1 General Information The AREVA P34x converter is designed for use with the OMICRON Test Universe 2.22 software for testing the P34x generator protection relays. The converter provides all necessary data for testing the generator protection functions (see chapter 2 ) of the P34x relays.
Note: This converter is tested with the relay described above. It may work with similar relays, too. 2 Quick Start Information To work with the AREVA P34x XRIO converter: 1. Start a new OMICRON Control Center (OCC) document or open an existing OCC document. 2. Insert a new test object or open the existing test object. 3. On the File menu, click Import. 4. Browse to the latest OMICRON P34x.xrio file. 5. Click Open. 6. Enter all necessary settings in the Relay Parameter Section, Additional Information General/Power System Parameters/Circuit Breaker Information/Test Parameters (see chapter 8.1.1 and 8.1.2 ). 7. Click OK.
Figure 1: Opening and importing the AREVA P34x XRIO converter OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 5/16 3 Using the Converter The AREVA P34x XRIO converter can be used as a stand-alone converter or in association with a relay specific test template, for example with the OMICRON Generator Protection template for the P34x relays.
In any way the converter is used, follow the quick start instructions and create your test using LinkToXRIO or start using the relay specific test template (for more information, see the test template documentation). 4 Required Software Version To use this converter, you must have a valid license for the OMICRON Test Universe 2.22 software. 5 Functional Range The AREVA P34x XRIO converter implements the following functions: 81 Over/Underfrequency protection 27 Phase Undervoltage protection 59 Phase Overvoltage protection 47 Negative Sequence Overvoltage protection 59N Neutral Overvoltage protection 24 Volts/Hz protection 87 Generator Differential protection 46 Stator Overload protection 46T NPS Thermal 49 Stator Overload protection 46 Negative Phase Sequence Overcurrent protection 50, 51 Phase Overcurrent protection 50/27 Dead Machine protection 32 Over/Underpower protection 21/51V System backup protection 40 Fields Failure protection 78 Pole Slipping protection 27T/59T 100% Stator protection 67N Sensitive Earth Fault Overcurrent 64 High Impedance Restricted Earth Fault protection 64 Low Impedance Restricted Earth Fault protection 50N/51N Earth Fault Overcurrent OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 6/16
Figure 2: Functional range of the AREVA P34x XRIO converter
Some of the functions listed above use the RIO interface of the Test Universe software. Consequently, the test modules are configured automatically without using LinkToXRIO. The following functions use the RIO interface: 87 Biased Differential protection 21 Impedance protection 78 Out of Step protection 40 Field Failure protection 46 Negative sequence 50, 50N, 50DT, 51N, 51V, 67N Instantaneous/Definite/Inverse Timed Phase/Neutral Overcurrent protection 49 Thermal overload protection 46 NPS Thermal protection
For testing the other functions, you must use LinkToXRIO. OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 7/16 6 Not Supported Functions The following functions are currently not supported:
64S 100% Stator Ground protection-low frequency injection Earth fault (P341 relay) 59N Residual voltage protection (VN2-input) 67N SEF protection with option wattmetric, cos(Phi) and sin(Phi) 32N Sensitive Power Supervision CB Fail RTD Inputs
7 OMICRON Test Strategy The OMICRON test strategy is described in the OMICRON Protection Test Template (PTT) Generator documentation. For detailed information, see the PTT Generator documentation. 8 Converter Structure The converter is divided into two sections: the P34x section and the RIO section. Both sections consist of several function blocks. The converter comes up in the standard view; the RIOplus section and the template controller section can only be seen in the advanced view. 8.1 P34x Section The P34x section is divided into four groups: the Relay Parameter Section, the Additional Information section, the RIO Plus section and the TemplateController section. 8.1.1 Relay Parameter Section The Relay Parameter Section includes the parameters which have to be changed by the user. All relay parameters are included in this section and have to be set to the actual relay values. The parameters are grouped and named as in the AREVA MiCOM S1 Studio software. Each parameter in this block is identified by a Foreign ID (witch corresponds to the Address in the relay software).
