1. SET POINT IS DEPENDENT ON THE TWO OPERATING MODES (LP MODE AND HP MODE).

ITEM NO.
SERVICE
DESIGN PRESS (barg)/(psig)
SIZE (mm)
2. FOR NITROGEN PURGING AND WATER FLUSHING.
3. MIN. DISTANCE BETWEEN GLOBE VALVE AND UPSTREAM VALVE IS 600 mm.
4. DELETED.
5. DRAIN ISOLATION VALVE TO BE LOCATED CLOSE TO THE HEADER.
6. MINIMUM LENGTH EQUAL TO THE MAXIMUM INTELLIGENT PIG LENGTH.
7. PRESSURE GAUGE TO BE FULL RANGE.
11. INLET SEPARATOR HIGH LIQUID LEVEL (SLUGGING) WILL CLOSE PCV-2010 DURING PIGGING.
9. TELLTALE VALVE TO CHECK ALL LIQUID IS DRAINED BEFORE OPENING THE END CLOSURE.
MATERIAL CS + 3mm CA
300 (MINOR) x 400 (MAJOR) BARREL
ORF PIG RECEIVER
R-2930
NOTE 9
8. STAND PIPE FOR FUEL GAS SUPPLY DURING START-UP.
10. LOCATE BYPASS LINE LINE AS CLOSE AS POSSIBLE TO THE ENTRY OF THE MAJOR BARREL.
DN300 x DN400
NOTE 10
NC
PG
2930
PG
N
O
T
E

3
2932
SIS
FPSO VIA WHP
V-2010
FALL
FB
TSO
CSC
FB
TSO
CSC
300-PG-2901-91XXXA
DN20
MOV MOV
DN20
2932 2931
LC
TSO
LC
NC
TSO
NC
TSO
TSO
NOTE 6
FALL 1:100
TO INLET SEPARATOR
LLlCN |L'l. (`C, 'AX.'lN.
HS HS
50-PG-2908-91492X
HS
MOV
2931 2932
ZI
2930
PZA
2936
GAS EXPORT FROM
R-2930
50-DC-6403-91492X
50-DC-6404-91492X
NC
NOTE 12
12. NON INTRUSIVE TYPE PIG SIGNALLER (CLAMP ON TYPE).
NOTES:
14. ESD VALVE PROVIDED WITH N2 BOTTLES FOR BACK-UP.
SDV
2930
FB
NOTE 14,28,34,41
PDG
NOTE 13
2933
PDG
2931
NOTE 13,19
91492X
91XXXA
91492X 11492X
TYPE 1
65/0
LC
DN20
NC
DN20
B-0602
B-10032
50-DC-6401-91492X
DN20
N2
N1 N4 I2
15. PIG RECEIVER TO BE SUITABLE FOR INTELLIGENT PIG.
2930
2930
B31.3
B31.8
91492X
91XXXA
B31.3
91492X
91XXXA
B31.3
B31.8
91XXXA
91492X
B31.8
B31.3
91492X
91XXXA
B31.3
B31.8
TSO
NOTE 12
N8
N7
I1
91XXXA
91492X
B31.8
B31.3
100 (1450)
B31.8
TSO
16. HV-2930 FOR PIPELINE MANUAL DEPRESSURISATION. TG-2930 PROVIDED FOR PIPE METAL SURFACE TEMPERATURE
B-0602
N5
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(psig) 41.4 (600)
24.3
NOTE 15
T&I ORF EPCC
CONTRACTOR CONTRACTOR
V-6060
FUEL GAS SCRUBBER
B-0604
50-PG-2904-91492X
NOTE 5,17
NOTE 9
SQC
2901
NOTE 9
VT-R2930-91492X TRIM NO.
SBT
2901
50-DC-6402-11492X
TO CLOSED
DRAIN HEADER
B-0608
17. VALVE TO BE OPENED ONLY AFTER RECEIVER IS DEPRESSURIZED.
300-PG-2902-91492X
LO
M
IN
.
SIS
BDV
2930
50-PG-2911-91492X
PCV
2010
NC NC
NC
NOTE 11 RO
2930
NC
NC
NOTE 7
N3
NC
N6
NC
DN20
NOTE 7
91492X
6
0
0
m
m
11492X
91492X
250-VH-6201-11492X
TO
N
O
T
E

3
11492X
NC
LL
30 barg
SET @
5
0
-
P
G
-
2
9
0
6
-
9
1
4
9
2
X
NC
200-PG-2905-91492X
PIA
2935
H
L
PG
2934
NOTE 2
300-PG-2907-91492X
FALL
DN20
DN20
FB
TG
2930
HV
2930
NOTE 16
FB
NC
11492X 91492X
DN20
NC
NC
LC
1
5
0
-
P
G
-
2
9
1
0
-
9
1
4
9
2
X
NOTE 18
50-PG-2903-91492X
MONITORING DURING DEPRESSURISATION. TG-2930 TO BE VISIBLE FROM HV-2930.
18. PIG RECEIVER SHALL BE PROVIDED WITH QUICK OPENING CLOSURE WHICH IS EQUIPPED WITH MECHANICAL INTERLOCK.
50-VH-6223-11492X
FB
LC LC
LC
1
5
0
-
P
G
-
2
9
1
3
-
9
1
4
9
2
X
N
O
T
E

8
2
0
0
0
m
m
M
IN
.
NC
NC
MIN.
600mm
M
IN
.
6
0
0
m
m
FALL
F
A
L
L
DN50
TSO
DN50
BARRED TEE
19. PRESSURE DIFFERENTIAL GAUGE SHOULD BE VISIBLE FROM DRAIN VALVES AND RECEIVER END CLOSURE.
50-PG-2914-91492X
TYPE 3
20. PG-2938 SHALL BE VISIBLE FROM GLOBE VALVE.
PG
2938
NOTE 20
NOTE 20,24,26
NC
DN20
NC
DN20
21. TO BE LOCATED IN AN ACCESSIBLE LOCATION WITH 2.5M CLEARANCE FOR REMOVAL.
SC
SSC
2901
CC
SCC
2901
CP
SCP
2901
NOTE 21
ZI
2931
22. VALVE TO BE PROVIDED WITH MECHANICAL STOPPER TO LIMIT MAXIMUM OPENING AT CV OF 292.
NOTE 22
B31.8 ASME Vlll
13. PRESSURE DIFFERENTIAL GAUGE SHALL BE INSTALLED AND LOW PRESSURE SIDE TO
23. 50 mm SPARE NOZZLE.
24. GLOBE VALVE'S CV, SHALL BE EQUAL OR LESS THAN PCV-2010. MECHANICAL STOPPER OR REDUCED TRIM IMPLEMENTATION
LC
N9
NOTE 23
NOTE 25
25. REFER TO WHP'S P&ID.
DN50
300x150 300x150
LC
DN20
NC
TSO
SQC
2902
NC
NOTE 27
DN50
TSO
DN50
DN50
NOTE 26
FB
TSO
HS
2933
26. OPERATOR SHALL MAKE SURE THAT MANUAL VALVES ON BYPASS LINE ARE CLOSED PRIOR TO PCV-2010 OPENING.
27. UTILITY CONNECTION TO BE BLINDED DURING NORMAL OPERATION.
28. SDV-2930 SHALL BE CLOSED IN 10 SECONDS.
300x200 300x200
29. DELETED.
NOTE 30
30. MOV-2930 WILL BE INTERLOCKED WITH PIA-2935 TO INHIBIT MOV-2930 OPENING IF INCOMING PIPELINE PRESSURE IS
MORE THAN 55 BARG.
VX-2914 VX-2915
VX-2916
VX-2918
VX-2919
VX-2901
VX-2902
VX-2903
VX-2904
VX-2905
VX-2906
VX-2907 VX-2909
VX-2908
VX-2912
VX-2913
VX-2910 VX-2911
VX-2930 VX-2931
VX-6202
VX-6201
VX-6407
VX-6408
VX-6405
VX-6406
VX-6403
VX-6404
VX-2923
VX-2917
VX-2924
VX-2925
VX-2935
VX-2921
VX-2936
VX-2920
VX-2926
VX-2922
VX-2929 VX-2928
MOV
2933
VX-2927
UG
AG
I.G
AG
UG
VX-2937
LO
FB
NC
DN20
VX-2939
VX-2938
PSV
2930
FB
VX-2940
LO FALL
50-PG-2916-91492X
SIZE : 1.5D2
SET@ 100 barg
CASE : FIRE CASE
N10
FALL
TSO
LC
TSO
SELECTOR
FROM HIGHER
MIN.
600mm
RO
2931
NOTE 16
LC
TSO
BE CONNECTED TO ATMOSPHERE.
31. DELETED.
32. DELETED.
TO BE CONFIRMED UPON CONFIRMATION ON THE MAXIMUM CV.
50-PG-2909-91492X
1
0
0
-
V
H
-
6
2
2
5
-
1
1
4
9
2
X
5
0
-
V
H
-
6
2
0
2
-
1
1
4
9
2
X
NOTE 1,40
35 barg
SET @
NOTE 1,30
42.5 barg
SET @
NOTE 34
NOTE 34 NOTE 34
NOTE 35
DRIP PAN
AG
UG
50-DH-6501-17161X
TO HAZARDOUS
OPEN DRAIN HEADER
B-0612
FALL
NOTE 36,43
33. SAMPLE CONNECTION SHALL BE LOCATED AT 6 O'CLOCK POSITION OR USING LONG
34. VALVE SHALL BE PIGABLE (API 6D).
35. VENT OR DRAIN HYDROTEST.
36. FLANGE CONNECTION TO PIPING CLASS 17161X SHOULD BE FLAT FACE TYPE
NOTE 33
LC
DN20
VX-2932
37. FROM EVERY SDV, BDV AND CONTROL VALVES INSTRUMENT GAS VENT LINE.
B-0607
DISTRIBUTION HEADER
50-GI-5821-13411X
FROM INSTRUMENT GAS
DN20 DN20
NOTE 38
38. PROCESS CONNECTION FOR INSTRUMENT AT INCOMING PIPELINE TO BE DN50.
39. PSV SIZE TO BE CONFIRMED BY VENDOR.
VX-5850 VX-5851
NOTE 39
TO FLARE HEADER
B-0609
FC
40. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
41. FINAL ELEMENT IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
42. THE ENTIRE BDV 2930 ASSEMBLY INCLUDING VALVE BODY, ACTUATOR AND ELECTRONIC
SHALL BE SIL 2 CERTIFIED.
NOTE 41,42
NOTE 37
B-0609
TO VENT HEADER
50-VH-6230-11492X
BY PIPING
BY INSTRUMENT
91492X 31492X 11492X
QUILS IN 12 O'CLOCK POSITION.
43. DRIP PAN COVERS OPENING OF PIG RECEIVER.
IF
150x250
50x40
50x100
DN20
91XXXA
91492X
B31.8
B31.3
NC
VX-6401
VX-6402 LC
TSO
TP
001
44. UTILITY CONNECTION FOR FLUSHING CONNECTION.
VX-2942 VX-2943 VX-2944
DN20
NC
DN20
NC
DN20
NC
NOTE 44
2. PG-2013 HAS TO BE READABLE FROM GLOBE VALVE.
1. NOZZLE FOR VENTILATION DURING VESSEL ENTRY, TO BE LOCATED AS FAR AS POSSIBLE
PIG RECEIVER R-2930
300-PG-2902-91492X
B-0601
600
INLET SEPARATOR
V-2010
46.5 (674.3)
65/-45
38.5 (558)/24.5 (355)
ITEM NO.
SERVICE
TYPE
DESIGN PRESS. (barg)/(psig)
MATERIAL
LLlCN |L'l. (`C, 'AX.'lN.
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(psig)
HORIZONTAL
23-14
LTCS + 3mm CA + INTERNAL LINING
SIZE (mm) 2850 (ID) x 7200 (T/T)
350x250
250-PG-2002-31492X
TO LIQUID BURNER
B-0619
DRAIN HEADER
TO CLOSED
B-0608
50-DC-6407-11492X
3. UTILITY CONNECTION TO BE BLINDED DURING NORMAL OPERATION.
4. 100mm SPARE NOZZLE.
NO POCKETS
A-6310
METERING PACKAGE
TO SALES GAS
B-0603
A-2610
LC
NC
11492X
31492X
TYPE 3
V-2010
N4
N3
I1B
I1A
N2
I3B
I3A
LZA
2013
HH
SCRUBBER
TO FUEL GAS
B-0604
V-6060
50-PG-2006-31492X
N7 N6
1
0
0
-
P
G
-
2
0
0
7
-
3
1
4
9
2
X
FB
ILO
I2B
I2A
LZA
2012
LL
1
5
0
-
P
G
-
2
0
0
5
-
3
1
4
9
2
X
PZA
2011
NOTE 23
N1
M
IN
.
6
0
0
m
m
I5 I4
LO
N5
50-DC-6405-31492X
NC DN20
50-DC-6406-31492X
INSTRUMENT DRAINS (TYP.)
NOTE 4
MH1
50-VH-6207-11492X 200-VH-6206-11492X
LEVEL SETTINGS
LZAHH
LAH
VESSEL BOTTOM (ID)
LAL
LZALL
DATUM:
0.0
NLL
1700
1500
550
350
250
11492X
31492X
SIS
SIS
SIS
LCV
2010
SDV
2011
SDV
2012
PG
2014
BDV
2010
PG
2013
SDV
2010
RO
2010
LG
2011
TRIM NO. VT-V2010-31492X
N8
SIS
NC
INSTRUMENT
PIPING
FALL
80x50
LC LC
NC
N9
4M6 SIZE
CASE
:
: BLOCKED
DISCHARGE
DN20
NC
FB
ILO
M
IN
.
6
0
0
m
m
FROM
LL
19 barg
SET @
50-PL-2030-31492X
NC
DN20
NC
OPEN DRAIN HEADER
TO HAZARDOUS
B-0612
50-DH-6502-17161X
FALL
LICA
2010
250x400
200-VH-6204-11492X
50-PG-2008-31492X
FB
100x200
FB
DN50
NOTE 1
H
NOTE 5
FALL
31492X 11492X
NC
SQC
2001
NC
DN50
50-DC-6408-31492X
NC
NOTE 2
F
A
L
L
NOTE 6
FROM MANWAY.
6. LOCAL LEVEL INDICATOR TO BE VISIBLE FROM BYPASS VALVE.
7. AUTO RESET.
13. 2 OUT OF 3 VOTING ON PZAHH-2015A/B/C IMPLEMENTATION, AS PER IPF REVIEW RECOMMENDATION. 50-PL-2031-31492X
NOTE 7, 26
PZA
2015A
HH
250-PG-2001-31492X
31492X 91492X
FB
ILO
4M6 SIZE
CASE
:
: BLOCKED
SET @ 46.5 barg
DN20
NC
FB
ILC
200-VH-6203-11492X
150-PG-2004-31492X
FALL
DN20
5. INLET SEPARATOR HIGH LIQUID LEVEL (SLUGGING) WILL OVERRIDE PICA-2014 AND WILL CLOSE
F
A
L
L
9. DELETED.
TO PCV-2010
B-0601 <
NOTE 8, 27
PCV-2010.
8. SDV-2012 SHALL BE CLOSED IN 10 SECONDS.
FALL
PICA
2014
2
5
0
-
P
G
-
2
0
0
3
-
3
1
4
9
2
X
PCV
2014
DN50
11492X
31492X
DN20
NC
300-VH-6205-11492X
H
NOTE 15, 26
QIA
2010
BTU ANALYZER
H
NOTE 10
NOTE 14,17
NOTE 7,15,16,27
NOTES:
10. VALVE TO BE PROVIDED WITH MECHANICAL STOPPER TO LIMIT MAXIMUM OPENING AT CV OF 202.
11. DELETED.
80-PL-6302-31492X
NOTE 6
80x40 50x40
12. DELETED.
I6
VX-2001
VX-2003
VX-2002
VX-2005
VX-2004
VX-2006
VX-2007
VX-2008
VX-2010
VX-2009
VX-2011
PZA
2015B
HH
I7
PZA
2015C
HH
I8
NOTE 13, 26
VX-2016
VX-6411
VX-6412
VX-2015
VX-2013
VX-2014
VX-2012
VX-6413
VX-6414
VX-6410
VX-6409
14. LEAKAGE CLASS OF LCV-2010 SHALL BE ANSI CLASS IV AS MINIMUM.
15. SDV-2011 LIQUID OUTLET AT V-2010 (INLET SEPARATOR) SHALL NOT BE CLOSED ON
HIGH HIGH LEVEL ALARM ON INLET SEPARATOR (LZAHH-2013) DURING PIGGING AS PER IPF REVIEW RECOMMENDATION.
16. SDV-2010 AND SDV-2011 (WHOLE ASSEMBLY) SHALL BE SIL 2 CERTIFIED AND TESTING INTERVAL SHALL BE DONE EVERY 12 MONTHLY.
HH
@42.5
SET
barg
@42.5
SET
barg
@42.5
SET
barg
VX-2037
VX-2036
VX-2031
VX-2032
VX-2033 VX-2034
VX-2035
N10
LC VX-6470
50-DC-6434-31492X
I.G.
AG
UG
HS
SET @
39 barg
2014
17. THE VALVE WILL UNDERGO CONTINUOUS FLASHING DURING PIGGING OPERATION.
MIN.
600mm
18. PERMANENT VENT/DRAIN ON HIGH/LOW POINT TO BE PROVIDED BY ORF EPCC CONTRACTOR FOR OPERATION/MAINTENANCE.
LC
DN20
VX-2933
LC
DN20
VX-2050
NOTE 19
NOTE 19
LC
DN20
VX-2051
19. VENT OR DRAIN.
20. FLANGE CONNECTION TO PIPING CLASS 17161X SHOULD BE FLAT FACE TYPE.
21. FROM EVERY SDV, BDV AND CONTROL VALVES INSTRUMENT GAS VENT LINE.
GWR GWR
DRIP FLOOR
AG
UG
NOTE 20
B-0607
DISTRIBUTION HEADER
50-GI-5806-13411X
FROM INSTRUMENT GAS
DN20 DN20
22. PSV SIZE TO BE CONFIRMED BY VENDOR.
NOTE 22
NOTE 22
VX-5852 VX-5853
B-0609
HEADER
TO FLARE
FALL
FC
FC
BY PIPING
BY INSTRUMENT
B-0609
TO VENT HEADER
50-VH-6231-11492X
NC
DN20
VX-6901
NC
DN20
VX-6902
NC
DN20
VX-6903
L
1300 BTU/scf
SET @
950 BTU/scf
SET @
NOTE 2
23. THE CALCULATION OF GROSS HEATING VALUE (MASS BASED).
250X200
300X200
NOTE 21
L
31492X 11492X
PSV
2010B
PSV
2010A
31492X 11492X
NOTE 24
24. SAMPLE CONNECTION SHALL BE LOCATED AT 6 O'CLOCK POSITION OR USING LONG
SC
SSC
2902
NOTE 25
26. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
27. FINAL ELEMENT IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
28. THE ENTIRE BDV 2010 ASSEMBLY INCLUDING VALVE BODY, ACTUATOR AND ELECTRONIC
SHALL BE SIL 2 CERTIFIED.
DISCHARGE
SET @ 46.5 barg
25. TWO DISSIMILAR CHECK VALVES TO BE INSTALLED.
QUILS IN 12 O'CLOCK POSITION.
NOTE 28
NOTE 13, 26 NOTE 13, 26
NOTE 26
150x200
150x200
29. KEY INTERLOCKING PSV SHOWN WITH ASTERISK :
VX-2053
VX-2052
150x100
150x100
DN20
NC
DN20
NC
TO LIQUID BURNER
B-0619
A-6310
DN20
NC
VX-2054
50-PG-6029-31492X
SIS
SDV
6063
TYPE 2
PACKAGE
TO LIQUID BURNER
30. SPOOL PIECE FOR FUTURE CONNECTION, CLOSE TO METERING.
RS
HS
2612
HS
2613
HS
2616
HS
2617
2. METERING TO BE FISCAL METERING STANDARD.
1. ESD VALVE TO BE PROVIDED WITH N2 BOTTLES FOR BACK UP.
3. MINIMUM UPSTREAM AND DOWNSTREAM STRAIGHT PIPE LENGTH REQUIREMENT SHALL BE CONFIRMED
4. CONTROL PANEL IS LOCATED INSIDE METERING HOUSE.
5. ALL MOV LIMIT SWITCHES INDICATION SHALL BE REPEATED TO PMCS.
6. INTRUMENT SETPOINT TO BE REVIEWED AS PER SALES GAS PIPELINE OPERATING AND
DESIGN CONDITION.
7. DELETED.
8. DELETED.
BY VENDOR.
9. DELETED.
V-2010
B-0602
SALES GAS METERING PACKAGE
A-2610
46.5 (674.3)
65/-18
38.5 (558)/24.5 (355)
ITEM NO.
NAME
DESIGN PRESS. (barg)/(psig)
LLlCN |L'l. (`C, 'AX.'lN.
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(psig)
22.8 - 13.2
250-PG-2912-31492X
FROM INLET SEPARATOR
250-PG-2002-31492X
MATERIAL LTCS + 3mm CA
CAPACITY (MMscfd) 77
NOTE 2
METER RUN #1
METER RUN #2
A-2610
M
IN
.

