VFD MODEL: SIEMENS MM420

SL NO: TERMINALS
1 3
2 4
3 12
4 13
5 9
6 6
7 5
8 10 NO
9 11 COM
SL NO: PARAMETER SETTING
1 P0100 0
2 P0307 *
3 P0310 50
4 P0304 *
5 P0305 *
6 P0311 *
7 P0640 150
8 P0700 2
9 P1000 2
10 P1080 0
11 P1082 50
12 P1120 30
13 P1121 10
14 P3900 0
0
1
30
1
2
3
17 P0725 0
18 P0701 10
19 P0702 1
20 P0731 52.3
21 P1058 50
NOTE:
MOTOR FREQUENCY (Hz)
MOTOR VOLTAGE (V)
ACCELERATION TIME (S)
DECELERATION TIME (S)
CURRENT RATING (A)
MOTOR SPEED (RPM)
*DIP SWITCH SEETTING TO BE DONE FOR 50Hz
P0003 16
TERMINAL 5 - JOG RIGHT: HAND MODE RUN
TERMINAL 6 - ENABLE VFD: AUTO MODE RUN
RELAY OUTPUT: CONFIGURED FOR DRIVE FAULT
NPN MODE SELECTED - TERMINAL 9
OVERLOAD FACTOR
CONTROL FROM - VFD TERMINALS
FOR FACTORY RESET:
15 P0010 QUICK COMMISSIONING
FACTORY RESET AFTER P0970 = 1
ANALOG OUTPUT (+)
SPEED FEEDBACK (0-20mA)
ANALOG OUTPUT (-)
INTERNAL 0V SUPPLY (SINK) NPN
UNIT IN kW & 50Hz SELECTION
MOTOR POWER (kW)
STANDARD USER
READY (SETTINGS COMPLETED)
SUB: VFD PARAMETER SETTING (ANALOG INPUT + FIXED FREQUENCY)
IO WIRING DESCRIPTION
DESCRIPTION REMARKS
ANALOG INPUT (0-10VDC)
AUTO MODE SPEED REFERENCE SOURCE
COMMON
ENABLED WHEN DRIVE FAULT ACTIVE
ANALOG SETPOINT FOR SPEED CONTROL
MINIMUM FREQUENCY
MAXIMUM FREQUNECY
* TO BE SET ACCORDING TO MOTOR NAMEPLATE RATING. CURRENTLY SET AT DRIVE RATINGS
NO QUICK COMMISSIONING - REQUIRED TO SET VFD
EXTENDED USER - REQUIRED TO MAKE SETTINGS
EXPERT USER - UNLOCK ALL PARAMENTERS
JOG FREQUENCY: HAND MODE RUN FREQUENCY
P0010 = 30
P0970 = 1
10 SEC REQUIRED FOR RESET.
VFD ENABLE/DISABLE CMD. AUTO MODE VFD ENABLE/DISABLE
JOG RIGHT SELECTION IN HAND
MODE
HAND MODE VFD RUN IN PRESET SPEED
SELECTION -1
VFD PARAMETER SETTING
DESCRIPTION
RELAY
OUTPUT