Figure 3: Setting the parameters in the Relay Parameter Section 8.1.2 Additional Information This block contains additional data for testing the P34x relay functionality. The block is divided into the following sections: General section includes detailed information needed for the test report like manufacturer, device type, substation name etc. This section includes parameters which have to be changed by the user according to the customer relay type and substation. Relay Information section - This block has been added for relay specific parameters such as tolerances which cannot be set by the user, because they are constant values. All values set in this block can be found in the "P34x Generator Protection Relay" manual. Typically, these blocks do not have to be changed, as they are already set to the values given in the user manual of the relay. Circuit Breaker Information section includes information which is required for the CB test. Test Tolerance section includes an additional test tolerance to calculate the start and end value for trip and pickup tests by using the OMICRON TU Ramping module. Test Parameters section includes additional test parameters for testing adaptive functions witch are not directly supported by the OMICRON TU test modules e.g. a voltage level for the 51V tests. Furthermore it includes additional test parameters which are needed for testing the protection function but not found in the relay settings. e.g. high operating current stage for the 87 Phase Differential protection function. This section includes parameters which have to be changed by the user. OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 9/16 8.1.3 RIOPlus (Advanced view) The RIO Plus section contains the interface, which provides the link between the XRIO converter and all test modules which have no access to RIO functions. All tests using basic test modules like Ramping or State Sequencer have to be linked to the parameters in the RIO Plus section of the converter. 8.1.3.1 NamePlate The NamePlate block contains all necessary information to identify the protection device to be tested. This block contains the relay vendor, serial number, model, the relay location, hardware revision, software revision and a description. 8.1.3.2 PowerSystemParameters The number of phases, phase rotation and the nominal frequency are stored in this block. 8.1.3.3 GeneratorProtection This block contains all data necessary for testing the functional range (see chapter 5 ) of the AREVA P34x relays except the underimpedance and overcurent protection functions. The nominal values and CT settings for both generator sides used by these protection functions can be found here. The following protection functions are included in this section: 8.1.3.3.1 FrequencyElements This block contains all necessary data for testing the over- and under frequency protection functions. All stages of the under frequency and over frequency protection function in the relay are modeled as sub blocks of the FrequencyElements block. Each stage sub block stores information about the pickup value, operating time and the pickup drop-off ratio. 8.1.3.3.2 VoltageElements This block contains all necessary data for testing the over- and under voltage protection functions. All stages of the voltage protection function in the relay are modeled as sub blocks of the VoltageElements block. Each stage sub block stores information about the pickup value, operating time and the pickup drop-off ratio. 8.1.3.3.3 PowerElements This block contains all necessary data for testing the over- and under power protection function. All stages of the directional power protection function in the relay are modeled as sub blocks of the PowerElements protection block. Each stage sub block stores information about the pickup value, operating time and the pickup drop-off ratio. 8.1.3.3.4 VoltsPerHertzElements This block contains all necessary data for testing the Volts per Hertz (Overfluxing) protection. All stages of the VoltsPerHertz protection function in the relay are modeled as sub blocks of the VoltsPerHerzElements block. Each stage sub block stores information about the pickup value, operating time, the pickup drop-off ratio and the operating curve. 8.1.3.3.5 DifferentialElements This block contains all necessary data for testing the 87G differential and the 64 restricted earth fault protection function. The following protection function curves are modeled as sub blocks of the DifferentialElements block: biased differential curve, high impedance differential curve, interturn differential curve, low impedance restricted earth fault curve and high impedance restricted earth fault curve
OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 10/16 Each sub block stores information about the pickup value, operating time, HarmonicRestraintElements and the operating curve. 8.1.3.3.6 InadvertentEnergizingElements This block contains all necessary data for testing the inadvertent energizing protection function. The block contains an InstantaneousObercurrentElement and an UnderVoltageElement sub blocks. Each sub block stores information about the pickup and pickup drop-off ratio and the operating time. 8.1.3.3.7 UnderExcitationElements This block contains all necessary data for testing the Field Failure protection function. The Field Failure tripping elements are modeled as sub blocks of the UnderExcitationElements block. Each tripping element sub block (FF1, FF2 and FFAlarm) stores information about: the impedances in the BorderElements and GenericShape sub blocks the reach and phi values and tolerances in the Reach sub block the operating and reset delay time values and tolerances in the OperateDelayTime sub block 8.1.3.3.8 Thermal Protection This block contains all necessary data for testing the stator overload protection. All stages of the stator overload protection function in the relay are modeled as sub blocks of the StatorOverloadElements block. Each sub block stores information about the stator overload characteristics of the relay. 