6
0
0
m
m
PT
2610
TT
2610
TW
2610
PG
2610
FT
2610
DUTY
NOTE 3
"STANDBY"
NOTE 3
TW
2611
PG
2611
NC
LC
MOV
2617
M
IN
.

6
0
0
m
m
NC
LC
NC
MOV
2614
FB
MOV
2610
TP
010
MOV
2611
NC
MOV
2615
DN20 NC
DN20
NC
FB FB
NC
FB
PZA
2942
LL
15 barg
TP
003
FB
DRIP PAN
DN50
F
A
L
L
SSV
2601
DN20
NC
SSV
2602
FALL
FALL
DN50
DN20 NC
11492X 31492X
TP
011
PZA
2940
40 barg
SET @
HH
SET @
SSC
SC
2601
NC
3
1
4
9
2
X
1
1
4
9
2
X
3
1
4
9
2
X
1
1
4
9
2
X
HS
2941
2902
SCC
2902
SCP
TSO
VX-6201VX-6202
VX-6203VX-6204
VX-6205
VX-6206
VX-2018 VX-2019
VX-2020
VX-2022
VX-2021
VX-2030
VX-2029
VX-2024 VX-2025
VX-2023
VX-2028 VX-2026
VX-2027
MOV
2941
VX-2038
VX-2040
AG
UG
AG
UG
I.G.
AG
UG
PZA
2941
40 barg
SET @
HH
CC CP
FLANGE CONNECTION
NOTE 12
2613
AT
AE
2612
AT
2611
AT
AE AE
2610
AT
AE
HC H2O GC1 GC2
2613 2612 2611 2610
NOTE 14
HC DEWPOINT
ANALYZER
FAULT
FAULT
GC-A USM-A
FAULT
USM-B
FAULT ANALYZER
MOISTURE
FAULT
FC-A
FAULT
FC-B
FAULT
C1 TO
AIA
2611
UA
2615
UA
2614
UA
2614
UA
2613
UA
2612
UA
2611
UA
2610
CONTENT
MOISTURE N2 CO SG
GHV
2
HC
DEWPOINT
H2O
DEWPOINT C6 FAULT
GC-B
UA
2616
C1 TO
C6
CO SG
GHV
AIA
2610
AI
2613
AI
2610
AI
2611
AIA
2612
AI
2612
AIA
2613
AI
2614
AIA
2615
AI
2615
AIA
2616
FIA
2610
TI
2610
PI
2610
FQI
2610
FIA
2611
TI
2611
PI
2611
FQI
2611
AIA
2619
AIA
2615
H2S H2S
H=0.01
AI
2616
E
N2
AIA
2614
C3 plus
H=10%
AIA
2617
C3 plus
H=10%
L=950
H=1270
L=950
H=1270 H=6.25
lb/mmscf Btu/scf
Btu/scf
Btu/scf
Btu/scf
grain/scf
H=0.01
grain/scf
H=5% H=5%
FALL
FALL
NOTES:
10. PERMANENT VENT/DRAIN ON HIGH/LOW POINT TO BE PROVIDED BY ORF EPCC CONTRACTOR
FOR OPERATION/MAINTENANCE.
11. DELETED.
B-0607
DISTRIBUTION HEADER
50-GI-5822-13411X
FROM INSTRUMENT GAS DN20 DN20
VX-5854 VX-5855
PIPELINES TO BE DN50 (PZT-2940/2941/2942).
12. PROCESS CONNECTION FOR INSTRUMENT AT INCOMING/OUTGOING
13. ONLINE RETRACTABLE SAMPLING PROBE
SAMPLING TAKE-OFF CONNECTION TO BE ON TOP OF PIPE.
14. SAMPLE CONDITIONING OF ANALYZER.
15. DELETED.
16. FROM EVERY SDV, BDV AND METERING PACKAGE GAS
VENT LINE.
2612
AIC
2611
FQI
2611
FX
2611
FX
2610
FQI
2610
FX
2610
FX
2610
TI
2610
FI
2610
PI
2611
FI
2611
PI
2613
AIC TI
2611
FI
2611A
FI
2611B
FI
2610A
FI
2610B
DN20 NC
VX-2055
NOTE 10
DN20 NC
VX-2054
2611 2612 2612
HS
2611
HS
2618
HS
2614
HS
2619
HS
2610
HS
2615
QI
2611
NOTE 17
17. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
18. FINAL ELEMENT IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
19. THE ENTIRE BDV 2020 ASSEMBLY INCLUDING VALVE BODY, ACTUATOR AND ELECTRONIC
SHALL BE SIL 2 CERTIFIED.
NOTE 20
20. FLANGE CONNECTION TO PIPING CLASS 17161X SHOULD BE FLAT FACE TYPE.
NOTE 13
19
NOTE 18NOTE 18
NOTE 18
IF
DN50
DN50
DN50
DN50
DN50 DN50
2610
QI
2610
DN20
TP
012
21. H2S ANALYZER SHALL BE INSTALLED WITH RETRACABLE PROBE AND CONNECTED TO THE FLOW COMPUTER.
22. SPOOL PIPE SHALL BE WET CALIBRATED TO PIGSAR GERMAN AS PER ACTUAL INSTALLATION TOTAL 25D
(UPSTREAM 10D, USM 10D AND DOWNSTREAM 5D).
23. HEAT TRACING SHALL BE INSTALLED TUBING BUNDLE FROM A TUBING MANUFACTURE.
ALL THESE SUPPLEMENTARY REQUIREMENT SHALL BE POWERED DIRECTLY FROM CONTROL PANEL.
NOTE 21
N
O
T
E

