Protection Co-ordination

Report
Electrical Distribution System
Salem Works
Report Compiled by:
Interface Electronics Pvt Ltd,Chennai
Email:ife@vsnl.com website:www.ifepwrana.com
Mobile no:9884370326
MI STEEL PROCESSING INDIA PVT LTD
Sl.No Descriptiion Page No
1 Executive Summary 3
2 Reference Documents 4
3 Device Details 5
4 Single Line Diagram 6
5 Short Circuit Report 7
6 Transformer Relay Setting Calculations 17
7 DG set Relay setting Calculation 18
8 Stabilising Restance Calculations for DG set 19
9 Stabilising Restance Calculations for Transformer 20
10 Setting Details for 11 kV Panels 21
11 Setting Details for MPCP and other Sub Panels 25
12 Time Current Characteristic Curves 35
13 Comments 38
Contents
Introduction
Project: MI STEEL PROCESSING INDIA PVT LTD
VENBAKKAM,VARANAVASAI VILLAGE,Kanchipuram dt,Tamilnadu
Main Contractor: M/s Fujita Corporation,
3 First floor,3 rd East street,
Thiruvanmyur,Chennai
Electrical Contractor: Triggo Tech Engineering,
2A/13,First Floor,
2nd street,Mudihur Road,
West Tambaram,Chennai 45
Architect: C R Narayana Rao,
#10,Karpagambal nagar,
Mylapore,Chennai
ElectricalDistribution System 11kV at Point of supply and distribution at 0.415 kV
Power System Data
Max Source Fault level (assumed) 500 MVA sec
Min Source Fault level (assumed)
250 MVA sec
Tools used: Paladin Design Base 5- an Electrical Design software
Protection Coordination
The short circuit currents at various busbars are calculated based on the above
assumptions. Calculated Short circuit currents are tabulated in the report and also
shown in the SLD.
Selectivity of relays and circuit breakers were worked out based on the cable size
and flow of short circuit currents.
Time current characterstic curves are generated for every path and verified .
Executive Summary
The short circuit currents at various busbars are calculated based on the above
assumptions. Calculated Short circuit currents are tabulated in the report and also
shown in the SLD.
Selectivity of relays and circuit breakers were worked out based on the cable size
and flow of short circuit currents.
Time current characterstic curves are generated for every path and verified .
Conclusion
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages. While doing this
exercise certain discrepencies were noticed and these are brought out seperately
under heading 'Comments and Observations'.
Sl.No Document Title File reference Document No
1 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM.DWG TRIGGO-MISP1-CEIG-O3-R1
2 CABLE SCHEDULE CABLE SCHEDULE-MISIPI.XLS
3 Covering sheet Main Power Control Panel SH1-12 LT PANEL GA DRWING.DWG VMCL/045/13-14
4 Covering sheet MPDB SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
5 Covering sheet PUMP PANEL SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
6 Covering sheet MLDB SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
7 Covering sheet PP-COMP SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
8 Covering sheet OFFICE AREA PANEL SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
9 Covering sheet CRANE PANEL SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
10 Covering sheet LEVELLER PANEL SH1-8 LT PANEL GA DRWING.DWG VMCL/045/13-14
11 Covering sheet APFC SH1-14 APFC PANEL.DWG VMCL/045/13-14
12 Covering sheet 11KV-630A OUTDOOR VCB PANEL HTPANEL STRUCTURE.PDF VMCL/045/13-14
13 Covering sheet 11KV-630A OUTDOOR VCB PANEL HTPANEL SUBSTATION.PDF VMCL/045/13-14
Reference Documents / Drawings
Details of Equipment kVA rating High
Voltage
side
Low voltage
side
Percentage
Impedance
Low
winding
High
winding
Grounding
Mode
Vector
Group
Type of
Cooling
Supply Variation on
Primary side
Transformer 1 1600 11000 433 6.25 Star Delta Direct Dyn11 ONAN -5% to +5% tapping
Details of Equipment kVA rating Output
Voltage
Sub transient
Reactance
DG1 1010 415 V 9%
Starting
Electric Manual
Device Details
2-Winding Transformers
Diesel Generating Set
DWG SIZE: SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: 17/04/2014 REV. DWG No.:
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
REV. DATE ECO# DWN APP DESCRIPTION
GRID
TNEB_SOURCE
Vs: 11000 V
CAB:SOURCE
TR1
HV_SP1
CAB:SP1_SP2
HV_SP2
B
U
S
D
U
C
T
_
T
R
MPCP_IC1
MPCP
Vs: 415 V
CAB:SP2_TR
GEN
DG
Vs: 433 V
MPCP_IC2
BUSDUCT_DG
MPCP_IC3
BUSDUCT_mp
MPCP_OG1
CAB:APFC
APFC
Vs: 415 V
APFC_IC
MPCP_OG2
CAB:Crane
CRANE_IC
MPCP_OG3
CAB:MPDB
MPDB_IC
MPCP_OG4
CAB:Leveller
LEVELLER_IC
MPCP_OG5
CAB:pump pnl
PUMP PNL_IC
MPCP_OG6
CAB:WM
WM_IC
MPCP_OG7
CAB:Turnover
TURNOVER_IC
MPCP_OG8
CAB:mldb
MLDB_IC
MPCP_OG9
CAB:PP comp
COMP_IC
MPCP_OG10
CAB:BL1
BL1_IC
MPCP_OG11
CAB:BL2
BL2_IC
MPCP_OG12
CAB:OFFICE
OFFICE_IC
SP1 SP3
Crane Panel
Vs: 415 V
PP_MPDB
Vs: 415 V
LEVELLER PNL
Vs: 415 V
PP_PUMP PNL
Vs: 415 V
WASHING M/C
Vs: 415 V
TURNOVER EQUP PNL
Vs: 415 V
PP_MLDB
Vs: 415 V
PP_COMP
Vs: 415 V
BL_PNL1
Vs: 415 V
BL_PNL2
Vs: 415 V
OFFICE AREA
Vs: 415 V
SP 2
PUMP PNL_OG1
CAB:STP PNL
STP PNL_IC
STP PNL
Vs: 415 V
PUMP PNL_OG2
CAB:WTP PNL
WTP PNL_IC
WTP PNL
Vs: 415 V
MPDB_OG1
