815

300.000

0.415

0.90

463.7

0.60

1113

668

0.128

0.071

2.56%

ok

3.5C X 300 AL

218

653

400.000

0.415

0.90

618.3

0.60

1113

668

0.128

0.071

2.74%

ok

3.5C X 300 AL

40

200

600.000

0.415

0.90

927.5

0.60

1855

1113

0.128

0.071

0.45%

ok

SHT. 1 / 5

PROJECT:
20 MW PV SOLAR PLANT AT PHALODI, RAJASTHAN

Sr. No.

Cable
Tag

LT CABLE SCHEDULE
MEPC-1146(A)-T-EN-E-1-CBL-06

From
Location

To
Equipment

Term.
No.

Location

Core Nos.
Equipment

Cable Size
(C x Sq. mm)

RUN

Length per run Total Length


(Mtr.)
(Mtr.)

Term.
No.

SHT. 2 / 5

MAHINDRA EPC

Load

Voltage

Kw

kV

Pf

Full load Derating Cable current Design Resistance at 90


Current Factor
Rating
current
deg C
Amp

Amp

Amp

R (ohm/km)

Reactance

Voltage drop

cable
suitability

R (ohm/km)

Id>Ifl

Sum of Total Length (Mtr.)


Cable Size (C x Sq. mm)
3.5C X 300 AL
Grand Total

Total
3894.3
3894

Size

Current

4C X 50 AL

134

0.82

0.0792

4C X 70 AL

165

0.567

0.0752

4C X 95 AL

198

0.41

0.0734

4C X 185 AL

285

0.21

0.0727

3.5C X 400 AL
3.5C X 300 AL
3.5C X 240 AL
4C X 35 AL
1C X 630 AL

437

0.1

0.0705

371

0.128

0.0711

325

0.151

0.0719

115

1.11

0.0794

666

0.06

0.0843

4C X 4 CU

44

5.9

0.0947

4C X 10 CU

72

2.34

0.0852

4C X 16 AL

73

2.44

0.0815

3C X 4 CU

44

5.9

0.0947

Derating factor
Variation in ground temp
0.91
Group Derating
0.62
Thermal Resistivity
1
Depth of laying
1
Total
0.600

40 deg C
4 cables
150deg C/W
750mm