2
3
NOTE 22
1. COMMON DRIP PAN TO COVER ENTIRE FUEL GAS AT PACKAGE AREA.
SIS
SIZE (mm)
LLlCN |L'l, (`C, 'AX.'lN.
DESIGN PRESSURE (barg)/(psig)
SERVICE
ITEM NO.
LC
PZA
6062
LL
VENT/PURGE
TO FLARE OF
FILTER SEPARATOR
TO FUEL GAS
ILO
FB
LG
6060
LZA
6061
HH
NC
H
LICA
6060
L
50-DC-6410-13411X
TO CLOSED
INLET SEPARATOR
INTERNAL
MATERIAL
TG
6061
PICA
6060
PSV
6060A
TG
6060
V-6060
SDV
PG
FB
ILO
PZA
HH
6061
SET @
5
0
-
F
G
-
6
0
1
3
-
9
3
4
1
1
X
50-DH-6504-17161X
TO HAZARDOUS
OPEN DRAIN HEADER
DRIP PAN
6060
6060
SS316L
LTCS + 3 mm CA
65/-15
14 (203)
FUEL GAS SCRUBBER
V-6060
B-0602
B-0605
B-0605
B-0605
B-0612
80-VH-6212-11492X
50-FG-6004-13411X
LC
NC
H
L
PCV
6060A
PCV
6060B
LCV
6060
50-DC-6409-13411X
80-FG-6016-13411X
50-FG-6015-13411X
80-VH-6211-11492X
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(pisg)
TYPE 2
DN20
PIPING
INST
FROM LEVEL
INSTRUMENT DRAINS (TYP.)
600
12.5 barg
FROM
INCOMING PIPELINE
B-0601
50-PG-2904-91492X
FUEL GAS PACKAGE
A-6060
A-6060
FALL
50-VH-6213-11492X
SET @
6.5 barg
DRAIN HEADER
93411X 13411X
91492X 93411X
MH1
I1
I2
I3
N1
N2
I7
N4
I4A
I4B
I6A
N3
LAHH
LAH
BOTTOM TL
LEVEL SETTINGS
NLL
LAL
DATUM:
LC
NC
2. FUEL GAS SUPPLY FROM INCOMING PIPELINE DURING START-UP.
3. STAGGERED CONFIGURATION.
NOTE 3,6,9,12,24
S-6060A/B
FALL
DN20
NC
LZA
6062
I5A
I5B
SIS
SDV
6061
TYPE 2
DN20 NC
FALL
NOTE 1
NC
50-FG-6002-93411X
DN20 NC
31492X 91492X
0
-
5
0
%
5
1
-
1
0
0
%
DN20
NC
NOTE 2
4. ONLY FUNCTIONAL REQUIREMENTS ARE SHOWN WITHIN PACKAGE. VENDOR SHALL RESPONSIBLE
FROM
50-PG-2006-31492X 50-FG-6001-91492X
DN20 NC
50-FG-6003-13411X
SIZE
CASE
SET @ 14 barg
5
0
-
P
L
-
6
0
5
0
-
1
3
4
1
1
X
8
0
-
F
G
-
6
0
1
4
-
1
3
4
1
1
X
M
IN
.
6
0
0
m
m
PSV
6060B
SIZE
CASE
: 2H3
: FIRE
SET @ 14 barg
FB
ILC
DN20
NC
ILO
FB
LL
FALL
NC
N5
DN20 NC
(NOTE 4, 8)
TP
017
TP
016
FOR DETAIL DESIGN OF THE PACKAGE.
LO
F
A
L
L
TYPICAL
DN20
NC
NC
TRIM VT-V6060-11492X
5. AUTO RESET.
NOTE 5,
FUEL GAS
FILTER SEPARATOR
1
3
4
1
1
X
1
1
4
9
2
X
6. 2X100% CONTROL VALVES.
7. DELETED.
8. UTILITY CONNECTION TO BE PROVIDED WITH CAMLOCK (FEMALE) TYPE.
NOTE 5,11,20
9. PCV-6060A/B SHALL BE EQUIPPED WITH SOLENOID VALVE AS PER IPF REVIEW
: 2H3
: FIRE
10. DELETED.
VX-6003
VX-6002
VX-2934
VX-2933
VX-2990
NOTE 11, 20
VX-6008
VX-6009
VX-6010
VX-6005
VX-6004 VX-6006
VX-6007
VX-6011
VX-6012
VX-6015
VX-6014
VX-6017
VX-6016
VX-6209
VX-6208
VX-6210
VX-6207
VX-6415
VX-6018
VX-6019
VX-6419
VX-6417
VX-6418
VX-6416
11. SDV-6060 AND SDV-6061 (WHOLE ASSEMBLY) SHALL BE SIL 2 CERTIFIED AND TESTING
INTERVAL SHALL BE DONE EVERY 12 MONTHLY.
VX-6078
AG
UG
SET @ 10.4 barg
SET @ 10 barg
12. DURING START UP FROM SETTLE OUT PRESSURE (INCOMING LINE PRESSURE OF 55 BARG) THE FUEL GAS
|L'lLlA|UlL WlLL EL '.3`C.
NOTE 13
DN20 NC
VX-6084
DN20 NC
VX-6085
NOTES:
13. INSULATION GASKET TO BE INSTALLED AT EVERY NOZZLE FOR DISSIMILAR METAL.
14. INSULATION GASKET TO BE INSTALLED AT PSV INLET.
NOTE 14,21
NOTE 14,21
DN20 LC
VX-2017
I6B
NOTE 16
15. DRAIN OR VENT FOR HYDROTEST.
16. FLANGE CONNECTION WITH PIPING CLASS 17161X SHOULD BE FF TYPE.
17. FROM EVERY SDV, BDV AND CONTROL VALVES INSTRUMENT GAS VENT LINE.
B-0607
DISTRIBUTION HEADER
50-GI-5825-13411X
FROM INSTRUMENT GAS
DN20 DN20
18. DELETED.
VX-5856 VX-5857
BY PIPING
BY INSTRUMENT
B-0609
TO VENT HEADER
NOTE 17
50-VH-6233-11492X
FC
FC
FC
SET @
12 barg
SET @
7 barg
NC
DN20
VX-6905
NC
DN20
VX-6906
NC
NC
VX-6421
VX-6420
VX-6422
MIN.
600mm
13411X 11492X
13411X 11492X
33411X
13411X
19. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
20. FINAL ELEMENT IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
10.38 (151)
2.8-3.8 (NOTE 12)
1800 (ID) X 4500 (T/T)
33411X
13411X
500
400
350
300
NOTE 19
NOTE 19
NOTE 19
19
21. DELETED.
50x40 40x50
50x40 40x50
50x80
50x80
50x40
50x40
22. PIPE SHALL BE SWAGGED UP TO DN100.
VX-6001
LALL 200
23. KEY INTERLOCKING PSV SHOWN WITH ASTERISK :
RECOMMENDATION.
24. CONTROL VALVE BODY SIZE SHALL BE BIGGER THAN 50% OF (I.D.) PIPE SIZE.
NOTE 3,6,9,12,24
ON/OFF
NOTE 8
N6
SQC
6001
NC
DN50 DN50
VX-6013
VX-6079
50-PL-6059-13411X
1. TELLTALE VALVE TO CHECK FILTER IS FULLY DEPRESSURISED BEFORE OPENING FILTER
S-6060A/B
FUEL GAS FILTER SEPARATOR
14 (203)
65/-15 LLlCN |L'l. (`C, 'AX.'lN.
DESIGN PRESSURE (barg)/(psig)
SERVICE
ITEM NO.
MATERIAL LTCS + 3mm CA
PG
6061
FB
LO
LC
NC
FALL
NOTE 1 NOTE 1
PG
NC
LC
FB
LO
LC
FALL
6063
DRAIN OF INSTRUMENT
TO CLOSED
PSV
6061
50-PL-6053-13411X 50-PL-6057-13411X
S-6060B S-6060A
50-FG-6004-13411X
NC
B-0606
B-0607
50-VH-6215-11492X
50-FG-6019-13411X 50-FG-6017-13411X
6002
SAD
6004
SAD
5
0
-
F
G
-
6
0
1
8
-
1
3
4
1
1
X
5
0
-
F
G
-
6
0
2
0
-
1
3
4
1
1
X
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(psig) 9.7 (141)
2.3-3.3 (NOTE 4)
2. LEVEL SWITCH IS INTEGRAL WITH LEVEL GAUGE.
(MIN.)
600mm
(MIN.)
600mm
V-6060
FUEL GAS SCRUBBER
B-0604
TO FUEL GAS
SUPERHEATER
B-0606
5
0
-
F
G
-
6
0
0
7
-
1
3
4
1
1
X
50-FG-6006-13411X
50-FG-6005-13411X
FROM FLARE OF
FUEL GAS SCRUBBER
B-0604
80-VH-6211-11492X
SUPERHEATER
FROM CLOSED DRAIN
OF FUEL GAS SCRUBBER
B-0604
50-DC-6409-13411X
I3
N5
N3
N2
I3
N5
I4A
I2
N3
N2
PSV
6062
NC
SIZE
CASE
: 1D2
: FIRE
SET @ 14 barg
FROM
5
0
-
P
L
-
6
0
5
4
-
1
3
4
1
1
X
SIZE
CASE
: 1D2
: FIRE
SET @ 14 barg
5
0
-
P
L
-
6
0
5
8
-
1
3
4
1
1
X
FUEL GAS PACKAGE
A-6060
A-6060
DN20
NC
DN20
NC
TYPICAL
DN20
NC
FB
LO
DN20
NC
FB
LO
TRIM VT-S6060-11492X
TO FLARE OF FUEL GAS
50-VH-6224-11492X
1
1
4
9
2
X
1
3
4
1
1
X
3. DELETED.
50-VH-6226-11492X
1
1
4
9
2
X
1
3
4
1
1
X
F
A
L
L
50-VH-6214-11492X
F
A
L
LVX-6211
VX-6212
VX-6213
VX-6021
VX-6020
VX-6029
VX-6022
VX-6024
VX-6026
VX-6423
VX-6027
VX-6214
VX-6215
VX-6216
VX-6031
VX-6030
VX-6032
VX-6033
VX-6036
VX-6038
VX-6429
VX-6039
4. DURING START UP FROM SETTLE OUT PRESSURE (INCOMING LINE PRESSURE OF 55 BARG)
|HL lULL CA |L'lLlA|UlL WlLL EL '.3`C.
NOTE 5 NOTE 5
NOTE 6
NOTE 6
5. INSULATION GASKET TO BE INSTALLED AT EVERY NOZZLE FOR DISSIMILAR METAL.
6. INSULATION GASKET TO BE INSTALLED AT PSV INLET.
REMOVAL EFFICIENCY
99.9% OF > 0.3 PARTICLES
99.98% OF > 1 AEROSOL
NOTE 7 NOTE 7
7. PROVIDE SWING DAVIT ON THE OPENING OF THE FILTER.
SIZE (mm) 273 (OD) x 2845 (S/S)
33411X
13411X
13411X 11492X 13411X 11492X
8. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
33411X
13411X
50x25
LG
6064
LSA
6065
H
NOTE 2
N7
50-FG-6024-13411X
VX-6040
N1
LG
6068
LSA
6069
H
NOTE 2
N7
50-FG-6022-13411X
I2
VX-6081 VX-6080
50x25 50x25
GAS RECEIVER
LG LSA
6066 6067
LSA LG
6062
H
6063
H
NOTE 2 NOTE 2
I1B
I1A
I1B
I1A
PDG
6061
LC
LC
PDIA
6062
50-FG-6021-13411X
5
0
-
P
L
-
6
0
5
1
-
1
3
4
1
1
X
H
50-DC-6411-13411X
SAD
6001
5
0
-
D
C
-
6
4
1
2
-
1
3
4
1
1
X
I4A
N6
N4
I4B
DN20
NC
NC
VX-6028 VX-6023
VX-6420
VX-6025
VX-6425
VX-6424
SET @
0.69 bar
PDG
LC
6064
PDIA
6065
5
0
-
P
L
-
6
0
5
5
-
1
3
4
1
1
X
50-FG-6023-13411X
50-DC-6414-13411X
6003
SAD
H
5
0
-
D
C
-
6
4
1
5
-
1
3
4
1
1
X
I4A
N6
N4
N1
I4B
5
0
-
P
L
-
6
0
5
6
-
1
3
4
1
1
X
DN20
NC
NC
VX-6035
VX-6426
VX-6034
VX-6037
VX-6431
VX-6430
SET @
0.69 bar
ENCLOSURE.
50x40
50x25
50x40
INSTRUMENT DRAINS
CONNECTION FROM
NC
50-DC-6416-13411X
PIPING
INST
DN20 NC
VX-6427
VX-6428
NC
DN20
VX-6907
50-PL-6052-13411X
50-DC-6413-13411X
NC
INSTRUMENT DRAINS
CONNECTION FROM
DN20 NC
VX-6422
VX-6421
PIPING
INST
NC
DN20
VX-6910
50x25 50x25
50x25
50x25
50x25 50x25
50x25
50x25
50x25
50x25 50x25
50x25
FILTER ELEMENT SIZE (mm) 139.7 (OD) x 914.4 (L)
9. INSTRUMENT DRAIN FROM LG-6070.
NOTE 8
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
NOTE 8
1. TEMPERATURE SET POINT TO BE CONFIRMED BY MICROTURBINE VENDOR.
ITEM NO.
SERVICE
DESIGN PRESSURE (barg)/(psig)
LLlCN |L'l. (`C, 'AX.'lN. 100/-15
14.0 (203)
FUEL GAS SUPERHEATER
E-6060
HEATER
CONTROL
LOGIC
MIN. FILTER SEPARATOR
E-6060
HH
MATERIAL
POWER REQ. (kW)
LTCS + 3mm CA
PSV
6063
50-FG-6005-13411X
B-0607
B-0605
5
0
-
F
G
-
6
0
2
7
-
1
1
4
9
2
X
TYPE 1
LC
50-FG-6026-13411X
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(psig) 9 (131)
2.3-3.3/52 (IN/OUT) (NOTE 9)
NC
FROM FUEL GAS
TICA
6066
H
L
LL
FB
LO
FB
LO
DN20
NC
80-VH-6211-11492X
FUEL GAS FILTER SEPARATOR
FROM FLARE OF
50-VH-6216-11492X
INSTRUMENT
HH
B-0607
V-6070
RECEIVER
TO INSTRUMENT GAS
50-FG-6009-13411X
N1 N4 N5 N2
N3
50-FG-6025-13411X
FALL
FALL
TZA
6062
HH
TZA
6061
HEADER
CLOSED DRAIN
B-0608
FLARE IGNITION PANEL
PILOT GAS TO
B-0611
50-FG-6010-13411X
S-6060A/B
SIZE
CASE :
: 1D2
SET @ 14 barg
13.5
FUEL GAS PACKAGE
A-6060
A-6060
600mm
2. SET POINT TO BE CONFIRMED BASED ON MICROTURBINE GENERATOR'S VENDOR DATA (FUTURE).
3. DELETED.
PCV
6080
SET @
0.3 barg
LO
PG
6080
TYPICAL
DN50 SET @
DN50
S I S
SET @
XX `C
SET @
cD `C
LO
PCV
6064
SET @
8 barg
LO LO
DN20 NC
IH
NOTE 4
N6
NC
4. VESSEL INSULATION FOR HEAT CONSERVATION 25 mm.
INSULATION TYPE/THK
TRIM
HEAT CONSERV./IH-25
VT-E6060-11492X
NC
DN20
GAS RECEIVER
TO FLARE OF
HCP-6060
50-FG-6034-13411X
13411X 11492X
5. SHEATH MATERIAL: INCOLOY 800.
TP
019
B-0605
(NOTE 5)
6. DELETED.
7. SET POINT TO BE ADVISED BY SUPERHEATER VENDOR.
NOTE 7,19
018
TP
NC
50-FG-6037-13411X
NOTE 7,19
50-FG-6036-13411X-IH-25
NC
50-FG-6012-13411X
8. DELETED.
NOTE 8
NOTE 8
50x40 50x40
VX-6053 VX-6054
VX-6055
VX-6048 VX-6050
VX-6051
VX-6052
VX-6049
VX-6060
VX-6041
VX-6042
VX-6217
VX-6045
VX-6044
VX-6046
VX-6047
TI
6067
9. DURING START UP FROM SETTLE OUT PRESSURE (INCOMING LINE PRESSURE OF 55 BARG)
|HL lULL CA |L'lLlA|UlL WlLL EL '.3`C.
NC
50-FG-6032-13411X
NC
VX-6056
VX-6057
NOTE 11
PG
6064
NOTE 10
NOTE 12
VX-6043
NOTE 12 NOTE 12
XX `C
NOTE 12
NOTE 1
10. PG-6064 SHALL BE VISIBLE FROM PCV-6064 AND THE BYPASS VALVE.
NOTES:
11. PG-6080 SHALL BE VISIBLE FROM PCV-6080 AND THE BYPASS VALVE.
12. INSULATION GASKET TO BE INSTALLED.
NOTE 1,19
NOTE 1,19
SIS
PZA
6080
TG
6065
SDV
6062
TYPE 2
GENERATORS
B-XXXXX
DN20 NC
PICA
6063
H
L
HH
SET @
7 barg
TP
020
NOTE 2,19
TO MICROTURBINE
VX-6059
(FUTURE)
13. FROM PCV-6063, SDV-6062 AND SDV 6063 INSTRUMENT GAS VENT LINE.
VX-6090
5
O
-
F
G
-
6
0
3
8
-
1
3
4
1
1
X
-
IH
-
2
5
14. BLIND FLANGE SHALL BE PROVIDED.
15. FUTURE LINE.
NOTE 14
NOTE 15
BY PIPING
BY INSTRUMENT
NOTE 13
B-0609
TO VENT HEADER
50-VH-6234-11492X
SET @
2 `C
SET @
6.5 barg
SET @
5.7 barg
FICA
606O
33411X
13411X
NOTE 16
16. PROVIDED FOR FUTURE TEMPERATURE TRANSMITTER.
NOTE 17,18
L
TZA
6063
TZA
6064
VX-6094
VX-6093
VX-6092
VX-6095
VX-6091
NC
FC
PCV
6063
SET @
6 barg
NOTE 2
17. LOW ALARM FROM FICA-6060 WILL SHUTDOWN THE HEATER.
18. FLOW INSTRUMENT USE VORTEX TYPE.
13411X 11492X
NC
NC
NC
NC
FIRE
NOTE 6
19. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
50-FG-6040-13411X-IH-25
50-FG-6039-13411X-IH-25
50-FG-6041-13411X-IH-25
NOTE 21
50x25
NOTE 20
NOTE 20
NOTE 21
NOTE 21
NOTE 21
NOTE 21
50x40 50x40
20. PIPING INSULATION.
21. PIPING SHALL SWAGGED UP TO DN100.
DN20
FLARE HEADER
PURGE GAS TO
B-0609
VX-2946 VX-2947 VX-2948
VX-6416
NC
DN20
NC
DN20
NC
DN20
NC
DN20
VX-2949
NC
DN20
50-FG-6011-13411X
LIQUID BURNER
PURGE GAS TO
B-0619
VX-6061
VX-6062
NOTE 22
22. INSULATION GASKET TO BE INSTALLED AT EVERY NOZZLE FOR DISSIMILAR METAL.
VX-6044
23. CONTROL VALVE BODY SIZE SHALL BE BIGGER THAN 50% OF (I.D.) PIPE SIZE.
50x25
50x25
SET @
' `C
SET @
' `C
50-DC-6436-11492X
1. 2 OUT OF 3 VOTING ON PZALL IMPLEMENTATION.
V-6070
INSTRUMENT GAS RECEIVER
14 (203)
65/0
1950 (ID) x 4900 (T/T) SIZE (mm)
LLlCN |L'l, (`C, 'AX.'lN.
DESIGN PRESSURE (barg)/(psig)
SERVICE
ITEM NO.
MATERIAL CS + 3mm CA
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)/(psig) 9 (131)
52
DRAIN HEADER
TO CLOSED
B-0608
V-6070
B-0602
TO PIG RECEIVER
TO FLARE HEADER
B-0609
PCV
6070B
SET @
7 barg
PCV
6070A
50-GI-5802-13411X
SET @
LL
PZA
6071A
5 barg
NOTE 1,16
SET @
LL
PZA
6071B
5 barg
NOTE 1,16
SET @
LL
PZA
6071C
5 barg
NOTE 1,16
PIA
6070
H
L
LG
6070
NC
50-DC-6418-11492X
80-VH-6219-11492X
FB
LO
8
0
-
G
I-
5
8
0
7
-
1
3
4
1
1
X
NC
PG
6070
B-0606
50-FG-6009-13411X
SUPERHEATER
FROM FUEL GAS
FB
LO
600
50-GI-5806-13411X
E-6060
B-0606
80-VH-6211-11492X
FUEL GAS SUPERHEATER
FROM FLARE OF
80-VH-6218-11492X
NOTE 2,11,
NOTE 2,11,
SAD
2. 2x100% CONFIGURATION.
B-0605
50-DC-6409-13411X
CLOSED DRAIN HEADER
FROM
50-DC-6417-13411X
11492X 13411X
N4
N1
N3
I2A
N6
I1
N2
N5
50-GI-5808-13411X
50-GI-5801-13411X
6401
3. CONNECTION FOR NITROGEN DURING BLACK START.
TO INLET SEPARATOR
B-0601
B-0603
TO METERING SYSTEM
LC
NC
NC DN20
FALL
LC
SIZE
CASE
: 1.5G3
: FIRE CASE
SET @ 14 barg
SET @
7.5 barg
5
0
-
G
I-
5
8
1
0
-
1
3
4
1
1
X
A-6060
FUEL GAS PACKAGE
A-6060
TP
021
TP
022
FALL
50-VH-6217-11492X
MH1
50-DC-6430-13411X
TP
023
MIN.
600mm
FALL
F
A
L
L
TYPICAL
B-0609
CYLINDER RACK
FROM NITROGEN
LC
NOTE 3 50-NT-5910-13411X
DN50 NC
NOTE 5
DN50
NOTE 4
DN20
NC
DN20 NC
PG
6071
TRIM VT-V6070-11432X
4. CONNECTION FOR FUTURE INSTRUMENT AIR SKID.
5. MAINTENANCE VENT.
11492X 13411X
6. UTILITY CONNECTION TO BE PROVIDED WITH CAMLOCK (FEMALE) TYPE WITH PLUG.
NOTE 8
RS
RS
7. IN CASE OF USING INSTRUMENT AIR INSTEAD OF INSTRUMENT GAS IN THE FUTURE, REMOVABLE
SPOOL SHALL BE REMOVED AND BLIND FLANGES SHALL BE INSTALLED.
8. TWO DISSIMILAR CHECK VALVES TO BE INSTALLED.
9. PROVISION FOR REROUTING PSV/VENT DISCHARGE LINE TO ATMOSPHERE IF INSTRUMENT AIR
NOTE 9
COMPRESSOR TO BE USED IN FUTURE.
10. PROVISION FOR REROUTING DRAIN LINE TO GRADE IF INSTRUMENT AIR TO BE USED IN FUTURE.
11. DELETED.
TP
004
VX-5922
VX-6218
VX-6219
VX-6220
VX-5802
VX-5801
VX-5903
VX-5902
VX-5901
VX-5809
VX-6061
VX-6066
VX-5810
VX-6064
VX-6065
VX-6432
VX-6433
VX-6435
VX-6434
VX-5811
VX-5803
VX-5806
VX-5805
VX-5808
VX-5804
VX-5807
VX-6436
I.G.
AG
UG
SET @ 8 barg
SET @ 6 barg
NOTE 13
NOTE 12
NOTE 14
NOTE 7
RS
12. PG-6071 SHALL BE VISIBLE FROM PCV-6070A/B.
NOTES:
13. INSULATION GASKET TO BE INSTALLED AT PSV INLET.
14. INSULATION GASKET TO BE INSTALLED AT EVERY NOZZLE FOR DISSIMILAR METAL.
FALL
FALL
TO OILY WATER TREATMENT
50-GI-5804-13411X
B-0614
B-0613
TO OPEN DRAIN SYSTEM
TO LIQUID BURNER
50-GI-5805-13411X
B-0619
TO CLOSED DRAIN SYSTEM
B-0610
50-GI-5821-13411X
50-GI-5822-13411X
50-GI-5823-13411X
50-GI-5824-13411X
15. DELETED.
NOTE 15
33411X
13411X
13411X 11492X
16. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
80x40
50-NT-5909-13411X
TO FUEL GAS PACKAGE
B-0604
50-GI-5825-13411X
NC
DN20 NC
TO NITROGEN CYLINDER RACK
B-0609
VX-5890
DN20
VX-5891
50-GI-5850-13411X
50-GI-5851-13411X
6070
PSV
50x25
25x50
25x50
17. CONTROL VALVE BODY SIZE SHALL BE BIGGER THAN 50% OF (ID) PIPE SIZE.
NOTE 6
N7
SQC
6002
NC
DN50 DN50
VX-6062
VX-6063
50x40 40x50
50x40 40x50
17
NOTE 18
18. CONNECTION FOR INSTRUMENT DRAIN COMBINED TO FUEL GAS FILTER SEPARATOR'S
INSTRUMENT DRAIN LINE.
17
PIPING
INST
NC
DN20
VX-6760
INSTRUMENT DRAINS
CONNECTION FROM
50-DC-6436-13411X
1. UTILITY CONNECTION TO BE BLINDED DURING NORMAL OPERATION.
PIG RECEIVER
R-2930
B-0601
FROM
INLET SEPARATOR
B-0602
V-2010
B-0607
50-DC-6418-11492X
50-DC-6402-11492X
FLARE KNOCKOUT DRUM
V-6450
CLOSED DRAIN HEADER
FROM
FUEL GAS PACKAGE
A-6060
50-DC-6407-11492X
B-0610
FALL
FALL
FALL
100-DC-6421-11492X
50-DC-6419-11492X FALL
FROM OILY WATER
TREATMENT PACKAGE
B-0614
A-4410
FALL
NOTE 1
SQC
6401
FROM ORF
NC
TO CLOSED DRAIN/
DN50
50-DC-6432-11492X FALL
FROM SALES GAS
METERING PACKAGE
B-0603
A-2610
DN50
VX-6437
VX-6451
I.G.
AG
UG
SUPERHEATER
E-6060
B-0606
50-DC-6436-11492X FALL
FROM FUEL GAS
B-0610
FUEL GAS HEADER
B-0606
B-0601
FROM HCV-2930
RELIEF AND BLOWDOWN
FROM INLET SEPARATOR
B-0602
V-2010
B-0603
& SALES GAS
RELIEF FROM
FUEL GAS PACKAGE
B-0607
300-VH-6221-11492X
FLARE KNOCKOUT DRUM
TO CLOSED DRAIN/
50-FG-6012-13411X
300-VH-6205-11492X
80-VH-6209-11492X
80-VH-6219-11492X
V-6450
250-VH-6201-11492X
FALL
FALL
FALL
FALL
NOTE 1
SQC
6202
PURGE GAS FROM
FALL
FLARE HEADER
50-NT-5902-13411X
13411X
11492X
LO
MIN.
DN50
DN50
NC
50-FG-6031-13411X
FIA
6081
LO
LC
NC
PG
6083
LO
L
NOTE 2
LO
LO
NOTE 4
FROM BDV-2020
VX-5904
VX-5905 VX-5906
VX-6068
VX-6067
VX-6069 VX-6070
VX-6071
VX-6072
VX-6223
VX-6224
VX-6221
VX-6222
NOTE 2
NOTE 6
NOTE 3,5
SET @
0.5 Sm /h 3
FROM PIG RECEIVER B-0601
FROM INLET
B-0602
FROM SALES
B-0603
SCRUBBER
B-0604
FROM FUEL GAS
B-0606
FROM CLOSED
B-0610
FROM FUEL GAS
GAS METERING
SUPERHEATER
SEPARATOR
DRAIN SYSTEM
50-VH-6230-11492X
50-VH-6231-11492X
50-VH-6232-11492X
50-VH-6233-11492X
50-VH-6234-11492X
50-VH-6235-11492X
METERING PACKAGE
600 mm
MIN.
100-VH-6240-11492X
FALL
VENT HEADER
VA-6201
VX-5871
VX-5872
NC
NC
1. UTILITY CONNECTION TO BE BLINDED DURING NORMAL OPERATION.
2. PG-6083 TO BE VISIBLE FROM GLOBE VALVE LOCATION.
3. ROTAMETER TO BE INSTALLED IN VERTICAL POSITION WITH FLOW UPWARDS.
4. TWO DISSIMILAR CHECK VALVES TO BE INSTALLED.
5. DELETED.
6. INSULATION GASKET TO BE INSTALLED.
ITEM NO.
SERVICE
SIZE (mm)
VA-6201
VENT STACK
50 (ID) x 3500 (H) (VTA)
5901
5
0
-
N
T
-
5
9
0
4
-
1
3
4
1
1
X
A-5910
50-NT-5901-13411X
PCV
5911
PCV
5912
PCV
5913
PG
5916
PG
5915
PG
5914
PG
5913
PG
5912
PG
5911
PCV
5910
PG
5910
PCV
5914
PG
5918
PG
5917
PSV
5910
SET @
12 barg
AT SAFE LOCATION
TO ATM
ATM ATM ATM ATM
SET @
7 barg
SET @
12 barg
SET @
12 barg
SET @
12 barg
SET @
12 barg
FO
TYPICAL
SIZE: NOTE 8
CASE: CONTROL VALVE FAILURE
SQC
5910
50-NT-5905-13411X
NC
NC
TP
030
SQC
5903
SHF
5901
SQC
5902
SQC
5905
SHF
5902
SQC
5904
SQC
5907
SHF
5903
SQC
5906
SQC
5909
SHF
5904
SQC
5908
NOTE 8
50-NT-5906-13411X
XV
5910
SIS
NOTE 7
PCV
5919
SET @
0.3 barg
NOTE 13
LO
PG
5920
LO
NC
DN20
TO INSTRUMENT
B-0607
GAS RECEIVER
50-NT-5909-13411X
PMCS
5
0
-
N
T
-
5
9
1
1
-
1
3
4
1
1
X
TYPE 6
NOTE 13
VX-5908
VX-5910
VX-5909
VX-5914
VX-5915
VX-5916
VX-5917
VX-5918
VX-5919
VX-5920
VX-5921
VX-5923
VX-5924
VX-5925
VX-5926
NC
50-NT-5910-13411X
NC
VX-5911
VX-5912
NOTE 9
A-5910
NITROGEN CYLINDER RACK
NOTE 8
NOTE 8
ITEM NO.
SERVICE
DESIGN PRESS. (barg)/(psig)
LLlCN |L'l. (`C,
7. XV-5910 TO BE OPENED AUTOMATICALLY FROM SIS UPON LOW PURGE GAS FLOWRATE
8. VENDOR TO ADVISE.
FIAL-6081 WITH TIME DELAY.
9. PG-5920 SHALL BE VISIBLE FROM PCV-5919 AND THE BYPASS VALVE.
11. FROM XV-5910 INSTRUMENT GAS VENT LINE.
10. DELETED.
5
0
-
V
H
-
6
2
3
6
-
1
1
4
9
2
X
SQC
12. DELETED.
FO FO FO
13. REGULATOR SIZE TO BE ADVISED BY VENDOR.
NOTES:
VX-6081
NC
DN20
DN50
FROM INSTRUMENT GAS
50-GI-5851-13411X
DISTRIBUTION HEADER
VX-6801
B-0607
15. INSTRUMENT GAS TO XV-5910.
SQC
6203
DN50
DN50
NC
VX-5874
VX-5873
NOTE 1
B-0614
FROM OIL WATER
NC DN20
VX-5870
50x25 25x50
TREATMENT SYSTEM
BY PIPING
BY INSTRUMENT
14. DELETED.
DN50
DN20
50-VH-6241-11492X
1. 50mm NOZZLE FOR VENTING PRIOR TO VESSEL MAINTENANCE TO BE BLINDED OFF AND
V-6450
RS
PG
6450
LO
LO
50-DH-6507-11492X
LTCS + 3mm CA + INTERNAL COATING
12 (174)/FV
CLOSED DRAIN/FLARE KNOCK-OUT DRUM
MATERIAL
V-6450
SERVICE
ITEM NO.
SIZE (mm) 3000 (ID) x 7500 (T/T)
LEVEL SETTINGS
LZAHH
LAH
VESSEL BOTTOM
DATUM:
0.0
LG
6450
100-DC-6421-11492X
PSV
PSV
50-DC-6423-31492X
5
0
-
D
C
-
6
4
2
5
-
3
1
4
9
2
X
DRAIN HEADER
FROM CLOSED
DIFFERENTIAL PRESS. (bar)/(psi)
ITEM NO.
SERVICE
DESIGN PRESS. (barg)/(psig)
P-6460
LLlCN |L'l. (`C, 'AX.'lN.
CLOSED DRAIN TRANSFER PUMP
17 (246.5)
ABSORBED POWER (KW)
LLlCN |L'l. (`C, 'AX.'lN.
DESIGN PRESS. (barg/psig)
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)
AMB
5
0
-
D
H
-
6
5
0
9
-
1
1
4
9
2
X
6451
6452
FLARE HEADER
FROM
MAX HH 950
FLOWRATE (m3/hr)
300-VH-6221-11492X
HH
LZA
6451
LZA
6452
LL
H LICA
6450
L
PIA
6451A
H
L
PZA
6452A
HH
PZA
6452B
HH
PIA
6451B
H
L
PZA
6453A
LL
PZA
6453B
LL
80-DC-6424-11492X
DN20
SFS
6402
6403
SFS
PI
6450
6450A 6450B
FX
6450
FIA
6450
FE FE
INSTRUMENT DRAINS (TYP.)
NC
600
PIPING
INST
FMC
6450
B-0609
B-0608
65/-45
6.05
6.99 (101.4)
3.92
LTCS
800
650
450
250
65/-45
P-6450B
0.1-6.45 (NOTE 2)
N2 I5 N3
I1A
I1B
N4
N5
NC
N8
B-0619
TO LIQUID BURNER
LO
TI
N7
50-DC-6427-11492X
I3B
I3A
VT-V6450-11492X TRIM NO.
I6
B-0611
TO FLARE STACK
FALL
FALL
NC
SIS
SDV
6450
TYPE 2,13
START/STOP
LAL
LZALL
P-6450A
LOGIC
MOTOR
TYPE 2.0
FALL
RS
I2B
I2A
300-VH-6222-11492X
LO
LOGIC
MOTOR
TYPE 2.0
SIZE
CASE
: 1D2
: BLOCKED DISCHARGE
SET @ 17 barg
SIZE
CASE
: 1D2
: BLOCKED DISCHARGE
SET @ 17 barg
SET @
10.5 barg
SET @
6.5 barg
SET @
10.5 barg
SET @
6.5 barg
CLOSED DRAIN SUMP PUMP
3.5 (50.8)
65/18
16.5 NOTE 9
1.1 (16)
1.01
SS316L
LOCATED AS FAR AS POSSIBLE FROM MANWAY.
P-6460
P-6450A/B
LICA
6460
H
L
LOGIC
MOTOR
TYPE 3.0
B-0612
80-DH-6508-11432X
PG
6460
MH1
50-DC-6428-11492X
5
0
-
D
C
-
6
4
2
6
-
1
1
4
9
2
X
5
0
-
D
C
-
6
4
2
9
-
1
1
4
9
2
X
DRAIN HEADER
TO HAZARDOUS OPEN
2. MAXIMUM OPERATING PRESSURE TO BE CONFIRMED UPON FINALIZATION OF FLARE TIP
N6
6450
80-DC-6431-11492X
NOTE 3
8
0
-
D
C
-
6
4
2
2
-
1
1
4
9
2
X
NOTE 5
150mm
MIN.
3. DIP PIPE TO TERMINATE 200mm ABOVE VESSEL BOTTOM. 5mm WEEP HOLE AT DIP PIPE
4. MINIMUM LIQUID HEIGHT TO BE CONFIRMED.
5. PROGRESSIVE CAVITY PUMP.
NOTE 4
N1
N9
SQC
6402
NC
DN50
TO BE PROVIDED.
NC
NOTE 6
NC
50-DH-6513-11492X
LZA
6461
LL
6. UTILITY CONNECTION TO BE BLINDED DURING NORMAL OPERATION.
500x300
N10
DUTY/STANDBY
500x300
RS
NOTE 5
DUTY/STANDBY
NOTE 8
NOTE 8
NOTE 7
N11
NOTE 8
7. 150mm SPARE NOZZLE.
8. BLIND FLANGE TO BE PROVIDED FOR POSITIVE ISOLATION AFTER SPOOL PIECE REMOVAL.
NOTE 1
DN50
NC
9. PUMP CAPACITY TO BE CONFIRMED AS PER FINAL DIMENSION OF SUMP.
VX-6502
VX-6438
VX-6439
VX-6503
VX-6505
VX-6506
VX-6501
VX-6507
VX-6508
VX-6504 VX-6440
VX-6444
VX-6445
VX-6446
11492X 31492X
11492X 31492X
VX-6448
VX-6447
VX-6443
VX-6441
VX-6442
50-DC-6435-11492X
50-DC-6433-11492X
TG
6451
NOTE 10,11
10. TG-6451 TO BE LOCATED BELOW LALL.
11. OPERATOR PROCEDURE TO MAKE SURE THAT FLUID TEMPERATURE IN THE VESSEL IS NOT
ELLOW AVLlACL A'ElLN| |L'lLlA|UlL (2` C, ELlOlL LlAlNlNC |O 'lNl'lZL lLAHlNC.
NC
NOTES:
S
T
O
P
NOTE 12
NOTE 13
FALL
GWR
GWR
GWR
GWR GWR
B-0607
DISTRIBUTION HEADER
50-GI-5824-13411X
FROM INSTRUMENT GAS
DN20
VX-5858
I7
B-0609
TO VENT HEADER
50-VH-6235-11492X
SET @
9.5 barg
SET @
7.5 barg
SET @
9.5 barg
SET @
7.5 barg
NC
DN20
VX-6913
NC
DN20
VX-6914
NC
DN20
VX-6915
NC
DN20
VX-6916
FQI
6450
H
14. AUTO PERMISSIVE DELAY FOR PUMP START.
LEAD AND LAG PUMP LEVEL SETTINGS
LEAD PUMP ON
LAG PUMP OFF
0.0
LAG PUMP ON 620
580
550
470 LEAD PUMP OFF
VESSEL BOTTOM
DATUM:
11492X 31492X
11492X 31492X
VX-6821
VX-6822
VX-6823
VX-6824
NC
NC
NC
NC
12. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
13. FINAL ELEMENT IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
NOTE 12
NOTE 12
NOTE 12
NOTE 12
NOTE 12
MATERIAL
15. FROM SDV-6450 INSTRUMENT GAS VENT LINE.
50x25
1
1
4
9
2
X
3
1
4
9
2
X
1
1
4
9
2
X
3
1
4
9
2
X
50x25
DN20
DN20
DN20
DN20
NC DN20
DN20
NC
VX-7452
VX-7451
DN20
NC
VX-7508
VENDOR DATA.
VX-6761
VX-6762
VX-6064
VX-6063
NC
DN20
NC
DN20
LO
LO
2. DELETED.
1. IGNITION CABLE.
ITEM NO.
SERVICE
DESIGN PRESS. (barg)/(psig)
MATERIAL
LLlCN |L'l. (`C,
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)
CAPACITY
A-6250
FLARE TIP
NOTE 4
SS310H
133 MMSCFD
NOTE 4
A-6910
PROPANE BOTTLES RACK
NOTE 4
NOTE 4
ITEM NO.
SERVICE
DESIGN PRESS. (barg)/(psig)
LLlCN |L'l. (`C,
5
-1.3
3. SONIC FLARE TIP.
NOTE 3
NOTE 4
4. VENDOR TO ADVISE.
5. VENDOR PACKAGE SHOWN IS ONLY INDICATIVE, VENDOR TO CONFIRM.
6. IN CASE OF FUEL GAS FAILURE, PROPANE SHOULD BE USED FOR PILOT & IGNITION. REQUIRED
PROPANE BOTTLES RACK AND ALL REQUIRED INSTRUMENTATION, VALVES, ETC ARE IN
7. NUMBER OF PILOT TO BE CONFIRMED BY VENDOR. EACH PILOT SHALL BE SUPPLIED WITH
I-6260
FLARE IGNITION PANEL
NOTE 4
NOTE 4
NOTE 4
NOTE 4
NOTE 4
NOTE 4
9. 2x100% SPARE THERMOCOUPLE.
10. REGULATOR SIZE TO BE ADVISED BY VENDOR.
8. NUMBER OF NITROGEN UTILITY STATION WAITING FINAL CALCULATION.
NOTE 4
TWO WIRED THERMOCOUPLE AS THE MINIMUM.
11. DELETED.
NOTES:
12. HIGH TEMPERATURE COATING REQUIREMENT TO BE APPLIED.
13. DELETED.
VENDOR'S SCOPE.
FROM FUEL
PILOT GAS
B-0606
GAS PACKAGE
I-6260
50-FG-6010-13411X 25-FG-6028-13411X
A-6250
FLARE KNOCKOUT DRUM
FROM CLOSED DRAIN/
B-0610
V-6450
300-VH-6222-11492X
TE
TYPICAL
NOTE 1
NOTE 1
SEAL
NOTE 9
TP
027
TP
028
NOTE 6, 7
XA
6261
UB
6261
UB
6262
XA
6260
IGNITION
FAILURE ALARM
PILOT 'B'
ON/OFF
PILOT 'A'
FIA
6260
PILOT 'A'
ON/OFF
PILOT GAS
LOW FLOW
IGNITION
FAILURE ALARM
PILOT 'B'
FALL
NOTE 7
NOTE 7
L
XA
6267
ALARM
COMMON FAULT
TIA TIA
VX-6073
VX-6074
TP
029
NOTE 12
NOTE 12
VX-6090
50-FG-6902-13411X
A-6910
5
0
-
F
G
-
6
9
0
2
-
1
3
4
1
1
X
PCV
6911
PG
6912
PG
6911
SET @
0.4-0.5 barg
FO
TYPICAL
NOTE 5,8
PSV
6915
SQC
6903
SHF
6901
SQC
6902
VX-6914
SET @
17.2 barg
TO ATM
AT SAFE LOCATION
PCV
6912
PG
6913
SET @
0.4-0.5 barg
FO
PSV
6916
VX-6916
SET @
17.2 barg
TO ATM
AT SAFE LOCATION
PCV
6913
6916
PG
6915
SET @
0.4-0.5 barg
FO
PSV
6917
VX-6918
SET @
17.2 barg
TO ATM
AT SAFE LOCATION
PCV
6914
6918
PG
6917
SET @
0.4-0.5 barg
FO
PSV
6918
VX-6920
SET @
17.2 barg
TO ATM
AT SAFE LOCATION
PG
6914
PG PG
SQC
6905
SHF
6902
SQC
6904
SQC
6907
SHF
6903
SQC
6906
SQC
6909
SHF
6904
SQC
6908
VX-6079
PCV
6910
PG
6910
SET @
0.55-0.69 barg
NOTE 10
6011
SFS
XA
6262
OUT ALARM
PILOT FLAME
RO
6002
RO
6001
NOTE 9
TE
1. FLUSHING POINT TO BE BLINDED DURING NORMAL OPERATION.
50-DH-6504-17161X
B-0604
FROM OILY WATER TREATMENT
PACKAGE
B-0614
HAZARDOUS OPEN DRAIN HEADER
B-0613
FROM FUEL GAS
PACKAGE
100-DH-6512-17161X
SUMP
TO OPEN DRAIN
50-DH-6511-17161X
B-0603
FROM SALES GAS
50-DH-6503-17161X
B-0602
FROM INLET SEPARATOR
50-DH-6502-17161X
NON HAZARDOUS OPEN DRAIN HEADER
B-0613
100-DN-6538-17161X
SUMP
TO OPEN DRAIN
B-0623
50-DN-6537-17161X
FROM EMERGENCY DIESEL
GENERATOR SKID
B-0621
50-DN-6535-17161X
FROM DIESEL
FALL
FALL
FALL
FALL
FALL
B-0601
50-DH-6501-17161X
FALL
FROM PIG RECEIVER
FALL
METERING PACKAGE
SYSTEM
B-0610
FROM CLOSED DRAIN
SUMP PUMP
80-DH-6508-11432X
FALL
FALL
11432X
17161X
B-0627
50-DN-6547-17161X
FROM FIREWATER
DIESEL DAY TANK AREA
FALL
FALL
NOTE 1
SQC
6502
NC
DN50 DN50
VX-6511 VX-6512
AG
UG
NOTE 1
SQC
6501
NC
DN50 DN50
VX-6509 VX-6510
AG
UG
1. ADJUSTABLE WEIR.
T-6550
ATM+FULL OF WATER
65/18
ATM OPERATING PRESSURE (barg)/(psig)
LLlCN |L'lLlA|UlL (`C,
DESIGN PRESSURE (barg)/(psig)
ITEM NO.
OlLlA|lNC |L'lLlA|UlL (`C, AMB
OPEN DRAIN SUMP SERVICE
P-6560 A/B
7 (101.5)
65/18
11
OPEN DRAIN WATER PUMP
1.55 (22.5)
P-6550 A/B
17 (246.6)
65/18
2.2
7.57 (109.8)
OPEN DRAIN OIL PUMP
CHROME STEEL
0.51 1.24
12 Cr
PUMP STOP
SUMP BOTTOM
LEVEL SETTINGS (mm)-WATER COMPARTMENT
LAL
DATUM:
LLlCN |L'lLlA|UlL (`C,
DESIGN PRESSURE (barg)/(psig)
ITEM NO.
FLOWRATE (m /hr)
DIFFERENTIAL PRESSURE (bar)/(psi)
SERVICE
MATERIAL
3
ABSORBED POWER (KW)
PUMP START
LAH
TO LIQUID BURNER
B-0619
50-PL-6303-31432X
SIS
SDV
6550
H LICA
6550
LOGIC
MOTOR
TYPE 4.0
LOGIC
MOTOR
L
PG
6550A
PG
6550B
5
0
-
P
L
-
6
3
0
4
-
1
1
4
3
2
X
OPEN DRAIN HEADER
FROM NON HAZARDOUS
B-0612
OPEN DRAIN HEADER
FROM HAZARDOUS
B-0612
100-DN-6538-17161X
FALL
FALL
100-DH-6512-17161X
P-6550B P-6550A
T-6550
B-0614
50-PL-4420-11432X
TREATMENT PACKAGE
FROM WATER
N1
N2
FALL
LALL 200
PZA
6550A
LL SET @
6 barg
PZA
6550B
LL
N7
N8
TO SEWER SYSTEM
-
100-PW-4404-11432X
TYPE 4.0
DUTY/STANDBY
MATERIAL CONCRETE SUMP + INTERNAL LINING/COATING AT BOTTOM
LAL
LEVEL SETTINGS (mm)-OIL BUCKET
LALL
LAH
2. PUMP SHALL STOP AUTOMATICALLY ON LEVEL ALARM LOW (LAL).
PUMP STARTS ONLY MANUALLY FROM CONTROL ROOM OR LOCAL.
DUTY/STANDBY
BOTTOM
N
O
T
E