CAB:PDB
PDB_IC
PDB
Vs: 415 V
Short Circuit Current Details
DWG SIZE: SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: 17/04/2014 REV. DWG No.:
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
REV. DATE ECO# DWN APP DESCRIPTION
SINGLE LINE DIAGRAM
SHORT CIRCUIT CURRENTS-MAXIMUM
SOURCE FAULT-TNEB
GRID
TNEB_SOURCE
Vs: 11000 V
Ik" : 26243.19A
CAB:SOURCE
TR1
HV_SP1
CAB:SP1_SP2
HV_SP2
B
U
S
D
U
C
T
_
T
R
MPCP_IC1
MPCP
Vs: 415 V
Ik" : 33338.02A
CAB:SP2_TR
GEN
DG
Vs: 433 V
MPCP_IC2
BUSDUCT_DG
MPCP_IC3
BUSDUCT_mp
MPCP_OG1
CAB:APFC
APFC
Vs: 415 V
Ik" : 30974.07A
APFC_IC
MPCP_OG2
CAB:Crane
CRANE_IC
MPCP_OG3
CAB:MPDB
MPDB_IC
MPCP_OG4
CAB:Leveller
LEVELLER_IC
MPCP_OG5
CAB:pump pnl
PUMP PNL_IC
MPCP_OG6
CAB:WM
WM_IC
MPCP_OG7
CAB:Turnover
TURNOVER_IC
MPCP_OG8
CAB:mldb
MLDB_IC
MPCP_OG9
CAB:PP comp
COMP_IC
MPCP_OG10
CAB:BL1
BL1_IC
MPCP_OG11
CAB:BL2
BL2_IC
MPCP_OG12
CAB:OFFICE
OFFICE_IC
SP1 SP3
Crane Panel
Vs: 415 V
Ik" : 15865.3A
PP_MPDB
Vs: 415 V
Ik" : 29054.58A
LEVELLER PNL
Vs: 415 V
Ik" : 12692.88A
PP_PUMP PNL
Vs: 415 V
Ik" : 18796.16A
WASHING M/C
Vs: 415 V
Ik" : 17941.08A
TURNOVER EQUP PNL
Vs: 415 V
Ik" : 16835.94A
PP_MLDB
Vs: 415 V
Ik" : 15758.9A
PP_COMP
Vs: 415 V
Ik" : 16980.14A
BL_PNL1
Vs: 415 V
Ik" : 13096.7A
BL_PNL2
Vs: 415 V
Ik" : 10046.51A
OFFICE AREA
Vs: 415 V
Ik" : 22564.56A
SP 2
PUMP PNL_OG1
CAB:STP PNL
STP PNL_IC
STP PNL
Vs: 415 V
Ik" : 3582.05A
PUMP PNL_OG2
CAB:WTP PNL
WTP PNL_IC
WTP PNL
Vs: 415 V
Ik" : 3582.05A
MPDB_OG1
CAB:PDB
PDB_IC
PDB
Vs: 415 V
Ik" : 1487.92A
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 68832 26243 26243 26243 26243 26243 26243
MPCP 415 73415 33338 33338 33338 33338 33338 33338
APFC 415 63417 30974 30974 30974 30974 30974 30974
PP_MPDB 415 57164 29055 29055 29055 29055 29055 29055
OFFICE AREA 415 34491 22565 22565 22565 22565 22565 22565
PP_PUMP PNL 415 31550 18796 18796 18796 18796 18796 18796
WASHING M/C 415 28752 17941 17941 17941 17941 17941 17941
PP_COMP 415 26217 16980 16980 16980 16980 16980 16980
TURNOVER EQUP PNL 415 25956 16836 16836 16836 16836 16836 16836
Crane Panel 415 25782 15865 15865 15865 15865 15865 15865
PP_MLDB 415 24048 15759 15759 15759 15759 15759 15759
LEVELLER PNL 415 20019 12693 12693 12693 12693 12693 12693
BL_PNL1 415 19559 13097 13097 13097 13097 13097 13097
BL_PNL2 415 14358 10047 10047 10047 10047 10047 10047
STP PNL 415 5066 3582 3582 3582 3582 3582 3582
WTP PNL 415 5066 3582 3582 3582 3582 3582 3582
PDB 415 2104 1488 1488 1488 1488 1488 1488
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
Short Circuit Detailed Report - TNEB source fault 500 MVA sec
3P Fault - IEC60909 Method
LL Fault - IEC60909 Method
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 68832 26243 26243 26243 26243 26243 26243
MPCP 415 63922 29056 29056 29056 29056 29056 29056
APFC 415 55175 26982 26982 26982 26982 26982 26982
PP_MPDB 415 49712 25299 25299 25299 25299 25299 25299
OFFICE AREA 415 29946 19611 19611 19611 19611 19611 19611
PP_PUMP PNL 415 27386 16331 16331 16331 16331 16331 16331
WASHING M/C 415 24952 15584 15584 15584 15584 15584 15584
PP_COMP 415 22748 14745 14745 14745 14745 14745 14745
TURNOVER EQUP PNL 415 22522 14619 14619 14619 14619 14619 14619
Crane Panel 415 22370 13777 13777 13777 13777 13777 13777
PP_MLDB 415 20863 13681 13681 13681 13681 13681 13681
LEVELLER PNL 415 17363 11015 11015 11015 11015 11015 11015
BL_PNL1 415 16963 11364 11364 11364 11364 11364 11364
BL_PNL2 415 12447 8711 8711 8711 8711 8711 8711
STP PNL 415 4388 3103 3103 3103 3103 3103 3103
WTP PNL 415 4388 3103 3103 3103 3103 3103 3103
PDB 415 1822 1289 1289 1289 1289 1289 1289
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 68832 26243 26243 26243 26243 26243 26243
MPCP 415 79139 36269 36269 36269 36269 36269 36269
APFC 415 60624 30774 30774 30774 30774 30774 30774
PP_MPDB 415 50380 26883 26883 26883 26883 26883 26883
OFFICE AREA 415 34164 21606 21606 21606 21606 21606 21606
PP_PUMP PNL 415 21101 12890 12890 12890 12890 12890 12890
WASHING M/C 415 20367 12692 12692 12692 12692 12692 12692
PP_COMP 415 19609 12456 12456 12456 12456 12456 12456
TURNOVER EQUP PNL 415 19380 12323 12323 12323 12323 12323 12323
PP_MLDB 415 17724 11349 11349 11349 11349 11349 11349
Crane Panel 415 16354 10187 10187 10187 10187 10187 10187
BL_PNL1 415 13991 9094 9094 9094 9094 9094 9094
LEVELLER PNL 415 12073 7647 7647 7647 7647 7647 7647
BL_PNL2 415 11890 8063 8063 8063 8063 8063 8063
STP PNL 415 5570 3931 3931 3931 3931 3931 3931
WTP PNL 415 5570 3931 3931 3931 3931 3931 3931
PDB 415 2967 2098 2098 2098 2098 2098 2098
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
Short Circuit Detailed Report - TNEB source fault 500 MVA sec (Contd)
LG Fault - IEC60909 Method
LLG Fault - IEC60909 Method
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 71359 27206 27206 27206 27206 27206 27206
MPCP 415 77169 35233 35233 35233 35233 35233 35233
APFC 415 63928 31819 31819 31819 31819 31819 31819
PP_MPDB 415 56198 29155 29155 29155 29155 29155 29155
