C0498a - SYNERGY DISTRIBUTION BOARD DB-B (MAIN SWICHROOM) REVISION D - 26 SEPTEMBER 2008

C0498a-0012(D).xls

REV
FAULT CURRENT: CHASSIS SIZE: CHASSIS RATING: PHASES: 6kA 72 POLES 250A 3 MAINSWITCH: SUPPLIED FROM: SUPPLY CABLE: 160A NON AUTO ISOLATOR MSB 4C50 A A A A

CIRC
P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18 P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30 P31 P32 P33 P34

PH
1 1 1 1 1 1 1 3 3 1 1 1 1 3 3 1 1 1 1 1 1 3 1 1 1 1 1 3

CIRCUIT BREAKER (amps)


20 20 20 20 20 20 20 20 20 40 20 20 20 20 20 20 20 20 20 20 20 20 20 20 25 20 20

CONTROL EQUIPMENT
RCD RCD RCD RCD RCD

CABLE SIZE ( mm2 )


2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 6.0 2.5 2.5 2.5 2.5 4.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4.0 2.5 4.0

LOCATION
LOWER GROUND B1 UPPER GROUND B2 UPPER GROUND UPPER GROUND LOWER GROUND

CIRCUIT USE
GPOs GPOs FIP GPOs AUTO DOOR GPOs RSD CPS1 - 7.5KW FAN CPS2 - 4KW FAN DB-UPS COMMS RM AC TSG LOBBY GPOs CPS-4 - 1.1KW PUMP PUMP DOL 3KW PUMP DOL 5KW CPS - 4KW FAN CR B PLANT GPOs FUEL PUMPS BLACKWATER PUMP PUMP RM GPOs JACKING PUMP JACKING PUMP HAND DRYER HAND DRYER PUMP A A A A A A A A A A A A A A D A A A A A A A A A A C C D A A A A A A

RCD RCD

LOWER GROUND LOWER GROUND UPPER GROUND UPPER GROUND UPPER GROUND B2 B2 LOWER GROUND LOWER GROUND LOWER GROUND UPPER GROUND UPPER GROUND UPPER GROUND UPPER GROUND LOWER GROUND UPPER GROUND UPPER GROUND

RCD RCD RCD RCD

RCD RCD

C0498a-0012(D).xls

Pages inc. any attach. 1 of 2 ELECTRICAL DESIGN GROUP BRISBANE PTY LTD ACN 092 710 793 TRADING AS ELECTRICAL DESIGN GROUP ABN 96 092 710 793

C0498a - SYNERGY DISTRIBUTION BOARD DB-B (MAIN SWICHROOM) REVISION D - 26 SEPTEMBER 2008

C0498a-0012(D).xls

REV
FAULT CURRENT: CHASSIS SIZE: CHASSIS RATING: PHASES: 6kA 72 POLES 250A 3 MAINSWITCH: SUPPLIED FROM: SUPPLY CABLE: 160A NON AUTO ISOLATOR MSB 4C50 A A A A

CIRC
L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20 L21 L22 L23 L24 L25 L26 L27 L28 L29 L30 L31 L32 L33 L34

PH
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

CIRCUIT BREAKER (amps)


20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

CONTROL EQUIPMENT
24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING PE ON/OFF 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING PB1, PB2, PB3, PB5 & RSD PE1, PB2 & PB3 PE1, PB2 & PB3 PE1 & PB3 PE1 & PB3 PE1 & PB3 REFER LIGHTING CONTROL SCHEDULE PE ON/OFF PE ON/ TC OFF PE1, PB3 & PB4 PE1, PB3 & PB4 PE2 & PB1 24 HOUR LIGHTING LOCAL CONTROL PE ON/ TC OFF PE ON/ TC OFF PE ON/ TC OFF

CABLE SIZE ( mm2 )


2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

LOCATION
GENERAL GENERAL GENERAL GENERAL LOWER GROUND LOWER GROUND LOWER GROUND LOWER GROUND B1 B2 LOWER GROUND LOWER GROUND LOWER GROUND B1 B1 B1 UPPER GROUND EXTERNAL EXTERNAL B2 B2 UPPER GROUND UPPER GROUND GENERAL EXTERNAL EXTERNAL EXTERNAL

CIRCUIT USE
STAIR STAIR STAIR STAIR EXTERNAL 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING 24 HOUR LIGHTING CARPARK LIGHTING CARPARK LIGHTING CARPARK LIGHTING CARPARK LIGHTING CARPARK LIGHTING CARPARK LIGHTING CARPARK LIGHTING EXTERNAL EXTERNAL CARPARK LIGHTING CARPARK LIGHTING CARPARK LIGHTING LIGHTING PLANT ROOM LTS LIGHTING FIN LIGHTS SIGNAGE A A A A A A A A A C A A A A A A A A A A A A A A A A A B A A A A A A

C0498a-0012(D).xls

Pages inc. any attach. 2 of 2 ELECTRICAL DESIGN GROUP BRISBANE PTY LTD ACN 092 710 793 TRADING AS ELECTRICAL DESIGN GROUP ABN 96 092 710 793