8.1.3.3.9 OutOfStepElements This block contains all necessary data for testing the out of step protection function. The out of step detection element and the starting element of the out of step protection function in the relay are modeled as sub blocks of the OutOfStepElements block. The sub block StartingElements block stores information about voltage pickup element. The sub block ImpedanceZoneElement includes the different pole slip detection elements and the reset delay time. Each SlipDetectionElement stores information about: the impedances in the BorderElements and GenericShape sub blocks the reach and phi values and tolerances in the Reach sub block the operating and reset delay time values and tolerances in the OperateDelayTime sub blocks 8.1.3.4 DistanceProtection This block contains all necessary data to test the distance protection circle. The nominal values and the CT / VT settings used by the distance protection functions can be found here. All zones of the distance protection function in the relay are modeled as sub blocks of the ImpedanceZoneElements block. Each zone sub block stores information about: the grounding factors in the GroundingFactor sub block the impedances in the BorderElements and GenericShape sub blocks the reach and phi values and tolerances in the Reach sub block the operating and reset delay time values and tolerances in the OperateDelayTime sub blocks 8.1.3.5 OvercurrentProtection This block contains all necessary data for testing the overcurrent protection elements witch use the phase current transformers. All stages of the overcurrent protection function in the relay are modeled as sub blocks of the OvercurrentElements block. Each stage sub block stores information about the pickup value, operating time, pickup drop-off ratio and the curve type. The sub block Voltage Dependent OC (System Backup) block contains all necessary data for testing the voltage dependent overcurrent function. 8.1.3.6 OvercurrentProtection (E/F CT) This block contains all necessary data for testing the overcurrent protection elements which use the neutral transformers. All stages of the overcurrent protection which use the E/F CT in the relay are modeled as sub blocks of the OvercurrentElements block. Each stage sub block stores information about the pickup value, operating time, pickup drop-off ratio and the curve type. OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 11/16 8.1.3.7 SEF This block contains all necessary data for testing the overcurrent protection elements which use the neutral transformers. All stages of the overcurrent protection which use the SEF CT in the relay are modeled as sub blocks of the OvercurrentElements block. Each stage sub block stores information about the pickup value, operating time, pickup drop-off ratio and the curve type. 8.1.4 TemplateController (Advanced view) The TemplateController block contains special values needed for some tests, especially for tests using LinkToXRIO. These are mainly calculated values which cannot be calculated in the RIOPlus. These values are needed for using LinkToXRIO. Furthermore this block contains special functionalities like e.g. an OC sort function. These values with its special functions are linked to the RIO section and are needed for the use of the OMICRON test modules.
Figure 4: Structure of the Template Controller
Note: Other values needed for customer designed test can be stored in this block. 8.1.4.1 Circuit Breaker The circuit breaker block contains all necessary data for testing protection functions together with the circuit breaker. The modeled parameter is the trip time. OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 12/16 8.2 RIO The RIO section of the converter contains all specialized RIO functions needed to use the more specialized test modules (like e.g. Advanced Differential or Overcurrent) provided by the OMICRON Test Universe software.
Warning: Do not change any values in this section. The values have been set using the relay settings of the Relay Parameter Section.
Note: Do not activate the former test object view in the advanced mode of the XRIO test object. Changing parameters in this view could disable formulas in the RIO section. 8.2.1 Generator Differential The RIO Differential function provides the necessary values for testing the Biased Differential protection function of the P34x relay. The RIO differential function contains all values needed for using the following OMICRON Test Universe modules: Diff Configuration Diff Characteristic 8.2.2 Low Z REF The RIO Differential function provides the necessary values for testing the Low Impedance Restricted Earth Fault protection function of the P34x relay. The RIO differential function contains all values needed for using the following OMICRON Test Universe modules: Diff Configuration Diff Characteristic 8.2.3 Distance This RIO Distance function provides the necessary values for testing the distance protection functions of the P34X relay with the Advanced Distance test module. The protection functions supported by this RIO function include: 21 Underimpedance
The following RIO function for testing these distance protection functions is available: Distance 8.2.4 Pole Slip The RIO Pole Slip block provides the necessary values for testing the out of step function of the P34x relay with the StateSequencer module with distance curve view. 8.2.5 Field Failure Trip This RIO Field Failure function provides the necessary values for testing the trip time of the field failure protection function of the P34x relay with the Advanced Distance test module. The protection functions supported by this RIO function include: 40 Filed Failure tripping zones