OFFICE AREA 415 36364 23463 23463 23463 23463 23463 23463
PP_PUMP PNL 415 28874 17310 17310 17310 17310 17310 17310
WASHING M/C 415 26218 16362 16362 16362 16362 16362 16362
PP_COMP 415 24600 15864 15864 15864 15864 15864 15864
TURNOVER EQUP PNL 415 24362 15732 15732 15732 15732 15732 15732
Crane Panel 415 23294 14376 14376 14376 14376 14376 14376
PP_MLDB 415 22614 14746 14746 14746 14746 14746 14746
BL_PNL1 415 18480 12303 12303 12303 12303 12303 12303
LEVELLER PNL 415 17914 11360 11360 11360 11360 11360 11360
BL_PNL2 415 14651 10187 10187 10187 10187 10187 10187
STP PNL 415 6251 4418 4418 4418 4418 4418 4418
WTP PNL 415 6251 4418 4418 4418 4418 4418 4418
PDB 415 3407 2409 2409 2409 2409 2409 2409
DWG SIZE: SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: 17/04/2014 REV. DWG No.:
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
REV. DATE ECO# DWN APP DESCRIPTION
SINGLE LINE DIAGRAM
SHORT CIRCUIT CURRENTS-MINIMUM
SOURCE FAULT-TNEB
GRID
TNEB_SOURCE
Vs: 11000 V
Ik" : 13121.6A
CAB:SOURCE
TR1
HV_SP1
CAB:SP1_SP2
HV_SP2
B
U
S
D
U
C
T
_
T
R
MPCP_IC1
MPCP
Vs: 415 V
Ik" : 31825.78A
CAB:SP2_TR
GEN
DG
Vs: 433 V
MPCP_IC2
BUSDUCT_DG
MPCP_IC3
BUSDUCT_mp
MPCP_OG1
CAB:APFC
APFC
Vs: 415 V
Ik" : 29677.9A
APFC_IC
MPCP_OG2
CAB:Crane
CRANE_IC
MPCP_OG3
CAB:MPDB
MPDB_IC
MPCP_OG4
CAB:Leveller
LEVELLER_IC
MPCP_OG5
CAB:pump pnl
PUMP PNL_IC
MPCP_OG6
CAB:WM
WM_IC
MPCP_OG7
CAB:Turnover
TURNOVER_IC
MPCP_OG8
CAB:mldb
MLDB_IC
MPCP_OG9
CAB:PP comp
COMP_IC
MPCP_OG10
CAB:BL1
BL1_IC
MPCP_OG11
CAB:BL2
BL2_IC
MPCP_OG12
CAB:OFFICE
OFFICE_IC
SP1 SP3
Crane Panel
Vs: 415 V
Ik" : 15552.21A
PP_MPDB
Vs: 415 V
Ik" : 27920.57A
LEVELLER PNL
Vs: 415 V
Ik" : 12498.19A
PP_PUMP PNL
Vs: 415 V
Ik" : 18346.53A
WASHING M/C
Vs: 415 V
Ik" : 17547.04A
TURNOVER EQUP PNL
Vs: 415 V
Ik" : 16505.52A
PP_MLDB
Vs: 415 V
Ik" : 15474.17A
PP_COMP
Vs: 415 V
Ik" : 16643.31A
BL_PNL1
Vs: 415 V
Ik" : 12908.71A
BL_PNL2
Vs: 415 V
Ik" : 9958.35A
OFFICE AREA
Vs: 415 V
Ik" : 21982.48A
SP 2
PUMP PNL_OG1
CAB:STP PNL
STP PNL_IC
STP PNL
Vs: 415 V
Ik" : 3576.51A
PUMP PNL_OG2
CAB:WTP PNL
WTP PNL_IC
WTP PNL
Vs: 415 V
Ik" : 3576.51A
MPDB_OG1
CAB:PDB
PDB_IC
PDB
Vs: 415 V
Ik" : 1487.52A
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 34416 13122 13122 13122 13122 13122 13122
MPCP 415 70588 31826 31826 31826 31826 31826 31826
APFC 415 61304 29678 29678 29678 29678 29678 29678
PP_MPDB 415 55444 27921 27921 27921 27921 27921 27921
OFFICE AREA 415 33849 21982 21982 21982 21982 21982 21982
PP_PUMP PNL 415 31019 18347 18347 18347 18347 18347 18347
WASHING M/C 415 28308 17547 17547 17547 17547 17547 17547
PP_COMP 415 25845 16643 16643 16643 16643 16643 16643
TURNOVER EQUP PNL 415 25592 16506 16506 16506 16506 16506 16506
Crane Panel 415 25426 15552 15552 15552 15552 15552 15552
PP_MLDB 415 23734 15474 15474 15474 15474 15474 15474
LEVELLER PNL 415 19802 12498 12498 12498 12498 12498 12498
BL_PNL1 415 19350 12909 12909 12909 12909 12909 12909
BL_PNL2 415 14249 9958 9958 9958 9958 9958 9958
STP PNL 415 5058 3577 3577 3577 3577 3577 3577
WTP PNL 415 5058 3577 3577 3577 3577 3577 3577
PDB 415 2104 1488 1488 1488 1488 1488 1488
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
Short Circuit Detailed Report - TNEB source fault 250MVA sec
3P Fault - IEC60909 Method
LL Fault - IEC60909 Method
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 34416 13122 13122 13122 13122 13122 13122
MPCP 415 61768 27901 27901 27901 27901 27901 27901
APFC 415 53569 25993 25993 25993 25993 25993 25993
PP_MPDB 415 48406 24436 24436 24436 24436 24436 24436
OFFICE AREA 415 29461 19171 19171 19171 19171 19171 19171
PP_PUMP PNL 415 26985 15991 15991 15991 15991 15991 15991
WASHING M/C 415 24617 15286 15286 15286 15286 15286 15286
PP_COMP 415 22467 14491 14491 14491 14491 14491 14491
TURNOVER EQUP PNL 415 22247 14370 14370 14370 14370 14370 14370
Crane Panel 415 22101 13540 13540 13540 13540 13540 13540
PP_MLDB 415 20627 13466 13466 13466 13466 13466 13466
LEVELLER PNL 415 17199 10869 10869 10869 10869 10869 10869
BL_PNL1 415 16806 11223 11223 11223 11223 11223 11223
BL_PNL2 415 12365 8645 8645 8645 8645 8645 8645
STP PNL 415 4382 3099 3099 3099 3099 3099 3099
WTP PNL 415 4382 3099 3099 3099 3099 3099 3099
PDB 415 1822 1288 1288 1288 1288 1288 1288
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 34416 13122 13122 13122 13122 13122 13122
MPCP 415 77215 35219 35219 35219 35219 35219 35219
APFC 415 59495 30028 30028 30028 30028 30028 30028
PP_MPDB 415 49599 26320 26320 26320 26320 26320 26320
OFFICE AREA 415 33800 21280 21280 21280 21280 21280 21280
PP_PUMP PNL 415 20962 12769 12769 12769 12769 12769 12769
WASHING M/C 415 20238 12577 12577 12577 12577 12577 12577
PP_COMP 415 19488 12348 12348 12348 12348 12348 12348
TURNOVER EQUP PNL 415 19262 12217 12217 12217 12217 12217 12217
PP_MLDB 415 17626 11260 11260 11260 11260 11260 11260
Crane Panel 415 16270 10113 10113 10113 10113 10113 10113
BL_PNL1 415 13929 9038 9038 9038 9038 9038 9038
LEVELLER PNL 415 12027 7606 7606 7606 7606 7606 7606
BL_PNL2 415 11845 8023 8023 8023 8023 8023 8023
