Protection & Control Division

IRIPRO
IRIPRO
IRIPRO
IRIPRO
Series
Over current Protection Relay
-V3 IRIPRO
ltl
lt2
:
:
000.00 A
000.00 A
ltl
lt2
:
:
000.00 A
000.00 A
02
INDEX
Descr|pt|on S.No.
1. lntroduction
2. Features
3. Application
4. Hardware
5. Protection Features
6. Functional Diagram
7. Fault Recording
8. Human Machine lnterface
9. Front Communication
10. Setting Ranges
11. Technical Data
12. Model Description Table
13. Connection Diagram
14. Dimensional Details
15. Panel cut out Details
16. Ordering lnformation
03
1) Introduct|on
lRlPRO Series offers a compact Over-current protection solution for distribution/feeder segment.
lRlPRO Family of protective relays are numeric relays that provides protection and monitoring with reliable and fast
protection solution in a single unit with programmable digital input & outputs.
2) Features
Three phase time over-current protection.
Three phase instantaneous protection.
Earth time over-current and earth instantaneous over current.
Circuit breaker failure detection.
Fault recorder.
Output DO programmable.
USB Communication.
S) App||cat|on
The lRlPRO-v3 relays have been designed for controlling, protecting and monitoring industrial, utility distribution networks and
substations. They can also be used as part of backup protection scheme for feeders, transformers and generators.
4) Hardware
Micro controller based numeric design.
Measures true RMS with DFT filter .
4 Current analog inputs.
3 digital outputs.
Bright LCD Display.
USB communication.
3 Push button on the front for MMl.
6 LEDs for annunciation.
5) Protect|on Features
Three phase time over current protection (51}.
Three phase instantaneous protection (50}.
Earth time over-current (51N}.
Earth instantaneous over-current (50N}.
Circuit breaker failure protection (50BF}
04
(Figure 1)
S) Funct|ona| D|agram
Fault Record 3 Digital Outputs
Aux. Supply
(18-60VDC) or
(80-265V AC/DC)
Front USB
Earth
current
Phase
current
PC/Laptop
3
CBFP
50BF
50BF
50N/
51N
86
50/51 86
COMMUNICATION RECORDS
1
Protect|on Funct|on
Three Phase Over-current Protection (50/51}
The independent two stages are available for phase fault protection. For l> the user may independently select definite time delay or
inverse time delay with different type of curves. The second Hi-Set stage can be configured with definite time only.
Earth Fault Protection (50N/51N}
The independent two stages are available for earth fault protection. For first stage (le>} the user can select definite time delay or
inverse time delay with different type of curves. The second Hi-Set stage can be configured with definite time only.
Relay Latching (86}
Relay can be configured to Latch /Unlatch depending on configuration.
(Latching is possible in presence of Auxiliary supply voltage only}
Circuit Breaker Failure Protection (50 BF}
The CB Failure Protection is based on supervision of phase and earth currents after tripping events. The test criterion is whether all
phase currents have dropped to less than 5% of ln within tCBFP. lf one or more of the phase currents have not dropped to specified
current within this time, CB failure is detected and the assigned output relay is activated.
Reset Delay
This parameter introduces a delay in opening of relay contacts, when the current goes below the drop out value for over load, short
circuit and earth faults. This parameter will not work when manual reset mode is selected.
05
lRlPRO-l records last 10 faults in its non volatile memory with it's time stamp. Each record has the following information:
Fault Format
[F| lL1 : 00.00A
[F| lL2 : 00.00A
[F| lL3 : 00.00A
[F| le : 00.00A
HOUR MlN : HH:MM
SEC mSEC : Sec:mSec
F-TYPE : FAULT TYPE
Where
[F|[lLx| Magnitude of phase current's.
[F|le Magnitude earth fault current's
F-Type Origin of fault (over current, negative phase sequence, etc.} (See Figure 2}
whenever the available memory space is exhausted the new fault automatically over writes the oldest fault. When the
relay trips the description of fault in the feeder will appears on the LCD screen automatically and by pressing 'i'key one
can easily get all the detailed information of that fault.
The user can view the fault record either via the front USB interface software or remotely via the RS-485
communication.(See Figure 2}
7) Fau|t Record|ng
(Figure 2} (Fault Data Recording on PC software}
Keys Manua| Key
is used to manual reset (after pressing for 2 sec} and also works as ENTER key.
is used to scroll in backward direction.
is used to scroll in forward direction.
06
U R R E N T C R O T E C T I O N P
IRIPro-V3
E L A Y R
I>>
Ie>
Ie>>
CBFP
ON
I>
R
R
(Figure 4) (HMI)
The unit has:
1 Front USB port for direct connection to a PC
The entire setting, Fault is available on 'A' type USB (female) interface with saving & printing option. This unit also has Front-end
Live Link simulation support for testing of relay even without any three phase injection source.
9) Front Commun|cat|on
lt comprises of bright LCD display
Two push switches for setting values of normal tripping characteristics and other operations for local access.
One 'RESET/ENTER' push switch.
Six LEDs for Phase Over current, Earth Over current, Fault or Block and event in any phase.
S) Human Mach|ne Interface
No. of digital outputs : 3 (DO1, DO2, DO3}
Type of outputs : Relay
Programmable (DO Assignment} : Yes
Relay reset type : Programmable (Auto/Manual}
Ie>
Ie>>
CBFP
ON
I>
I>>
U R R E N T C R O T E C T I O N P
IRIPro-V3
E L A Y R
R
07
lRlPRO-v3 Setting
Over current and Earth Protection
S. Parameter Display Setting Range Step Default
No Min. Max. Size Setting
1 Phase over-current characteristics P-Char DEFT/ElNv/vlNv DEFT
/LlNv/NlNv1.3/
NlNv3.0/NlNv0.6
2 Earth over-current Characteristics E-Char DEFT/ElNv/vlNv DEFT
/LlNv/NlNv1.3/
NlNv3.0/NlNv0.6
3 Phase over-current low set pickup setting l> 0.20xlp 2.5xlp 0.05xlp EXlT
Phase over-current definite timing t> 0.1 Sec 150 Sec 0.01Sec 0.10 Sec
Phase over-current inverse timing ti> 0.01 1.500 0.005 0.05
4 Phase over-current hi-set pickup setting l>> 0.5xlp 25xlp 0.5xlp EXlT
Phase over-current hi-set definite timing t>> 0.03 Sec 20 Sec 0.01Sec 0.10 Sec
5 **Earth over-current low set pickup setting le> 0.05xln 2.5xln 0.05xln EXlT
Earth over-current low set definite timing te> 0.03 Sec 150 Sec 0.01Sec 0.10 Sec
Earth over-current low set inverse timing tie> 0.01 1.500 0.005 0.05
6 **Earth over-current hi-set pickup setting le>> 0.5xln 15xln 0.05xln EXlT
Earth over-current hi-set definite timing te>> 0.02 Sec 20 Sec 0.01 Sec 0.10 Sec
13.5
very lnverse t= ti [s|
(l / l } - 1
S
80
Extremely lnverse t = ti [s|
2
(l / l } - 1
S
120
Long time lnverse t= ti [s|
(l / l } - 1
S
0.14/0.061/0.028
Normal lnverse 3.0/1.3 /0.6 t = ti [s|
0.02
(l / l } - 1
S