1
HH HH
100
100 (NOTE 4)
(NOTE 4)
200
SET @
9.5 barg
SET @
6 barg
SET @
9.5 barg
3. LIQUID CAPACITY BETWEEN LAL AND LAH SHOULD BE 1 m (MIN) OR 200 mm WHICH EVER
4. LIQUID CAPACITY BETWEEN PUMP START AND PUMP STOP SHOULD BE 21 m (MIN).
3
3
TOP EDGE OF OIL BUCKET
DATUM:
(NOTE 2,3) 400
300
200
VX-6301
VX-6302
31432X
11432X
VX-6303
VX-6304
31432X
11432X
5
0
-
P
L
-
6
3
0
7
-
1
1
4
3
2
X
5. 200 MM DISTANCE FROM BOTTOM OF POND FOR WATER LAYER OVER FLOW.
SIZE. 7100(L) X 6000(W) X 2500(H)
NOTES:
6. INLET CONNECTION FOR HAZARDOUS OPEN DRAIN SHOULD BE HIGHER THAN THE INLET
CONNECTION FOR NON HAZARDOUS OPEN DRAIN.
NOTE 6
7. PZALL TO BE OVERRIDDEN BY OPERATOR TO START THE PUMP AND IT SHALL BE
AUTOMATICALLY NORMALIZED ONCE THE DISCHARGE PRESSURE EXCEEDING PZALL SETTING.
RECOVERED OIL
IS HIGHER.
NOTE 7,8
100
1400
GWR
S
T
O
P
N
O
T
E