STP PNL 415 5562 3925 3925 3925 3925 3925 3925
WTP PNL 415 5562 3925 3925 3925 3925 3925 3925
PDB 415 2966 2098 2098 2098 2098 2098 2098
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
Short Circuit Detailed Report - TNEB source fault 250MVA sec (Contd)
LG Fault - IEC60909 Method
LLG Fault - IEC60909 Method
Bus Name Pre Fault
Voltage
Peak Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
TNEB_SOURCE 11000 35679 13603 13603 13603 13603 13603 13603
MPCP 415 74940 34020 34020 34020 34020 34020 34020
APFC 415 62333 30813 30813 30813 30813 30813 30813
PP_MPDB 415 54926 28295 28295 28295 28295 28295 28295
OFFICE AREA 415 35712 22895 22895 22895 22895 22895 22895
PP_PUMP PNL 415 28509 16995 16995 16995 16995 16995 16995
WASHING M/C 415 25816 16025 16025 16025 16025 16025 16025
PP_COMP 415 24253 15566 15566 15566 15566 15566 15566
TURNOVER EQUP PNL 415 24022 15440 15440 15440 15440 15440 15440
Crane Panel 415 23054 14160 14160 14160 14160 14160 14160
PP_MLDB 415 22320 14492 14492 14492 14492 14492 14492
BL_PNL1 415 18284 12133 12133 12133 12133 12133 12133
LEVELLER PNL 415 17722 11197 11197 11197 11197 11197 11197
BL_PNL2 415 14539 10096 10096 10096 10096 10096 10096
STP PNL 415 6238 4409 4409 4409 4409 4409 4409
WTP PNL 415 6238 4409 4409 4409 4409 4409 4409
PDB 415 3405 2408 2408 2408 2408 2408 2408
DWG SIZE: SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: 17/04/2014 REV. DWG No.:
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
REV. DATE ECO# DWN APP DESCRIPTION
SINGLE LINE DIAGRAM
SHORT CIRCUIT CURRENTS-DG SOURCE
GRID
TNEB_SOURCE
Vs: 11000 V
CAB:SOURCE
TR1
HV_SP1
CAB:SP1_SP2
HV_SP2
B
U
S
D
U
C
T
_
T
R
MPCP_IC1
MPCP
Vs: 415 V
Ik" : 16182.84A
CAB:SP2_TR
GEN
DG
Vs: 433 V
Ik" : 15662.58A
MPCP_IC2
BUSDUCT_DG
MPCP_IC3
BUSDUCT_mp
MPCP_OG1
CAB:APFC
APFC
Vs: 415 V
Ik" : 15682.9A
APFC_IC
MPCP_OG2
CAB:Crane
CRANE_IC
MPCP_OG3
CAB:MPDB
MPDB_IC
MPCP_OG4
CAB:Leveller
LEVELLER_IC
MPCP_OG5
CAB:pump pnl
PUMP PNL_IC
MPCP_OG6
CAB:WM
WM_IC
MPCP_OG7
CAB:Turnover
TURNOVER_IC
MPCP_OG8
CAB:mldb
MLDB_IC
MPCP_OG9
CAB:PP comp
COMP_IC
MPCP_OG10
CAB:BL1
BL1_IC
MPCP_OG11
CAB:BL2
BL2_IC
MPCP_OG12
CAB:OFFICE
OFFICE_IC
SP1 SP3
Crane Panel
Vs: 415 V
Ik" : 10942.76A
PP_MPDB
Vs: 415 V
Ik" : 15232.46A
LEVELLER PNL
Vs: 415 V
Ik" : 9430.64A
PP_PUMP PNL
Vs: 415 V
Ik" : 12134.73A
WASHING M/C
Vs: 415 V
Ik" : 11914.29A
TURNOVER EQUP PNL
Vs: 415 V
Ik" : 11580.56A
PP_MLDB
Vs: 415 V
Ik" : 11123.58A
PP_COMP
Vs: 415 V
Ik" : 11639.63A
BL_PNL1
Vs: 415 V
Ik" : 9862.55A
BL_PNL2
Vs: 415 V
Ik" : 8377.34A
OFFICE AREA
Vs: 415 V
Ik" : 13977.11A
SP 2
PUMP PNL_OG1
CAB:STP PNL
STP PNL_IC
STP PNL
Vs: 415 V
Ik" : 3484.68A
PUMP PNL_OG2
CAB:WTP PNL
WTP PNL_IC
WTP PNL
Vs: 415 V
Ik" : 3484.68A
MPDB_OG1
CAB:PDB
PDB_IC
PDB
Vs: 415 V
Ik" : 1485.47A
Bus Name Pre Fault
Voltage
Peak
Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
MPCP 415 42137 16183 16183 14443 12325 10852 1527
DG 433 42026 15663 15663 13964 11901 10469 1465
APFC 415 38737 15683 15683 14046 12036 10628 1523
PP_MPDB 415 36364 15232 15232 13686 11773 10424 1519
OFFICE AREA 415 25696 13977 13977 12719 11104 9927 1513
PP_PUMP PNL 415 24059 12135 12135 11155 9874 8922 1486
WASHING M/C 415 22390 11914 11914 10982 9752 8830 1485
PP_COMP 415 20802 11640 11640 10764 9597 8713 1484
TURNOVER EQUP PNL 415 20637 11581 11581 10715 9559 8682 1483
Crane Panel 415 20550 10943 10943 10152 9092 8287 1469
PP_MLDB 415 19403 11124 11124 10331 9261 8442 1478
LEVELLER PNL 415 16704 9431 9431 8851 8050 7423 1444
BL_PNL1 415 16351 9863 9863 9254 8409 7744 1461
BL_PNL2 415 12550 8377 8377 7990 7420 6947 1452
STP PNL 415 4929 3485 3485 3449 3390 3333 1329
WTP PNL 415 4929 3485 3485 3449 3390 3333 1329
PDB 415 2101 1485 1485 1483 1478 1474 1037
Bus Name Pre Fault
Voltage
Peak
Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
Short Circuit Detailed Report - DG set Feeding
3P Fault - IEC60909 Method
LL Fault - IEC60909 Method
Bus Name Pre Fault
Voltage
Peak
Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
MPCP 415 36492 14015 14015 12508 10674 9398 2425
DG 433 36396 13564 13564 12093 10306 9066 2328
APFC 415 33547 13582 13582 12164 10424 9204 2412
PP_MPDB 415 31492 13192 13192 11852 10196 9027 2400
OFFICE AREA 415 22254 12105 12105 11015 9617 8597 2381
PP_PUMP PNL 415 20835 10509 10509 9661 8552 7726 2305
WASHING M/C 415 19391 10318 10318 9511 8445 7647 2302
PP_COMP 415 18015 10080 10080 9322 8311 7546 2299
TURNOVER EQUP PNL 415 17872 10029 10029 9279 8278 7519 2297
Crane Panel 415 17797 9477 9477 8792 7874 7176 2259
PP_MLDB 415 16803 9633 9633 8947 8020 7311 2281
LEVELLER PNL 415 14466 8167 8167 7665 6972 6429 2188
BL_PNL1 415 14160 8541 8541 8014 7282 6707 2231
BL_PNL2 415 10868 7255 7255 6919 6426 6016 2196
STP PNL 415 4269 3018 3018 2987 2936 2886 1785
WTP PNL 415 4269 3018 3018 2987 2936 2886 1785
PDB 415 1819 1286 1286 1284 1280 1276 1115
Bus Name Pre Fault
Voltage
Peak
Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
DG 433 42026 15663 15663 13964 11901 10469 3725
