TOWER CRANE FOOTING


STRUCTURAL DESIGN REPORT

PROJECT: NORTHGATE RETAIL/OFFICE BUILDINGS

0 Rev.

27-12-2011 Date

A.Z By

F.H Chkd

F.M.I Appr. Status

ISSUED FOR APPROVAL Revision reason for issue description


MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 1 of 13

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

TABLE OF CONTENTS

1.0 1.1 1.2 1.3 1.4 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8

CHAPTER I: GENRALITES ........................................................................................................ 3 OBJECT OF THE PRESENT DOCUMENT ............................................................................ 3 REFERENCE DRAWINGS & DOCUMENTS .......................................................................... 3 REFERENCES AND CODES ................................................................................................. 3 MATERIALS PROPERTIES ................................................................................................... 3 CHAPTER II: DESIGN CALCULATIONS .................................................................................... 5 DESIGN CONCEPT ............................................................................................................... 5 DESIGN LOADS..................................................................................................................... 5 LOADING COMBINATIONS ................................................................................................... 5 GEOMETRY OF CRANE LEGS ............................................................................................. 5 OVER TURNING STABILITY CALCULATIONS ..................................................................... 5 CHECK SLIDING AND SOIL CAPACITY................................................................................ 7 CHECK PUNCHING ............................................................................................................... 8 REINFORCEMENT ................................................................................................................ 8

APPENDIX A 14

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 2 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

1.0 1.1

CHAPTER I: GENRALITES
OBJECT OF THE PRESENT DOCUMENT

The purpose of this document is to provide the final structural analysis and design for the footing related to the tower crane in the considered project (Northgate Retail/Office Buildings).

1.2

REFERENCE DRAWINGS & DOCUMENTS

The following drawings & documents have been used for establishing the final design of the present structure: Foundation reaction forces Data sheet - Page 2-39 - For 52.0m height crane The above data sheets are attached. refer to appendix A. 1.3
REFERENCES AND CODES

The references of codes and standards are: - Qatar Construction Specification 2002 - BS 8110, 1997 Structural use of concrete - Code of practice For design and Construction - BS 8004, 1986 Code of Practice for Foundations - BS449, 2005 steel for the reinforcement of concrete

1.4

MATERIALS PROPERTIES

1.4.1 Concrete Concrete compressive strength (Cube) at 28days : - Blinding Concret - footings C20/25 C32/40 20MPa 40MPa

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 3 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

1.4.2 Reinforcement Steel bars of yield strength not less than 420MPa to be used for longitudinal & transversal bars. This design is for an isolated tower crane foundation. 1.4.3 Soil The allowable bearing capacity was taken 300KN/m2.

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 4 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

2.0 2.1

CHAPTER II: DESIGN CALCULATIONS


DESIGN CONCEPT

2.2

The footing dimensions was estimated based on over turning moment calculations with factor of safty 1.5 Checking for Sliding stability and soil capacity. Checking for Punching shear calculations for required reinforcement

DESIGN LOADS

As per manufacturer data sheet, the most critical design loads were considered for the case of crane in operation as follows: Moment (Over turning) M=4908 KN.m Horizontal force (Sliding) H=91KN gravity Load V=917 KN

2.3

LOADING COMBINATIONS

The given loads are mixed of dead loads, wind loads and live loads. However, a 1.5 ultimate factor can be considered as conservative load factor for concrete design. 2.4
GEOMETRY OF CRANE LEGS

The crane have a base dimensions with square shape of 1.98m side length. The fixing leg of 1.4m length should be embedded with 1.13m inside the footing. This means that the footing should has minimum thickness 1.40m.

2.5

OVER TURNING STABILITY CALCULATIONS

As per the figure below, the stability calculations were calculated as follows:

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 5 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

Figure 1: Stability against over turning

assume h=1.50m ==> over turning moment MOT = 4908+91*1.5 = 5044.5 KN.m footing weight = 25*1.5*L2 = 37.5L2 Stability moment = Mst = 917*L/2 + 37.5*L2*L/2 = 18.75 L3 + 458.5 L Use Factor of safty = F.O.S = 1.5 ==> 1.5=Mst / MOT ==> 18.75 L3 + 458.5 L - 7566.75 = 0 ==> L=6.5 m satisfy the equation.

