DESIGN OF BASE PLATE

STRUCTURE: XFR AREA J


Column Mark : UC-203 UC203X203X46
1. DESIGN FORCES SUMMARY
Fx Fy Fz Axial (F) (Fy
2
+Fz
2
)
0.5
Friction (f) Shear
Beam L/C NODE (kN) (kN) (kN) F = Fx (kN) Q (kN) f=0.45F (kN) Q - f (kN)
2027 456 255 232.8 30.2 3.3 232.8 30.4 104.8 0.0
2001 595 245 -13.9 10.5 0.0 -13.9 10.5 0.0 10.5
2030 595 256 -7.2 22.9 -0.5 -7.2 22.9 0.0 22.9
F = Fc (Axial Compression) if value is positive, F = Ft (Axial Tension) if values is negative
2. MATERIAL PROPERTY AND DIMENSION
Steel Column : D = 203.2 mm
B = 203.6 mm
t = 7.2 mm
T = 11.0 mm
Base Plate : P
yp
= 265.0 Mpa (S275)
D
p
= 250.0 mm
B
p
= 250.0 mm
tp = 22.0 mm
Anchor Bolt : Grade : 4.6
db = 24.0 mm
n = 2.0 pcs
Effective Area per bolt (Ae
perbolt
) = 353.0 mm
2
Effective Area of bolts (Ae
bolts
) = 706.0 mm
2
3. CHECK FOR CONCRETE BEARING STRENGTH (4.13.1 of BS 5950-1:2000)
f
cu
= 30.0 Mpa Fc / B
p
D
p
= 3.7 Mpa < 0.6fcu OK!
0.6f
cu
= 18.0 Mpa A
req
= Fc / 0.6F
cu
Fc = 232.8 kN (Maximum Compression Force) = 12,933.3 mm
2
4. CHECK FOR BASE PLATE THICKNESS BY EFFECTIVE AREA METHOD (sec 4.13.2.2 of BS 5950-1:2000)
base plate thickness (tpreq) = c (3x0.6f
cu
/P
yp
)
0.5
Column Perimeter (Per
col
) = 1,190.0 mm
effective area (Aeff) = 4c1
2
+ c1(Per
col
) + A
col
(Assuming no Overlap of Effective Area) Area of Steel Column A
col
= 5,870.0 mm
2
effective area (Aeff) = 4c2
2
+ 2(D + B)c2 + DB (Assuming Effective Area has Overlap)
solving for c by equating Aeff to Areq : 12,933.3 = 4c1
2
+ 1,190.0c1 + 5,870.0 c1 = 5.82 mm
12,933.3 = 4c2
2
+ 813.6c2 + 41,371.5 c2 = -44.84 mm
(D-2T )/2 = 90.6 mm > c1, effective area has no overlap (use value of c1 for c)
D +2c = 214.84 mm < Dp
B + 2c = 215.24 mm < Bp
Hence the calculated value of c is valid.
c = 5.82 mm
tp
req
= 2.7 mm < tp, OK!
STAAD OUTPUT DESIGN FORCES UC-203
DESCRIPTION
Condition
Max Compression
Max Tension
Max Shear
4.4 BASE PLATE AND ANCHOR BOLT CHECK
5. ANCHOR BOLT STRESS CHECK
5.1 Design Strength of Anchor Bolts
pt = 240 Mpa, tension strength of anchor bolt
ps = 160 Mpa, shear strength of anchor bolt
5.2 Capacity of Ancor Bolts
Tension Capacity of Anchor Bolts (Pt) = 162.8 kN Shear Capacity of Anchor Bolts (Ps) = 108.6 kN
5.3 Combined Tension and Shear Check
Due to Maximum Tension, Load Case # : 595 Due to Maximum Shear, Load Case # : 595
Ft = 13.9 kN Ft = 7.2 kN
V = 10.5 kN V = 22.9 kN
Ft / Pt = 0.09 < 1.0 OK! Ft / Pt = 0.04 < 1.0 OK!
V/Ps = 0.10 < 1.0 OK! V/Ps = 0.21 < 1.0, OK!
(Ft/Pt)
2
+ (V/Ps)
2
= 0.02 <1.0, OK! (Ft/Pt)
2
+ (V/Ps)
2
= 0.05 <1.0, OK!