MPCP 415 41325 16000 16000 14298 12219 10770 3867
APFC 415 35758 14943 14943 13451 11599 10287 3804
PP_MPDB 415 31984 14043 14043 12722 11057 9861 3746
OFFICE AREA 415 24620 12890 12890 11800 10386 9342 3685
PP_PUMP PNL 415 17029 9176 9176 8616 7844 7240 3317
WASHING M/C 415 16544 9119 9119 8570 7812 7216 3317
PP_COMP 415 16033 9046 9046 8511 7769 7183 3315
TURNOVER EQUP PNL 415 15879 8980 8980 8453 7721 7143 3308
PP_MLDB 415 14746 8478 8478 8010 7355 6832 3246
Crane Panel 415 13792 7767 7767 7369 6806 6353 3131
BL_PNL1 415 12060 7201 7201 6869 6392 6001 3063
LEVELLER PNL 415 10612 6231 6231 5979 5611 5306 2871
BL_PNL2 415 10451 6658 6658 6390 5997 5669 3010
STP PNL 415 5267 3691 3691 3632 3538 3453 2399
WTP PNL 415 5267 3691 3691 3632 3538 3453 2399
PDB 415 2936 2076 2076 2068 2053 2039 1771
Bus Name Pre Fault
Voltage
Peak
Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
LG Fault - IEC60909 Method
LLG Fault - IEC60909 Method
Short Circuit Detailed Report - DG set Feeding (CONTINUED)
Bus Name Pre Fault
Voltage
Peak
Short
Circuit
Current in
Amps
Initial
Symmetric
al
SCCurrent
in Amps
0.5 Cycle
Symmetric
al SC
Current in
Amps
1 Cycle
Symmetric
al SC
Current in
Amps
3 Cycle
Symmetric
al SC
Current in
Amps
5 cycle
Symmetric
al SC
Current in
Amps
Std
Symmetric
al SC
Current in
Amps
DG 433 42026 15663 15663 13964 11901 10469 2103
MPCP 415 41937 16170 16170 14433 12318 10847 2201
APFC 415 38048 15625 15625 14003 12009 10610 2219
PP_MPDB 415 35362 15107 15107 13593 11713 10381 2229
OFFICE AREA 415 25998 13926 13926 12654 11031 9854 2225
PP_PUMP PNL 415 22436 11531 11531 10656 9498 8626 2183
WASHING M/C 415 20822 11192 11192 10377 9287 8458 2148
PP_COMP 415 19254 10799 10799 10052 9040 8262 2109
TURNOVER EQUP PNL 415 19088 10735 10735 9998 8997 8227 2107
Crane Panel 415 18962 10240 10240 9553 8623 7905 2140
PP_MLDB 415 17855 10244 10244 9577 8664 7952 2088
LEVELLER PNL 415 15230 8673 8673 8185 7504 6963 2070
BL_PNL1 415 15073 9069 9069 8497 7712 7100 2069
BL_PNL2 415 12500 8245 8245 7835 7243 6757 2147
STP PNL 415 5935 4186 4186 4122 4018 3923 2038
WTP PNL 415 5935 4186 4186 4122 4018 3923 2038
PDB 415 3399 2404 2404 2394 2377 2360 1692
Transformer capacity P
T
1600 kVA
Primary Voltage Vp 11 kV
Secondary Voltage Vs 0.433 kV
Transformer HV side CT details CTHV 100/5
Turns Ratio CTRP 20
Transformer LV side ACB Rating 2500
Percentage Impedance of Transformer Z 6.25%
Fault Current at 11 kV Bus as per report 13122 Amps
Fault current at 0.415 kV Bus as per report 27901 Amps
Transformer HV side current as per name plate 83.98 Amps
Relay drop off Ratio 0.95
HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 83.98/0.95
97.24
Transformer HV side CT Secondary Pick up Current Isfl 4.86
IDMT setting at 11kV side 1
Setting proposed on HV side Ip 1
Curve IEC Normal Inverse
Transformer LV side current as per name plate 2133.46
LV Pick up Current 1.1 x LV Currrent
=1.1 x 2133.82
2346.81
Setting Calculation for Distribution Transformers 1.6 MVA
0.433 kV
11kV,
-5% to +5%
ACB In:2500
CT
HV
:100/5
1.6 MVA
2346.81
Transformer LV side CT Secondary Pick up Current =2346/2500
IDMT setting at 0.433kV side 0.94
Setting proposed LV side Ip 0.95
Fault current at 0.415kV Bus as per report,for MINIMUM SOURCE Fault 27901.00 Amps
HV side current due to fault at 0.415 kV bus 1098.28 Amps
HV side CT Secondary current due to fault at0.415kV bus 54.91 Amps
HV side Current fault at Transformer HV side 13122.00
HV side CT current due to fault at Transformer HV side 656.10 Amps
Setting proposed on HV side relay I>> 10.98 x 1.2=11.04 Amps
Setting proposed on HV side relay I>> 13.00
Setting proposed on LV side ACB>> 6
0.415 kV
ACB In:1600
1010 kVA
ACB In:2000
Generator capacity P
T
1010 kVA
Generator Voltage Vp 0.415 kV
Generator full load current 1405.16
ACB Rating in AMF panel 1600 Amps
ACB Rating in Main Panel panel 2000 Amps
Sub Transient reactance of Alternator X'' 9.00%
Fault current at 0.415 kV Bus as per report 14015 Amps
Pick up current at Main Panel =1.05*1405 Amps
1475.25
Pick up current at AMF Panel =1.1*1405
1545.50
Over current Setting @ main panel 1475.25/2000
0.75
Over current Setting @AMF panel 1545/1600
1.00
Instantaneous setting Current at Main Panel 10000 Amps
Instantaneous setting at Main Panel 10000/2000
5.00
Instantaneous setting Current at AMF panel 12000 Amps
Instantaneous setting at AMF panel 12000/1600
7.50
Setting Calculation for Diesel Generator set 1010 kVA
0.433 kV
11kV,
-5% to +5%
ACB In:2500
CT
HV
:100/5
1.6 MVA
0.415 kV
ACB In:1600
1010 kVA
ACB In:2000
Generator Capacity = 1010 kVA
Operating Voltage 415 volts
CT Primary(n) 2000 Amps
CT Secondary = 5 amps
TRF Impedance = 9 %
n = 400
CT Secondary wiring Length = 25 met
CT Secondary wiring size = 4 Sq.mm
Resistance of conductor = 4.61 ohms per km
CT resistance(RCT) = 3 ohms
CT magnitization current(Im) = 30 mA
Fault level in CT Primary: 15663.00 Amps
IF Secondary = 39.16 Amps
Lead Resistance: 25*4.61/1000 ohms
RL= CT Secondary wiring Length x Resistance of Conductor per meter 0.11525 ohms