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 6 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

2.6

CHECK SLIDING AND SOIL CAPACITY

- Sliding: Sliding coefficient is equal =tan where =angle of internal friction ==> 30 = 0.57, Use 0.5 Sliding force = H = 91KN resisting force = (V+W)* = (917+1584.375)*0.50 = 1250.7 >>91, OK - Soil capacity: soil stress = f = (V+W)/A MOT/(L*L2/6) A=footing area=L2 ==> f= 2501.375/42.25 4908/(6.53/6) = 59.2 107.23 Negative value is rejected ==> use another approach. refer to figure 2.

=tan

Figure 2: soil stress calculations

e=MOT/(V+W) = 4908/2501.375 = 1.96 m ==> r=1.29 m 0.5f*(3r)*L = (V+W) ==> 0.5f*3.87*6.5=2501.375 ==> f=198.88 KN/m2 < 300KN/m2, OK
CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 7 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

2.7

CHECK PUNCHING

The fixing leg consists of several steel plates welded to the main shaft. Each plate of 350x350mm dimensions. The maximum force act for punching is considered for the case where the moments is diagonal on the footing. Fpunching = MOT/(2*2.32) +V/4 = 4908/3.25 + 917/4 = 1510.2+229.25=1739.45 KN fs= punching stress directly at plate edge = 1.5*1739450/(4*350*d) where d=footing depth = 1500-65=1435mm ==> fs=1.3MPa << 0.8fcu=5MPa (BS8110-1:1997, clause 3.7.7.2) it is obvious that the punching effect is very negligible.

2.8

REINFORCEMENT

For hign accuracy, the bending moment calculations were performed through finit element analysis. Autodesk ROBOT structural analysis software was used for that purpose. Note that only the large footing was considered (most critical) and the reinforcement was applied to the small one. The acting forces on the crane legs were calculated and applied to the model as follows: Compression side = M/2.3 + V/4 = 4908/2*2.3 + 917/4 = 1067+229.25=1296.25 KN Tension side = M/2.3 - V/4 = 4908/2*2.3 - 917/4 = 1067-229.25 =837.75 KN The fixing leg The following figures represent the footing geometry with acting loads, soil stress (As a verification on the manual calculations) and the service bending moments maps.

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 8 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

Figure 3: acting forces on footing

Figure 4: Soil reaction

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 9 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

Figure 5: Moment on footing

The ultimate bending moment = 347*1.5=520.5 KN.m/m ==> T25@200mm is sufficient as per following data sheet extracted from ROBOT expert software.

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 10 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

Section design for simple bending


1. Assumptions:
Concrete: fcu = 40.0 (MPa)
Code: BS 8110

Reinforcing steel: fy = 420.0 (MPa)

2. Section:

b = 1000.0 (mm) h = 1500.0 (mm) ds = 75.0 (mm) d' = 75.0 (mm)

3. Applied loads:
Mmax (kN*m) at Ultimate Limite State 520.50 Mmin(kN*m) 0.00

4. Results:
Reinforcement: Theoretical area: As = 2264.3 (mm2) Reinforcement ratio: min max Case analysis: Case No 1: ULS M = 520.50 (kN*m) - not significant case = 0.16 (%) = 0.16 (%) = 4.00 (%) A's = 0.0 (mm2)

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 11 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

APPENDIX A (Data sheets)

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 12 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

CLIENT: EQUINOX NORTHGATE SUB CONTRACTOR: UNITED EQUIPMENTS GROUP

CONSULTANT: ASSOCIATED CONSULTING ENGINEERS SUBCONSULTANT TO UNITED: MZ & PARTNERS

MAIN CONTRACTOR: HABTOOR LEIGHTON GROUP MZ Project No: 10109 Rev. 0 Sheet: 13 of 13

Project: Northgate Retail/Office Building


DESIGN CALCULATIONS TOWER CRANE FOOTING

You might also like