You are on page 1of 2

LOC

FINAL STATUTORY INSPECTION REPORT OF 132KV RENIGUNTA -RACHAGUNNERI DC/SC CIRCUIT REMARKS TO BE ATTENDED
Jumpers to be given

3(TND ) 5 6(CP) 12(CP) 13

(A)Vibration dampers not fixed properly (A)Vibration dampers not fixed properly (A). Vibration dampers not fixed properly (A). Vibration dampers not fixed properly (B). Earth bond jumper not provided (C) Cross Arm Bolts and uts missing at leg side 1 (A).Earth bond jumper not fixed . (B). Earth !ire " bolts are not fixed(C)#$ os %tep Bolts missing. 15 (A). Earth !ire " bolts are not fixed(B)Bottom Cross arm bolts and missing at leg side. 16 (A)Earth bond jumper not fixed . (B). Earth !ire " bolts are not fixed 1! (A)Bolts and uts to be !elded(B)Cross arm bolts and nuts missing at leg side (C) tree &utting to be done bet!een lo& #'(#) 1" (A)Copings not done (B) *$ os %tep bolts missing (C) +ree &utting to be done bet!een #)(#, (-)Cross arm bolts and nuts missing at leg side 1# (A) +ree &utting to be done bet!een lo& #,(*$ 2$(CP) (A)Vibration dampers not fixed properly 21 (A)) o %tub Bolts and uts .issing 23 (A)/ne number eem +ree &utting to be done bet!een lo& *0(*1 2! (A) Vibration dampers not fixed properly 2"(CP) (A) Vibration dampers not fixed properly

31(CP) 32 33 3 $ 1 3(CP) (CP) 5(CP) ! 5$(CP) 51 6$(CP) 62(CP)

(A)Copings to be done(B). .iddle phase Ar&ing 2orn are fixed reverse &ondition(C) +ree &utting to be done(.ango tree) (A)Copings to be done (B).iddle x arm bolts and nuts missing (A)Copings to be done(B) Vibration dampers are very near to armour rod. Copings to be done (A)Earth !ire " bolts are not fixed (A)34 angle missing. (A) Vibration dampers not fixed properly (A) Vibration dampers not fixed properly(B)J".3E5% +ightness to be done (A)Vibration dampers not fixed properly(B)J".3E5% +ightness to be done (A).iddle phase Ar&ing 2orn not fitted properly. (A)* o %tub Bolts and uts .issing (A)# o %tub damaged (A)#$ o %tep Bolts .issing(B)# o Bolt .issing in Jumper (A) 6evelling of ex&avation of soil to be done

COMMON REMARKS TO ALL TOWERS :


(#) +/7E5 EA5+2 B/ -% A5E /+ 35/V8-E- +/ A66 %"%3E %8/ +/7E5%. (*)+/7E5 9//+8 : 5E%8%+A CE /+ A558VE-. (0) C/++E5 38 % /+ 35/V8-E- 9/5 2A :E5 5/-% A - 2A5-7A5E% (1);8 C 58C2 3A8 + /+ 35/V8-E- 9/5 7E6-E- 3A5+%.

You might also like