2
NOTE 11
B-0614
B-0607
DISTRIBUTION HEADER
50-GI-5823-13411X
FROM INSTRUMENT GAS
DN20 DN20
VX-5860 VX-5862
TO OILY WATER
50-VH-6241-11492X
VX-6307
N10
NOTE 10
10. OVER FLOW TO SEWER SYSTEM SHOULD BE LOWER THAN WEIR OF THE OIL BUCKET.
VENT TO
80-VA-6250-11412X
SAFE LOCATION
VX-6837
50-PL-6308-11432X
NC
8. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
9. FINAL ELEMENT IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
NOTE 7,8
TYPE 2,9
11. FROM SDV-6550 AND SDV-6560 INSTRUMENT GAS VENT LINE.
VX-6841
N11
12. LZA-6560LL SET POINT LEVEL SHOULD BE HIGHER THAN NOZZLE N2.
NC
DN20
DN20
TREATMENT SYSTEM
DN20 DN20
VX-6305 VX-6306
NC NC
VX-7570
NC
VX-7571
NC
BY PIPING
BY INSTRUMENT
CONTROL
BOX
B-0614
50-PW-4406-11432X
TREATMENT PACKAGE
FROM WATER
RECYCLED WATER
N10
SFA
6501
OVERFLOW
I1
N3 N4
TREATMENT PACKAGE
B-0614
TO OILY WATER
SIS
SDV
6560
H LICA
6560
LOGIC
MOTOR
LOGIC
MOTOR
L
5
0
-
P
W
-
4
4
0
2
-
1
1
4
3
2
X
PG
6560A
PG
6560B
50-PW-4401-11432X
I2
I3
I4 N5 N6
TYPE 2,9
LZA
6560
LL
LZA
6550
LL
PZA
6560A
LL
PZA
6560B
LL
TYPE 4.0 TYPE 4.0
DUTY/STANDBY
DUTY/STANDBY
SET @
0.5 barg
SET @
4 barg
HH
SET @
0.5 barg
SET @
4 barg
HH
VX-4402
VX-4401
VX-4404
VX-4403
S
T
O
P
N
O
T
E