The following RIO function for testing these distance protection functions is available: Distance OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 13/16 8.2.6 Field Failure Alarm This RIO Loss of Field Alarm function provides the necessary values for testing the alarm signal of the field failure protection functions of the P34x relay with the Advanced Distance test module. The protection functions supported by this RIO function include: 40 Field Failure tripping zones
The following RIO function for testing these distance protection functions is available: Distance 8.2.7 Phase Overcurrent Forward This RIO Phase Overcurrent Forward block provides the necessary values for testing the trip times of the Phase Overcurrent function in forward direction. The protection functions supported by this RIO function include: 50,51,67 Phase Overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.8 Phase Overcurrent Reverse This RIO Phase Overcurrent Reverse block provides the necessary values for testing the trip times of the Phase Overcurrent function in reverse direction. The protection functions supported by this RIO function include: 50,51,67 Phase Overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.9 NPS Overcurrent Forward This RIO NPS Overcurrent Forward block provides the necessary values for testing the trip times of the NPS Overcurrent function in forward direction. The protection functions supported by this RIO function include: 46 NPS Overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.10 NPS Overcurrent Reverse This RIO NPS Overcurrent Reverse block provides the necessary values for testing the trip times of the NPS Overcurrent function in reverse direction. The protection functions supported by this RIO function include:: 46 NPS Overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 14/16 8.2.11 ThermalOverload Trip The RIO ThermalOverload functions for testing the trip time of the thermal overload protection function with Test Universe are implemented in the RIO block of the P34x XRIO converter: Thermal Overload (tripping element) This module contains the stator overload characteristic curve.
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.12 ThermalOverload Alarm The RIO ThermalOverload functions for testing the alarm time of the thermal overload protection function with Test Universe are implemented in the RIO block of the P34x XRIO converter: Thermal Overload (tripping element) This module contains the stator overload characteristic curve.
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.13 NPS Thermal The RIO NPS Thermal functions for testing the NPS thermal protection function with Test Universe are implemented in the RIO block of the P34x XRIO converter: NPS Thermal (tripping element) This module contains the rotor overload characteristic curve.
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.14 NPS Alarm The RIO NPS Alarm functions for testing the alarm signal of the NPS thermal protection function with Test Universe are implemented in the RIO block of the P34x XRIO converter: NPS Thermal (tripping element) This module contains the rotor overload characteristic curve.
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.15 Earth Fault This RIO Earth Fault block provides the necessary values for testing the trip times of the Earth Fault Overcurrent. The protection functions supported by this RIO function include: 50N,51N Earth Fault Overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 15/16 8.2.16 Voltage dependent OC (Vtest>Vs1) This RIO Voltage dependent Overcurrent function provides the necessary values for testing the voltage restrained/controlled inverse time overcurrent protection function with test voltages above the MiCOM Vs1 setting of the P34x relay with the Overcurrent test module. The protection functions supported by this RIO function include: 51V overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.17 Voltage dependent OC (Vtest<Vs1) This RIO Voltage dependent Overcurrent function provides the necessary values for testing the voltage restrained/controlled inverse time overcurrent protection function with test voltages below the MiCOM Vs1 setting of the P34x relay with the Overcurrent test module. The protection functions supported by this RIO function include: 51V overcurrent
The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.18 SEF This RIO SEF block provides the necessary values for testing the trip times of the sensitive earth fault overcurrent. The protection functions supported by this RIO function include: 50N,67N SEF The following RIO function for testing these distance protection functions is available: Overcurrent 8.2.19 Hi Z REF This RIO Hi Z REF block provides the necessary values for testing the trip times of the high impedance restricted earth fault. The protection functions supported by this RIO function include: 64 high impedance REF
The following RIO function for testing these distance protection functions is available: Overcurrent OMICRON PTL AREVA P34x XRIO Converter User Manual OMICRON electronics GmbH 16/16 8.3 Activating the RIO functions The RIO functions have to be set to active manually in each Overcurrent test module if the converter is used in the stand-alone mode. Activate the RIO function you intend to use in the local hardware configuration as shown below.
Figure 5: Activating a RIO function
8.4 Specific Features This section deals with special requirements of some of the converter's functions. Functions not listed here have no known limitations to their functionalities. 8.4.1 Not-Supported IDMT curves The converter doesnt support the Operating curves type IDG. 8.4.2 Phase / Neg Seq / Earth Fault / SEF Overcurrent For the successful phase overcurrent testing with the P34x converter, it is allowed to set only one stage as IDMT in each direction. The other stages should be set to DMT (ANSI Def. Time or IEC Def. Time). The IDMT stage must have the lowest pickup value!