You are on page 1of 1

Project:

JEBEL ALI POWER AND DESALINATION


STATION L-PHASE I

Mitsubishi Corporation

INSPECTION AND TEST SHEET


System: 197/350MVA POWER TRANSFORMER
(KKS.No: 72BAT10 )
Title: IMPEDANCE MEASUREMENT
Test sheet No.

Client:
DUBAI ELECTRICITY &
WATER AUTHORITY
Consultant:

Rev.No.

TS-130HX sh.1 of 1

Tested Equipment : 72BAT10 (#2 GT Unit Step Up Transformer)


test : Feb. 13, 2005
Connection
HV-LV
Test results
Frequency
Voltage (V)
(Hz)

1U-1V

1V-1W

52.34

405.74

406.72

Tap 9a

Current (A)

1W-1U
406.4

1U

1V

1W

2.776

2.772

2.765

Average: 406.29

Measured voltage
(406.29V)
Impedance(%)=

420.015.75 kV
Impedance
(%)
350MVA Base
16.04
(Factory result: 16.05)

Average: 2.771

Rated frequency(50Hz) Rated current(481A)

Measured frequency
Measured current
(52.34Hz)
(2.771A)
100
Rated voltage (420000V)

Test circuit
A

1U
f

1N

3ph

V
A

1W

50Hz

Date

Remarks

LAHMEYER:

Date:

2W
1V

3 Ph 380V

Signature:
DEWA:

2U

TSB:

Date:

2V

You might also like