Additional Resistance: Ra=0.01 ohms 0.01
Vs=If/n (Rct+2RL+Ra) 126.89 volts
Knee point voltage must be in excess of 2 x Vs 253.78 volts
V kn 253.78 volts
10% Percent setting
Required Loop Resistance value
Rs=Vs/Is
Is=10 % 10
Is= 0.5 Amps 0.5 Amps
Vs= 126.89 volts
Rs= 253.78 ohms
Relay VA burden= VA 10
Relay resistance= VA/Is
2
0.4 ohms
Rstab=Rs-Relay resistance 253.38 Ohms
Calculation for the Value of Stabilizing Resistor-for 1010 kVA
Generator Details
TRF Capacity = 1600 kVA
TRF Primary = 11000 volts
TRF Secondary = 433 volts
CT Primary(n) 2500 Amps
CT Secondary = 5 amps
TRF Impedance = 6.25 %
n = 500
CT Secondary wiring Length = 25 met
CT Secondary wiring size = 4 Sq.mm
Resistance of conductor = 4.61 ohms per km
CT resistance(RCT) = 3 ohms
CT magnitization current(Im) = 20 mA
Fault level in CT Primary: 31826.00 Amps
IF Secondary = 63.65 Amps
Lead Resistance: 25*4.61/1000 ohms
RL= CT Secondary wiring Length x Resistance of Conductor per meter 0.11525 ohms
Additional Resistance: Ra=0.01 ohms 0.01
Vs=If/n (Rct+2RL+Ra) 206.26 volts
Knee point voltage must be in excess of 2 x Vs 412.53 volts
V kn 412.53 volts
10% Percent setting
Required Loop Resistance value
Rs=Vs/Is
Is=10 % 10
Is= 0.5 Amps 0.5 Amps
Vs= 206.26 volts
Rs= 412.53 ohms
Relay VA burden= VA 10
Relay resistance= VA/Is
2
0.4 ohms
Rstab=Rs-Relay resistance 412.13 Ohms
Calculation for the Value of Stabilizing Resistor- TR 1.6MVA
Transformer Details
Setting Details for
11 kV SwitchBoard
Relay type:VN100R Feeder Ref: 11kV SWBD IC1
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 100 A
CT rated secondary 1 A / 5 A 5A
Setting name Units Range Setting Primary Value
Current set (low) (51-1) I> 0.1..5 1.1 110
Time multiplier at IDMT mode tms 0.05..1 0.9
IEC Curve Normal Inverse
,Very Inverse
,Extremely Inverse
,Long Inverse
Normal Inverse
Current set (high) (50-1) I>> 0.1..40.00 A 9 900
Operate time DT mode T-I>> 0.05..300.00 s 0.45
Current set (high Inst) (50-2) I>>> 0.1..40.00 A 15 1500
Operate time DT mode T-I>>> 0.05..300.00 s 0.05
Relay Setting Data for 11 kV Switchgear
11 kV Outdoor VCB Panel HVSP1 (Near 2 pole structure)
SCOPE OF FUNCTION
Power System Data 1
Phase over current Protection: 50/51
Ground over current Protection: 50N/51 N
Operate time DT mode T-I>>> 0.05..300.00 s 0.05
Setting name Units Range Setting Primary Value
Current set (low) (51N-1) I0> 0.10..12 x In 0.3 30
Operate time DT mode T Io> 0.05..300.00 s 0.45
Current set high),Io>> (50N-1) Io>> 0.10..12 x In 1.1 110
Operate time DT mode T Io>> 0.05..300.00 s 0.05
Ground over current Protection: 50N/51 N
Relay type:VN100R Feeder Ref: 11kV SWBD IC2
Address Setting Title Setting Range Setting
Fault Records Enabled/Disabled Enabled
Function 50/51
Function 50N/51N
Other functions are disabled
Title Setting Range Setting
CTs
CT rated primary 10..50000 A 100 A
CT rated secondary 1 A / 5 A 5A
Setting name Units Range Setting Primary Value
Current set (low) (51-1) I> 0.1..5 1 100
Time multiplier at IDMT mode tms 0.05..1 0.85
IEC Curve Normal Inverse
,Very Inverse
,Extremely Inverse
,Long Inverse
Normal Inverse
Current set (high) (50-1) I>> 0.1..40.00 A 8 800
Operate time DT mode T-I>> 0.05..300.00 s 0.3
Current set (high Inst) (50-2) I>>> 0.1..40.00 A 13 1300
Operate time DT mode T-I>>> 0.05..300.00 s 0.05
Phase over current Protection: 50/51
Ground over current Protection: 50N/51 N
Relay Setting Data for 11 kV Switchgear
11 kV Outdoor VCB Panel HVSP2 (Substation )
SCOPE OF FUNCTION
Power System Data 1
Operate time DT mode T-I>>> 0.05..300.00 s 0.05
Setting name Units Range Setting Primary Value
Current set (low) (51N-1) I0> 0.10..12 x In 0.25 25
Operate time DT mode T Io> 0.05..300.00 s 0.3
Current set high),Io>> (50N-1) Io>> 0.10..12 x In 1 100
Operate time DT mode T Io>> 0.05..300.00 s 0.05
Ground over current Protection: 50N/51 N
Relay type:V64RRS1
CT Primary 2500
CT Seconary 5
Description Range Setting Prime
Setting Range 10-40% 10% 250
Stabilising resistance Value 413 ohms
Relay type:V64RRS1
CT Primary 2000
CT Seconary 5
Description Range Setting Prime
Setting Range 10-40% 10% 200
Stabilising Resistance Value 254 ohms
Restricted Earth Fault (64 R) @ MPCP1 for Transformer Incomer
Restricted Earth Fault (64 R) @ MPCP1 for DG Incomer
Setting Details for MPCP
Rating
In in
Amps
Phase
Current
setting
I1,Range
'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
Setting
range for
time lag
tr (at 3x
I1) in Sec
Time
setting Tr
Short
circuit
Current
setting
Isd,Range
Isd=Ir x
'b'
Current
setting 'b'
Current
setting
(I2 ='b' X
In)
Setting
range for
delay
time tsd
in
seconds
Time Tsd
in
seconds
Instantan
eous
Current
Setting Ii
Range:
I3=In x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:Ii
= 'c' x In
Ground
fault
Current
Range Ig
range d
Current
Setting d
Primary
current
I4=In x d
Setting
range of
delay
time tg in
seconds
Setting
delay
time tg in
seconds
1 INCOMER from
Transformer
2500 2500,4P ACB- PR121 LSIG
release
2500 0.4-1.0
step 0.