Where t = Tripping time ti = Time multiplier
l = Fault current l = Setting value of current
S
Trip timing Accuracy : DEFT/ vlNv / NlNv 3.0 / 1.3 : +5% OR +30mSec (whichever is higher}
ElNv / NlNv 0.6 / LlNv : +7.5% OR +30mSec (whichever is higher}
10) Sett|ng Ranges
08
DO Reset Mode
S.No. Parameter Display Setting Range Step Default
Min. Max. Size Setting
1 Relay 1 DO1 Auto Manual ----- Auto
2 Relay 2 DO2 Auto Manual ----- Auto
S.No Parameter Display Step Default
Size Setting
1 Phase over-current low set l> --- DO1/DO2/DO3 ---
2 Phase over-current hi-set l>> --- DO1/DO2/DO3 ---
3 Earth over-current low set le> --- DO1/DO2/DO3 ---
4 Earth over-current hi-set le>> --- DO1/DO2/DO3 ---
5 Self supervision SELF SUP --- DO1/DO2/DO3 ---
S.No Parameter Display Setting Range Step Default
Min. Max. Size Setting
1 Enable CBFP Enable NO YES - NO
2 CBFP tCBFP 0.05 Sec 2 Sec - 0.05 Sec
DO Assignment *
Circuit Breaker Failure Protection
General Setting: (These are the settings common for all protections}
S.No. Parameter Display Setting Range Step Default
Min. Max. Size Setting
1. Phase CT ratio PCTRATlO 1 9999 1 1
2. Earth CT ratio ECTRATlO 1 9999 1 1
3. Reset Delay ResetDly 0 20 Sec 0.1 Sec 1 Sec
USB Commun|cat|on
Protocol : CSE proprietary protocol: available with front software
Cable required for interface : USB cable type (A to A}
09
Rated Auxiliary voltage UH 18-60v DC or 80-265v AC/DC
Power consumption Quiescent approx. 3W operating <7W
Auxiliary Supply
S.No Quantity Range Frequency Range Accuracy
1 Current 0.2 - 20 x lp 50 - 60 Hz +2%
Measurement Accuracy
Rated Data Rated current lp :1A or 5A
Rated frequency Fn : 50 Hz
Drop out to Pickup Ratio >96%
Power consumption in current circuit At lp=1A 0.2 vA
At lp=5A 0.4 vA
Thermal withstand capability in
current circuit Dynamic current withstand
(half wave}: 250 x lp
for 1 Sec : 100 x lp
for 10 Sec : 30 x lp
continuously : 4 x lp
Protection-Front Panel lP-54
Weight Approx. 1.0 Kg
11) Techn|ca| Data
Measur|ng Inputs
12) Mode| Descr|pt|on Tab|e
Function lRlPRO-v3
CT lnputs 4
Over Current (50/51}
Earth Fault (50N/51N}
CBFP (50BF}
Digital Output 3
Fault Record 10
Selection of 1/5A Ordering information
Enclosure Type Non Draw-out
Enclosure Size (WxHxD} (144x76x185} mm
Front Communication
Terminal Connection Details
1S) Connect|on D|agram
IRIPRO-V3
10
(Figure 5}
L1
L2
L3
P1 S1 A1 L1.1
L1
A2 L1.2
P2 S2
A3 L2.1
L2
A4 L2.2
P1 S1
P2 S2
A5 L3.1
L3
A6 L3.2
P1 S1
P2 S2
A7 N2
Ie
A8 N1
Power Supply
B9 B8 B7
+ -
CB Trip Relay
B5
B6
Relay 2
B3
B4
Relay 1
B1
B2
14) D|mens|ona| Deta||s
11
22
Front view
Top view
Side view
(Figure 6)
(Figure 7)
(Figure 8)
15) Pane| Cut out Deta||s
12
22
Horizontal Relay
vertical Relay
Panel cutout dimensions
137.5 mm
6
9
.
5

