You are on page 1of 3

PARAMETER Ultimate Tensile Strength (UTS) Overall diameter of Conductor (d) Area of Cross section of Conductor (A) Weight

of Conductor (w) Coefficient of linear Expansion () Youngs Modulus of elasticity (E) Maximum temperature Minimum temperature Everyday temperature Factor of Safety (FOS) (at 27 C) Ground clearance Weight of Conductor per unit area () Equivalent Span (L) : : : : : : : : : : : : : 8810.348 kg 21.9 mm 243 mm2 0.987 kg/m 0.0000189 /C 7700 kg/mm2 80 C 10 C 27 C 5 13.5 m 350 m

Initial Condition Temperature = 27 C Working Tension Working Stress

Loading Factor

Maximum Temperature Condition Temperature = 80 C Loading Factor

Difference of Temperature The working stress is determined by the following formula: [ [ [ ] ] ]

Working Tension Maximum Sag Minimum Temperature Condition Temperature = 10 C Loading Factor

Difference of Temperature The working stress is determined by the following formula: [ [ [ ] ] ]

Working Tension Maximum Sag

No. Equiv. Span (m) 1 250 2 300 3 350 4 400 5 450

Sag (m) 3.84 5.69 7.91 10.50 13.45

10 C Tension (kg) 2009.705 1953.299 1911.928 1881.642 1859.202

Temperature 27 C Sag (m) Tension (kg) 4.38 1762.069 6.31 1762.069 8.58 1762.069 11.21 1762.069 14.20 1762.069

Sag (m) 6.05 8.15 10.57 13.31 16.39

80 C Tension (kg) 1275.709412 1363.413335 1431.500233 1484.938504 1527.335447