025
0.95 2375 3-12-24-
36-48-72-
108-144s
3 1-10 step
0.5
4 10000 0.1-0.8
sec
0.1 1.5-15
step 1
6 15000 0.2-1.0
step 0.1
0.2 500 0.1-0.2-
0.4-0.8sec
0.2
2 INCOMER from
DG
2000 2000,4P ACB -PR121 LSIG
release
2000 0.4-1.0
step 0.
025
0.75 1500 3-12-24-
36-48-72-
108-144s
3 1-10 step
0.5
3 6000 0.1-0.8
sec
0.1 1.5-15
step 1
5 10000 0.2-1.0
step 0.1
0.2 400 0.1-0.2-
0.4-0.8sec
0.2
3 APFC Panel 1000 1000,3P PR121 LSIG release 1000 0.4-1.0
step 0.
025
0.9 900 3-12-24-
36-48-72-
108-144s
3 1-10 step
0.5
4 4000 0.1-0.8
sec
0.1 1.5-15
step 1
6 6000 0.2-1.0
step 0.1
0.2 200 0.1-0.2-
0.4-0.8sec
0.1
4 Spare 630 630,3P MCCB TMA release 630 0.7-1.0 x
In
1 630 NA NA NA NA NA NA NA 5-10 xIn 6 3780 NA NA NA NA NA
5 Crane Control
panel
400 400,3P MCCB TMA release 400 0.7-1.0 x
In
0.9 360 NA NA NA NA NA NA NA 5-10 xIn 6 2400 NA NA NA NA NA
6 PP-MPDB 400 400,3P MCCB TMA release 400 0.7-1.0 x
In
0.9 360 NA NA NA NA NA NA NA 5-10 xIn 6 2400 NA NA NA NA NA
7 Leveller Panel 800 800,3P MCCB TMA release 800 0.7-1.0 x
In
0.9 720 NA NA NA NA NA NA NA 5-10 xIn 6 4800 NA NA NA NA NA
8 PP-Pump Panel 400 400,3P MCCB TMA release 400 0.7-1.0 x
In
0.9 360 NA NA NA NA NA NA NA 5-10 xIn 6 2400 NA NA NA NA NA
9 Washing M/C
equip Panel
250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
10 Turnover Equip
Panel
250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.7 175 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
11 Spare 630 630,3P MCCB TMA release 630 0.7-1.0 x
In
1 630 NA NA NA NA NA NA NA 5-10 xIn 6 3780 NA NA NA NA NA
12 Spare 400 400,3P MCCB TMA release 400 0.7-1.0 x
In
1 400 NA NA NA NA NA NA NA 5-10 xIn 6 2400 NA NA NA NA NA
13 PP-MLDB 250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
Short time delayed short circuit protection Instantaneous short circuit Ground Fault Protection
Setting Data Sheet for 0.415 kV- MPCP1
Ref_DrawingNo VMCL/ 045/ 2013-14
Sl.No Feeder name: Feeder
Rating in
Amps/KW
ACB/MCCB type
ACB setting
Over load protection
13 PP-MLDB 250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
14 PP-Comp 250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
15 Blanking label 1 250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
16 Blanking label 2 250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
17 PP-Office Area 250 250,3P MCCB TMA release 250 0.7-1.0 x
In
0.9 225 NA NA NA NA NA NA NA 5-10 xIn 6 1500 NA NA NA NA NA
Rating
In in
Amps
Phase
Current
setting
I1,Range
'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
Setting
range for
time lag
tr (at 3x
I1) in Sec
Time
setting Tr
Short
circuit
Current
setting
Isd,Range
Isd=Ir x
'b'
Current
setting 'b'
Current
setting
(I2 ='b' X
In)
Setting
range for
delay
time tsd
in
seconds
Time Tsd
in
seconds
Instantan
eous
Current
Setting Ii
Range:
I3=In x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:Ii
= 'c' x In
Ground
fault
Current
Range Ig
range d
Current
Setting d
Primary
current
I4=In x d
Setting
range of
delay
time tg in
seconds
Setting
delay
time tg in
seconds
1 INCOMER from
MPCP1
1000 1000,3P ACBPR121 LSIG
release
1000 0.4-1.0
step 0.
025
0.85 850 3-12-24-
36-48-72-
108-144s
3 1-10 step
0.5
3 3000 0.1-0.8
sec
0.1 1.5-15
step 1
5 5000 0.2-1.0
step 0.1
0.2 200 0.1-0.2-
0.4-0.8sec
0.1
2 28 kVAR Feeder 63 63,3P MCCB TMD release 63 0.7-1.0 x
In
1 63 NA NA NA NA NA NA NA FIXED 10
Xin
10 630 NA NA NA NA NA
3 56 kVAR Feeder 100 100,3P MCCB TMD release 100 0.7-1.0 x
In
1 100 NA NA NA NA NA NA NA FIXED 10
Xin
10 1000 NA NA NA NA NA
Sl.No Feeder name: Feeder
Rating in
Amps/KW
ACB/MCCB type
ACB setting
Over load protection Short time delayed short circuit protection Instantaneous short circuit Ground Fault Protection
Setting Data Sheet for 0.415 kV- APFC Panel
Ref_DrawingNo VMCL/ 045/ 2013-14
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 400 400,3P MCCB-TMA Release 400 0.7-1.0 step 0.5 0.85 340 NA NA 5-10 X In 5 2000
1 PDB1 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 0.7 70 NA NA FIXED 10 Xin 10 1000
2 SPARE 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 1 100 NA NA FIXED 10 Xin 10 1000
3 SPARE 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 1 100 NA NA FIXED 10 Xin 10 1000
4 PDB2 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.7 44.1 NA NA FIXED 10 Xin 10 630
5 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
6 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
7 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
8 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
9 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
10 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
11 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
12 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
13 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
14 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
15 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
16 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
Instantaneous short circuit
Setting Data Sheet for 0.415 kV- MPDB MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Over load protection
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 400 400,3P MCCB-TMA Release 400 0.7-1.0 step 0.5 0.85 340 NA NA 5-10 X In 5 2000
2 FIRE HYDRANT PUMP PANEL 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 1 125 NA NA FIXED 10 Xin 10 1250
3 STP PANEL 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
4 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
5 DOMESTIC WATER PUMP 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
6 GARDEN WATER PUMP 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
7 RAW WATER PUMP 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
8 SPARE 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
9 SPARE 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
10 SPARE 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
11 SPARE 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
12 SPARE 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
Over load protection Instantaneous short circuit
Setting Data Sheet for 0.415 kV- PUMP PANEL MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 250 250,3P MCCB-TMA Release 250 0.7-1.0 step 0.5 0.85 212.5 NA NA 5-10 X In 5 1250
2 LDB 1 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
3 LDB2 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
4 LDB 3 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
5 LDB 4 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