2
NOTE 7,8
GWR GWR GWR
NOTE 8,12
VENT TO
SAFE LOCATION
VX-6839
50-PW-4406-11432X
NOTE 8
NOTE 7,8
N9
N12
VX-6840
VX-6838
NC
DN20
NC
DN20
80-VA-6251-11412X
VX-6835 VX-6836
NC NC
DN20
VX-7572
NC
DN20
VX-7573
NC
SFA
6502
P-6560B P-6560A
NOTE 5
NOTE 8
5
0
-
P
W
-
4
4
0
3
-
1
1
4
3
2
X
LG
4410
H
LT
LL
LT
LL
NC
PG
4411
LO
4411
SFS
VX-4405
PG
4412
LC
4412
SFS
VX-4409
PG
4413
LO
4413
SFS
VX-4412
PG
4414
LC
4414
SFS
VX-4415
1. VENDOR TO ADVISE THE OPERATING & DESIGN CONDITION.
2. FOR INSTRUMENTATION ONLY. FUEL GAS SHALL NOT BE USED AS ASSIST GAS.
3. MANUAL SAMPLING POINT.
4. FROM SDV-4411 INSTRUMENT GAS VENT LINE.
5. PACKAGE P&ID IS INDICATIVE AND MINUMUM REQUIREMENT VENDOR TO CONFIRMED.
6. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
LOGIC
MOTOR
TYPE 4.0
LOGIC
MOTOR
TYPE 4.0
LOGIC
MOTOR
TYPE 4.0
LOGIC
MOTOR
TYPE 4.0
SIS
TYPE 2
VX-4414
VX-4413
VX-6420
NC
NC
VX-6828
VX-6421
NC
NC
VX-6830
VX-4417
VX-4416
NC
VX-6825
NC
VX-6827
4411B
VX-4425
VX-4409
50-PW-4401-11432X
TP
031
VX-4407
VX-4408
VX-6411
NC
VX-6410
NC
VX-4410
VX-4411
LG
4411
LT
L
GWR
4411A
LT
H
L
GWR
4410A
BY PIPING
BY INSTRUMENT
NOTE 4
B-0609
TO VENT HEADER
100-VH-6241-11492X
B-0613
DRAIN SYSTEM
FROM OPEN
B-0607
DISTRIBUTION HEADER
50-GI-5804-13411X
FROM INSTRUMENT GAS
TP
032
NOTE 2 VX-5812
TP
033
I.F.
TP
034
AG
UG
AG
UG
B-0608
HEADER
B-0612
TO HAZARDOUS
OPEN DRAIN HEADER
TO CLOSED DRAIN
TP
035
TP
036
-
50-PW-4403-11432X
TO SEWER SYSTEM
I.G.
AG
UG
SDV
4411
A-4410
4410B
50-PL-4420-11432X
VX-2950 VX-2951 VX-2952 VX-2953
DN20
NC
DN20
NC
DN20
NC
DN20
NC
B-0613
SUMP
TO OPEN DRAIN
CONTROL
BOX
NOTE 7
SC
SSC
2904
8. FUTURE CONNECTION.
NOTE 8
7. SAMPLE CONNECTION SHALL BE LOCATED AT 6 O'CLOCK POSITION OR USING LONG
QUILS IN 12 O'CLOCK POSITION.
RECYCLE 50-PW-4406-11432X
NOTE 7
SC
SSC
2903
NC
VX-6076
SIS
LCP-4410
PMCS
50-DH-6511-17161X
50-DC-6419-11492X
5
0
-
D
H
-
6
5
1
0
-
1
1
4
3
2
X
50-PL-6303-31432X
50-DC-6423-31492X
80-PL-6302-31492X
50-GI-5805-13411X
OIL PUMP
FROM OPEN DRAIN
B-0613
TRANSFER PUMP
FROM CLOSED DRAIN
B-0610
INLET SEPARATOR
FROM
B-0602
DISTRIBUTION HEADER
FROM INSTRUMENT GAS
B-0607
TP
038
TP
040
50-FG-6029-31492X
INLET SEPARATOR V-2010
B-0602
039
31432X
31492X
VX-5875
VX-5813
1. OPERATING AND DESIGN CONDITIONS TO BE ADVISED BY VENDOR.
2. FLOW RATE AS PER FPSO SIMULATION.
3. REQUIREMENT OF CLOSED DRAIN LINE TO BE CONFIRMED BASED ON LIQUID BURNER
XA
6321
UB
6321
UB
6322
XA
6320
IGNITION
FAILURE ALARM
PILOT 'B'
ON/OFF
PILOT 'A'
FIA
6320
PILOT 'A'
ON/OFF
PILOT GAS
LOW FLOW
IGNITION
FAILURE ALARM
PILOT 'B'
XA
6327
ALARM
COMMON FAULT
TIA TIA
TP
TE TE
073
059
TP
TP
4. IGNITION CABLE.
5. REQUIREMENT FOR INSTRUMENT GAS CONFIRMED BY VENDOR'S.
6. IGNITION PANEL SHALL BE LOCATED MINIMUM 100M FROM BURNER.
7. PCV SET POINT TO BE ADVISED BY VENDOR.
8. VENDOR PACKAGE SHOWN IS ONLY INDICATIVE.
NOTE 9
RS
9. REMOVABLE SPOOL FOR FUTURE CONNECTION.
TP
041
GAS FROM
074
TP
VX-6310
DN20
XA
6322
OUT ALARM
PILOT FLAME
ATOMIZING GAS LINE
PILOT LINE
FUEL GAS SUPERHEATER
PURGE GAS FROM
B-0606
50-FG-6011-13411X
VENDOR'S DATA.
PCV
6310
VX-6093
PG
6310
6001
SFS
VX-6090
VX-6096
FCV
6311
PG
6311
VX-6094
VX-6097
31492X
13411X
5
0
-
F
G
-
6
0
3
0
-
3
1
4
9
2
X
075
TP
VX-6098
VALVE PIT
N1
SUMP PIT
TO ATM
N2
50-VA-6265-11412X
DN20
VX-6311
RO
6301
RO
6302
SET @
0.55-0.89 barg
VX-6092 VX-6080
NC
31492X 11492X
31492X 11492X
50-FG-6042-11492X
50-FG-6043-11492X
FT
6311
FY
6311
FI
6311
FC
6311
FCV
6311
SIS
SDV
6301
TYPE 2
A-6910
PCV
6311
PG
6312
PG
6311
SET @
0.4-0.5 barg
FO
TYPICAL
NOTE 5,8
PSV
6315
SQC
6303
SHF
6301
SQC
6302
VX-6314
SET @
17.2 barg
TO ATM
PCV
6312
PG
6313
SET @
0.4-0.5 barg
FO
PSV
6316
VX-6316
SET @
17.2 barg
TO ATM
PCV
6313
6316
PG
6315
SET @
0.4-0.5 barg
FO
PSV
6317
VX-6318
SET @
17.2 barg
TO ATM
PCV
6314
6318
PG
6317
SET @
0.4-0.5 barg
FO
PSV
6318
VX-6320
SET @
17.2 barg
TO ATM
PG
6314
PG PG
SQC
6305
SHF
6302
SQC
6304
SQC
6307
SHF
6303
SQC
6306
SQC
6309
SHF
6304
SQC
6308
VX-6379
50-FG-6903-13411X
VX-6387
ITEM NO.
SERVICE
CAPACITY (m )
SIZE (mm)
T-6750
DIESEL STORAGE TANK
21
3000 (ID) x 4000 (H)
3
1. DIESEL TANK SHALL BE SIZED FOR 7 DAYS OPERATION OF 320 KW EMERGENCY
MATERIAL CS + 3 mm CA + INTERNAL COATING.
DIESEL GENERATOR. SELECTED TANK SIZE CAN LEAD TO NET CAPACITY OF 21m .
DESIGN PRESS. (barg/psig)
LLlCN |L'l. (`C, 65/18
0.02 barg + FULL OF WATER
OPERATING PRESS. (barg)
OlLlA|lNC |L'l. (`C, AMB
ATM
TRIM. NO VT-T6750-11412X
2. VALVE TO BE OPENED DURING THE FILLING OF DIESEL STORAGE TANK BY USING P-6750 A/B.
LOGIC
MOTOR
TYPE 4.0
SBS
6701
SFA
6701
TO ATM
LO
6701
SFS
LC
6702
SFS
T-6750
50-FD-6704-11412X
50-FD-6712-11412X
SQC
6701
50-FD-6701-11412X
N3
N2
P-6750B
50-DN-6530-17161X
I1C
I1A
PG
6750
8
0
-
F
D
-
6
7
1
0
-
1
1
4
1
2
X
50-FD-6707-11412X
50-FD-6709-11412X
5
0
-
F
D
-
6
7
0
8
-
1
1
4
1
2
X
NC
NOTE 2
ITEM NO.
SERVICE
ABSORBED POWER (kw)
P-6750 A/B
DIESEL TRANSFER PUMP
0.42
3
MATERIAL CS
DESIGN PRESS. (barg/psig)
LLlCN |L'l. (`C, 65/18
4 (58)
FLOWRATE (m /h)
DIFFERENTIAL PRESS (bar)/(psi) 1.43 (20.74)
2.2
LEVEL SETTINGS
LAH
LAL
DATUM: TANK BOTTOM
OVERFLOW
50-FD-6705-11412X
50-DN-6535-17161X
FALL
NOTE 1
SUPPLY FROM
TANKER
600
MH2
PDG
6760
FQI
6750
FQI
6750
NC
LOGIC
MOTOR
TYPE 4.0
P-6750A
RO
6750
5
0
-
F
D
-
6
7
0
3
-
1
1
4
1
2
X
PG
6751
LALL
80-VA-6253-11412X
NC
6760
SFS
NC
3. DIP PIPE TO BE BELOW LOW LIQUID LEVEL. 5mm WEEP HOLE AT DIP PIPE TO BE PROVIDED.
N4
MH1
600
3500
450
350
5
0
-
D
N
-
6
5
3
9
-
1
7
1
6
1
X
NC DN50
NOTE 4
NC DN40
NC N1
NC
DN50
DN50
4. SAMPLE CONNECTION.
5. DIP HATCH NOZZLE.
6. UTILITY CONNECTION.
N5
NOTE 5
NOTE 3
150
N6
3
NOTE 7
50-FD-6702-11412X
N7
NOTE 8
NOTE 9
LO
7. TUNDISH SHOULD BE VISIBLE FROM DRAIN VALVE VX-6704 AND VX-6513.
NC
8. DRAIN CONNECTION TO BE INSTALLED AT TANK LOWEST POINT.
9. DIMENSION OF CLEAN OUT DOOR: 610mm(24")x915mm(36").
DI
NOTE 10
10. FIRE RELIEF MANWAY.
DUTY/STANDBY
DUTY/STANDBY
LL
I2
SMH
6701
LZA
6751
11. LG-6750 SHOULD COVER ENTIRE TANK'S LEVEL FROM BOTTOM OF TANK TO OVERFLOW LEVEL.
VX-6704
VX-6705
VX-6708 VX-6709 VX-6701
VX-6702
VX-6703
VX-6513
VX-6710
VX-6707
VX-6718
VX-6717
VX-6711
VX-6712
VX-6714
VX-6715
VX-6713
VX-6716
AG
UG
NOTE 7
AG
UG
NOTE 11,14
NOTE 12
12. VALVE TO BE CLOSED DURING THE FILLING OF STORAGE TANK BY USING P-6750A/B.
50-FD-6714-11412X
13. LOCAL PUSH BUTTON TO BE PROVIDED TO STOP PUMP DURING EMERGENCY.
NOTES:
NOTE 13
NOTE 13
VX-6831
VX-6832
VX-6833
14. LG-6750 USE LEVEL GLASS GAUGE TYPE.
NOTE 15
15. TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
LG
6750
VX-6751
VX-6750
VX-6752
VX-6753
VX-6754
VX-6755
DRIP PAN
DRIP PAN
AG
UG
DN20 DN20
DN20
DN50
DN50
DN50
DN50
DN20
DN20
LIA
6753
H
L
DN50
NOTE 6
NC
I3
VX-6706
DN20
DN20
DRIP PAN
50-DN-6532-17161X
AG
UG
50-DN-6534-17161X
50-DN-6533-17161X
VX-7750
VX-7751
LAHH 3600
OVERFLOW 3800
VX-6064
VX-6065
50-DH-6548-11432X
VALVE PIT
VX-6099
VX-6077
CATCH
BASIN
11412X 31412X 11412X
I1B
I1D
1. DAY TANK TO BE ADEQUATE TO HOLD 8 HOURS CONSUMPTION.
DAY TANK WILL HAVE FLOAT VALVE INSTALLED. IF ONE TANK IS NOT FEASIBLE,
NOTE 1
50-FD-6704-11412X
ATM
TO
OPEN DRAIN HEADER
TO NON HAZARDOUS
STORAGE TANK
FROM DIESEL
ITEM NO.
SERVICE EMERGENCY
DRIVEN
PRIME RATING (kW) 440 kW
DIESEL
EMERGENCY DIESEL GENERATOR SKID
GD-7730
VENDOR TO PROVIDE OFF-SKID TANK CONNECTED TO THE GENSET SKID.
50-DN-6537-17161X
B-0621
B-0612
GD-7730
2. DETAILS OF SKID SHALL BE CONFIRMED BY VENDOR. ALL EQUIPMENTS, INSTRUMENTATION,
NOTES 2,3
SIS
DGCP-7730
NOTE 4
ATM
TO
NOTE 4
TP
049
TP
048
FALL
PIPING, FITTING, SILENCER/SPARK ARRESTOR WITH NECESSARY ACCESSORIES, EXHAUST ARE IN
VENDOR'S SCOPE.
3. DETAILS FOR LEVEL MEASUREMENT IN DIESEL GENERATOR SKID SHALL BE REFLECTED IN
THE VENDOR'S DRAWING.
4. EXHAUST VENT TO SAFE LOCATION.
TO ATMOSPHERE
5
0
-
V
A
-
6
2
5
7
-
1
1
4
1
2
X
PMCS
5. DGCP-7730 TO BE LOCATED IN ELECTRICAL ROOM AT ELECTRICAL BUILDING.
INLET
AIR
DGLCP-7730
TP
047
NOTE 5
VX-6719
AG
UG
LL. |L'l. (`C,
DES. PRESS (barg)/(psig)
MATERIAL
SIZE (mm)
CAPACITY (m )
SERVICE
ITEM NO.
3
15.6
FRP
65/18
FRESH WATER TANK
ATM + FULL OF WATER
T-5110
UTILITY WATER SUPPLY
FROM OTHER SOURCE
NOTE 1
1. TANK CAPACITY IS FOR 1 DAY STORAGE BASED ON 233 LITRE/PERSON/SHIFT
3000 (ID) x 3800 (H)
-
TO
ELECTRICAL BUILDING
-
1
2
0
0
0