m
m
Panel cutout
dimensions
1
3
7
.
5

m
m
69.5 mm
1S) Order|ng Informat|on
13
IRIPRO-VS-EO-H-L-1-1 Examp|e:
lRlPRO-v3- XXXXX X X X X
MODEL NO.
EO : Earth Fault with Hi-set
3l-El : 3 Over Current with Earth fault
ENCLOSURE TYPE
H : Horizontal
v : vertical
PHASE RATED
EARTH RATED
1A
1A
5A
5A
AUXlLlARY SUPPLY
L : 18-60v DC
H : 80-265v AC/DC
Rev.No.: 00, Rev. Date: 05.08.10, Issue Date: 05.08.10
Branch office
E-mail
+91 79 30074519 cspc.ahmedabad@cselectric.co.in
+91 2558 4839 cspc.bangalore@cselectric.co.in
+91 674 2507265 cspc.bhubaneswar@cselectric.co.in
+91 44 39180514 cspc.chennai@cselectric.co.in
+91 0484 3071716 cspc.cochin@cselectric.co.in
+91 11 30838826 cspc.delhi@cselectric.co.in
+91 40 3910 3631 cspc.hyderabad@cselectric.co.in
+91 33 2227 5849 cspc.kolkata@cselectric.co.in
+91 22 2412 6631 cspc.mumbai@cselectric.co.in
+91 20 30283244 cspc.pune@cselectric.co.in
44, Okhla lndustrial Estate, Phase -lll, New Delhi -110 020 (lNDlA}
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 6660 2413 E-mail: cspc@cselectric.co.in
C&S Electric Ltd.
F o r F u r t h e r i n f o r ma t i o n , Pl e a s e c o n t a c t :
Rev.No: 05
Rev. Date: 31.01.13
lssue Date: 30.3.12
Fax
+91 79 30074534/35/36
+91 80 3057 0372/73, 3057 0347
+91 44 3918 0531-35
+91 0484 3071717
+91 11 30838822-25
+91 40 3918 2496/97
+91 33 22275850/51
+91 22 30487146/47/48
+91 20 30283244/45
Branch Phone
Ahmedabad:
Bangalore:
Bhubaneswar: +91 674 2507265
Chennai:
Cochin:
Delhi:
Hyderabad:
Kolkata:
Mumbai:
Pune:

You might also like