6 LDB 5 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
7 LDB 6 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
8 LDB 7 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
9 LDB 8 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
10 LDB EXT 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
11 LDB ESC 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.75 47.25 NA NA FIXED 10 Xin 10 630
12 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
Over load protection Instantaneous short circuit
Setting Data Sheet for 0.415 kV- MLDB MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 250 250,3P MCCB-TMA Release 250 0.7-1.0 step 0.5 0.85 212.5 NA NA 5-10 X In 5 1250
2 COMPRESSOR 1 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 0.7 87.5 NA NA FIXED 10 Xin 10 1250
3 COMPRESSOR 2 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 0.7 87.5 NA NA FIXED 10 Xin 10 1250
4 SPARE 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 1 125 NA NA FIXED 10 Xin 10 1250
5 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
6 DRYER 1 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
7 DRYER 2 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
8 SPARE 32 32,3P MCCB-TMD Release 32 0.7-1.0 step 0.5 1 32 NA NA FIXED 10 Xin 10 320
Over load protection Instantaneous short circuit
Setting Data Sheet for 0.415 kV- PP COMP MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 250 250,3P MCCB-TMA Release 250 0.7-1.0 step 0.5 0.85 212.5 NA NA 5-10 X In 5 1250
2 PDB 3 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 0.7 70 NA NA FIXED 10 Xin 10 1000
3 PDB 4 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 0.7 70 NA NA FIXED 10 Xin 10 1000
4 ACDB 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.7 44.1 NA NA FIXED 10 Xin 10 630
5 PACKAGE UNIT 1 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.7 44.1 NA NA FIXED 10 Xin 10 630
6 PACKAGE UNIT 2 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.7 44.1 NA NA FIXED 10 Xin 10 630
7 UPS DB 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 0.7 44.1 NA NA FIXED 10 Xin 10 630
8 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
9 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
10 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
11 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
12 SPARE 63 63,3P MCCB-TMD Release 63 0.7-1.0 step 0.5 1 63 NA NA FIXED 10 Xin 10 630
Over load protection Instantaneous short circuit
Setting Data Sheet for 0.415 kV- OFFICE AREA MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 400 400,3P MCCB-TMA Release 400 0.7-1.0 step 0.5 0.85 340 NA NA 5-10 X In 5 2000
2 CRANE 1 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 1 125 NA NA FIXED 10 Xin 10 1250
3 CRANE 2 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 1 125 NA NA FIXED 10 Xin 10 1250
4 CRANE 3 125 125,3P MCCB-TMD Release 125 0.7-1.0 step 0.5 1 125 NA NA FIXED 10 Xin 10 1250
5 CRANE 4 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 0.8 80 NA NA FIXED 10 Xin 10 1000
6 CRANE 5 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 0.8 80 NA NA FIXED 10 Xin 10 1000
7 CRANE 6 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 0.8 80 NA NA FIXED 10 Xin 10 1000
8 SPARE 100 100,3P MCCB-TMD Release 100 0.7-1.0 step 0.5 1 100 NA NA FIXED 10 Xin 10 1000
Over load protection Instantaneous short circuit
Setting Data Sheet for 0.415 kV- CRANE PANEL MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Rating
In in
Amps
Phase Current
setting I1,Range 'a'
Current
setting 'a'
Primary
Current
(I1 =a X
In)
time lag
tR in sec
range
time lag
tR in sec
range
Instantaneo
us Current
Setting I2
Range: I2=In
x 'c'
Current
setting 'c'
Primary
Instantan
eous
current:I2
= 'c' x In
1 INCOMER 800 800,3P MCCB-TMA Release 800 0.7-1.0 step 0.5 0.85 680 NA NA 5-10 X In 5 4000
2 LEVELLER EQUIPMENT 1 400 400,3P MCCB-TMA Release 400 0.7-1.0 step 0.5 0.9 360 NA NA FIXED 10 Xin 10 4000
3 LEVELLER EQUIPMENT 2 400 400,3P MCCB-TMA Release 400 0.7-1.0 step 0.5 0.9 360 NA NA FIXED 10 Xin 10 4000
Over load protection Instantaneous short circuit
Setting Data Sheet for 0.415 kV-LEVELLER PANEL MCCB Feeeders
Ref_Drawing No VMCL/ 045/ 2013-14
Sl No Feeder name: Feeder
Rating in
Amps
MCCB type
MCCB setting
Time Current Characterstic Curves
11000 Volt Phase Time-Current Characteristic Curves
0 - Path: Grid-Cap_Pnl
04-18-2014
11:07:47
MISTEEL_170414
.
0
1
.
1
1
1
0
1
0
0
1
0
0
0
1
0
0
0
0
T
i
m
e

i
n

S
e
c
o
n
d
s
.5 1 10 100 1000 10000
Current in Amperes X 10
MPCP_IC1
MPCP_OG1
HV_SP2
HVSP1
A
TR1 1600.0 KVA
Transformer
Inrush
11000 Volt Ground Time-Current Characteristic Curves
0 - Path: Grid-Cap_Pnl
04-18-2014
11:01:58
MISTEEL_170414
.
0
1
.
1
1
1
0
1
0
0
1
0
0
0
1
0
0
0
0
T
i
m
e

i
n

S
e
c
o
n
d
s
.5 1 10 100 1000 10000
Current in Amperes X 10
MPCP_IC1
MPCP_OG1
HV_SP1
HV_SP2
OBSERVATIONS
&
SUGGESTIONS
OBSERVATIONS
&
SUGGESTIONS
1 The CTs provided in the Main MPCP Panel for REF relays for both Transformer and DG
Incomer should be of Class PS and not otherwise
2 For REF Protection of the transformer and DG set , there should be 4 CTs. 3 on phase and
one on Neutral before earthing .All the 4 CTs are to be PS class with designed Kneepoint
voltage.For transformer incoming circuit the CT ratio is to be 2500/5 and for the DG
Incoming circuit it should be 2000/5
3 REF protection relay should trip and cut of source supply to the Primary side of the
Transformer.Presently it is wired only to trip LT side ACB,which is not correct.
4 The Generator panel has been provided with REF relay.But only 3 CTs of Class 5P10 has been
shown.There should be neutral CT.All CTs are to be Class PS
5 In office area Panel the selection MCCB and Cable does not match.The MCCBs will not
protect the cable.For example for PDB 3 and PDB 4 feeders the selected cable is 4 x 10
sqmm.AL.These cable can carry only 38 Amps .Where as the MCCB provided are 100 Amps
with over current setting range is 70-100 Amps.Now the cable is un protected from 38 Amps
to 70 Amps.Even for other feeders the same problem persists.
6 In PP COMP Panel the selection MCCB and Cable does not match.The MCCBs will not
protect the cable.
7 In MPDB Panel the selection MCCB and Cable does not match.The MCCBs will not protect
the cable.
8 The device ratings and cable sizing indicated in the SLD drawing does not match with Panel
drawings and Cable schedule.
Observations and Suggestions