m
m
OlLlA|lNC |L'l. (`C,
OPERATING PRESS. (barg)
80-WS-5114-13411X
80-WS-5107-18011X
8
0
-
W
S
-
5
1
0
1
-
1
3
4
1
1
X
N2
N3 N1
HOSEREEL
UTILITY STATION
(TYP.)
SBS
5101
N4
MH1
600
AMB
ATM
2. WASH WATER UTILITY IS FOR GENERAL CLEANING. WATER BOTTLE WILL BE USED AS
DRINKING WATER.
8
0
-
W
S
-
5
1
0
2
-
1
3
4
1
1
X
NOTE 2,5,6
T-5110
50-VA-6254-11432X
17161X
13411X
8
0
-
W
S
-
5
1
0
8
-
1
3
4
1
1
X
NC
LG
5110
LIC
5110
H
L
START/STOP
MH2 600
TP
002A
UTILITY STATION
(TYP.)
NOTE 2,5,6
80-WS-5105-18011X
LEVEL DIAGRAM (mm)
LAH
PUMP STOP
DATUM: TANK BOTTOM
PUMP START
OVER FLOW 3600
3350
3300
LAL
380
350
I1B
I1A
75mm
NC
DN50
N5
13411X
18011X
SQC
5102
5101
I2
TRIM NUMBER VT-T5110-17161X
5101
SFS
P-5110
LOGIC
MOTOR
TYPE 3.0
PG
5110
13411X 18011X
ITEM NO.
SERVICE
ABSORBED POWER (kw)
P-5110
FRESH WATER FEED PUMP
3
MATERIAL
DESIGN PRESS. (barg/psig)
LLlCN |L'l. (`C,
FLOWRATE (m /h)
DIFFERENTIAL PRESS (bar)/(psi)
TO
CONTROL BUILDING
-
80-WS-5104-13411X
TO ADMINISTRATION
BUILDING
-
80-WS-5112-13411X
80x50
80x50
15 (217.5)
65/18
8.8
2.55 (37)
1.56
17161X
13411X
11432X
17161X
17161X
13411X
5
0
-
W
S
-
5
1
1
1
-
1
3
4
1
1
X
TO GRADE
OVER FLOW
3. REQUIREMENT OF SAFETY SHOWER AND EYE WASH STATION TO BE CONFIRMED.
B-0627
TO FIREWATER POND
NC
50-WS-5109-18011X
13411X 18011X
NC
NC
SQC
4. PUMP WILL START ONCE THE LEVEL IN FRESH WATER TANK REACH TO 500 mm AND
NOTE 4
PUMP WILL STOP ONCE THE LEVEL REACH TO 3200 mm.
80-WS-5103-13411X
SS136L
VX-5111
VX-5113
VX-5114
VX-5115
VX-5117
VX-5106
VX-5108
VX-5110
VX-5109
VX-5105
VX-5107
VX-5116
VX-5118
VX-5102
VX-5103
VX-5104
VX-5101
5. NUMBER OF UTILITY STATION TO BE CONFIRMED.
6. UTILITY STATION OF FRESH WATER TO BE PROVIDED AROUND PIG RECEIVER, OPEN DRAIN SUMP,
INLET SEPARATOR, CLOSED DRAIN/FLARE KO DRUM, DIESEL STORAGE TANK.
7. ONE MOVABLE HOSE REEL IS PROVIDED AND CAN BE USED FOR OTHER FRESH WATER
NOTE 7
MOVABLE
UTILITY STATIONS.
(FOR TOTAL 3 SHIFT/DAY AND 12 PEOPLE/SHIFT) PLUS 7.2 m (FOR 1 HOUR WASHDOWN 3
HOSE CONSUMPTION).
NC
50-WS-5115-13411X
VX-5150
VX-5151
UTILITY WATER
SUPPLY FROM MASPION
-
TP
002B
VX-5152
VX-6834
NC
13411X 18011X
8
0
-
W
S
-
5
1
0
6
-
1
3
4
1
1
X
NC
DN20
VX-6835
DN20
LC
TO ATMOSPHERE
TP
057
LZA
5301
FIREWATER PUMP
LOCAL CONTROL PANEL
FIREWATER PUMP
LOCAL CONTROL PANEL
HS
5311
XL
5310
HS
5321
XL
5320
FGS FGS
UB-5310-PUMP RUNNING
UB-5311-COMMON FAULT
UB-5310-UNAVAILABLE
UB-5312-BATTERY FAILURE
LL
UB-5320-PUMP RUNNING
UB-5321-COMMON FAULT
UB-5310-UNAVAILABLE
UB-5322-BATTERY FAILURE
5
0
-
V
A
-
6
2
6
2
-
1
1
4
1
2
X
FGS
HS
5310
P-5310
NOTE 11
LCP-5320 LCP-5310
VF
P-5320
FIREWATER PUMP
14 (203)
65/18
CAST DUCTILE IRON
NOTE 5
1. AUTOMATIC AIR RELEASE VALVE TO BE PROVIDED TO VENT AIR UPON THE STARTING OF
THE PUMP OR TO DISSIPATE THE VACUUM UPON STOPPING OF THE PUMP. THIS VALVE
SHALL BE LOCATED AT THE HIGHEST POINT BETWEEN FIRE WATER PUMP AND CHECK VALVE.
FLAME RESISTANT FLEXIBLE HOSES TO ALLOW FOR MACHINE VIBRATION TO BE SUPPLIED BY 2.
4.
3. FIREWATER PUMP AND AUXILIARIES SHALL BE DESIGNED AS PER NFPA 20 REQUIREMENTS.
5.
NO POCKETS ON PUMP DISCHARGE LINE.
NON SLAM CHECK VALVE.
7.
8.
ALLOWABLE WORKING PRESSURE (DESIGN) OF DISCHARGE GRE PIPEWORK (14 barg).
PUMP SELECTION TO ENSURE MAXIMUM SHUT-OFF HEAD DOES NOT EXCEED THE MAXIMUM
PCV SIZE TO BE CONFIRMED AS PER VENDOR'S DATA.
ONLY FUNCTIONAL REQUIREMENTS ARE SHOWN WITHIN PACKAGE. 9.
10.
VENDOR SHALL BE RESPONSIBLE FOR DETAIL DESIGN OF THE PACKAGE.
NOTES :
250
DIESEL DAY TANK.
TO BE CONFIRMED BY VENDOR.
HS-5310, HS-5320 AND HS-5331 ARE LOCATED ON PUSH BUTTON 11.
FLEXIBLE CONNECTOR. 12.
P-5310
FIREWATER PUMP
14 (203)
65/18
11.46 (166.2)
ITEM NO.
SERVICE
DESIGN PRESS. (barg)/(psig)
LLlCN |L'l.(`C, 'AX.'lN.
DIFFERENTIAL PRESS.(bar)/(psi)
FLOW RATE (m /hr)
ABSORBED POWER (kW) 146
MATERIAL CAST DUCTILE IRON
NOTE 5
250
3
6.
METERING DEVICE FOR PUMP TESTING SHALL BE LISTED AS PER NFPA 20. 13.
METERING DEVICE SHALL BE CAPABLE OF WATER FLOW OF NOT LESS THAN
175% OF MAIN PUMPS RATED CAPACITY.
14. DEBRIS SCREEN.
15. PSV SIZE AND INLET/OUTLET PIPE SIZE BY VENDOR.
B-0629
TO FIREWATER RING
NOTE 6
NOTE 12
B-0629
TO FIREWATER RING
TP
055
NOTE 7,9
RS
NOTE 6
NOTE 12
P-5320 P-5310
NOTE 6
PSV
TP
061
SIZE : 1D2
CASE : BLOCKED
SET@ : 14 barg
5330
WASTE
CONE
TP
053
PSV
SIZE : 4M6
CASE : BLOCKED DISCHARGE
SET@ : 14 barg 5310
WASTE
CONE
NOTE 8
PCV
5310
LO
DN20 NC
SET @
11 barg
NOTE 8
PCV
5320
LO
DN20 NC
SET @
11 barg
FI
5310
5334-11432X
5320
PG
TP
060
DISCHARGE
PSV
SIZE : 4M6
SET@ : 14 barg
5320
WASTE
CONE
TP
052
NOTE 10
LG
LIA
5321
5320
L
H
NC
DRIP PAN
N
O
T
E

2
NOTE 2
D
IE
S
E
L

F
U
E
L

R
E
T
U
R
N
D
IE
S
E
L

F
U
E
L

S
U
P
P
L
Y
NOTE 10
LG
LIA
5311
5310
L
H
NC
DRIP PAN
CONSOLE INSIDE ORF CENTRAL CONTROL ROOM.
B-0621
DISTRIBUTION HEADER
FROM DIESEL
50-FD-6712-11412X
VX-6720
B-0624
DISTRIBUTION
FROM FRESH WATER
LIA
5302
L
H
MOV
5310
-
OVERFLOW TO SEWER
TP
051
B-0612
OPEN DRAIN HEADER
TO NON HAZARDOUS
1
5
0
-
F
W
-
5
3
0
5
-
1
1
4
3
2
X
NOTE 7,9
NOTE 16 NOTE 16
TP
050
VX-6721
VX-6722
VX-5302
VX-5303
VX-5304
VX-5305
VX-5307
VX-5308
VX-5310
VX-5309
VX-5312
VX-5311
P-5330
JOCKEY PUMP
14 (203)
65/18
10.93 (158.5)
7.6
CAST DUCTILE IRON
NOTE 5
5.0
16. P-5310/5320 "INHIBIT TO START" INDICATION TO BECOME HIGH
VX-6723
VX-6724
PRIORITY ALARM.
150-FW-5311-11432X
SFA
5301
NOTE 2
DIESEL FUEL RETURN
NOTE 2
DIESEL FUEL SUPPLY
CASE : BLOCKED DISCHARGE
VX-5336
VX-5335
17.
AG
UG
5
0
-
F
D
-
6
7
1
3
-
1
1
4
1
2
X
PS
5334
TO LCP-5310
@ 6 barg
PS
5333
TO LCP-5320
1
5
0
-
F
W
-
5
3
0
4
-
1
1
4
3
2
X
DN 80
VX-5339
NC
TP
063
NOTE 17
FIRE WATER TIE IN FOR BACK UP SUPPLY FROM MASPION INDUSTRIAL ESTATE.
18.
TO ATMOSPHERE
TP
056
5
0
-
V
A
-
6
2
5
9
-
1
1
4
1
2
X
VF
SFA
5302
RUNNING START RUNNING START
NOTE 19
NOTE 18
DN 50
NOTE 14
TP
071
NOTE 1
50-FW-5308-11432X
NOTE 1
5310
PG
50-FW-5302-11432X
TP
054
RO
5330
1
5
0
-
F
W
-
5
3
3
7
-
1
1
4
3
2
X
START
@ 5.5 barg
START
PROVISION FOR CHEMICAL INJECTION.
19. MOV-5310 TO BE OPENED AT LAL AND TO BE CLOSED AT LAH.
20.
21.
NOTE 20
THE VALVE TO BE EQUIPPED WITH DECLUTCHABLE MANUAL HANDWHEEL.
22.
HS
5320
RS
I.G.
AG
UG
START
NOTE 11
HS
5331
SELECT SWITCH
NOTE 11
LEAD/LAG
P-5320
START
THE SET POINT TO BE REVIEWED.
NOTE 21
NOTE 21
GWR GWR
DELETED.
33411X
17161X
31492X
33411X
31492X
33411X
33411X
13411X
50-FW-
31492X
33411X
33411X
13411X
NOTE 12
P-5330
NOTE 7,9
RS
NOTE 23
TRANSMITTER IS PART OF SIL 2 SAFETY INSTRUMENTATION FUNCTION (SIF).
MINIMUM SAFETY FAILURE FRACTION (SFF) IS 60% FOR TYPE A AND 90% FOR TYPE B
WITH HARDWIRE FAULT TOLERANCE = 0.
23.
NOTE 24
NOTE 24
NOTE 24
PSV SIZE TO BE CONFIRMED BY VENDOR. 24.
50x80
100-FW-5303-11432X
100-FW-5309-11432X
50-FW-5336-11432X
1
5
0
-
F
W
-
5
3
1
0
-
1
1
4
3
2
X
8
0
-
F
W
-
5
3
3
5
-
1
1
4
3
2
X
150-FW-5306-11432X
150-FW-5312-11432X
80x50
5330
PG
NOTE 1
50-FW-5330-11432X
VENDOR.
11.46 (166.2)
146
DN 150
DN 150
SAR
5302
1. ALL VALVES TO BE LOCATED ABOVE GROUND.
START/STOP SIGNAL TO BE SENT TO PMCS. 2.
AIR RELEASE VALVE SHALL BE INSTALLED AT HIGH POINT. 3.
IF THE DISTRIBUTION SYSTEM PRESSURE DOES NOT REACH THE SET POINT WITHIN 4.
20 SECONDS AFTER STARTING OF THE FIRST MAIN FIREWATER PUMP, ANOTHER PULSE
SHALL BE SENT TO START THE FIREWATER PUMP DESIGNATED AS THE SPARE OF BACK-UP.
FGS
UG
AG
UG
AG
ALL VALVES, FIRE HYDRANTS, AND FIRE MONITORS SHALL BE INSTALLED ABOVE GROUND. 5.
DETAIL CONFIGURATION PIPING SHALL REFER TO DOC.NO 11-BTORF-B-DAS-0002. 6.
PROVISION FOR PORTABLE FOAM AS PER HAZID RECOMMENDATION FLANGE 7.
CONNECTION/DEVISE INTEGRATED WITH NOZZLE.
17161X 18011X