DVR Parameters 906 KVA

01 Generator Output Voltage (V) 480


02 Ratio of Output Voltage to Sensing Voltage 2
03 Generator Type 4
04 Rated Generator Output Current (A) 2510
05 CT Voltage At Rated Generator Current (V) 4,57
06 Knee Frequency (Hz) 59,8
07 Decreasing Volts/Hz Slope 1 (V/Hz) 2,0
08 Decreasing Volts/Hz Slope 2 (V/Hz) 2,0
09 Minimum Voltage (%) 60,0
10 Underfrequency Point (Hz) 25,0
11 Overvoltage Trip Point (%) 115
12 Overvoltage Trip Time (s) 3
13 Undervoltage Trip Point (%) 85
14 Undervoltage Trip Time (s) 30
15 Voltage Gain (IR Compensation) (%) 0
16 Integral Gain 6,0
17 Proportional Gain 5,0
18 Single Phase Sensing Select
0 = Three phase ; 1 = Single phase 0
19 Diode Monitor Trip Point 4,0
20 Reverse VAR Trip Time 5,0
21 Reverse VAR Fault Selection 1,0
22 Droop/CCC Select (0 = Droop, 1 = CCC) 0
30 Droop Percentage (%) 5,0
31 PF/KVAR Select (0 = PF, 1 = KVAR) 0
32 PF Reference 0,82
33 KVAR Reference 1,0
34 Reverse Power Trip Point (%) 7,0
35 Reverse Power Trip Time (s) 5,0
36 Paralleling Integral Gain -
37 Paralleling Proportional Gain -
38 PF Switch Point (%) -
50 Generator Output Frequency (Hz)
51 Generator Output Voltage (V)
52 Generator Output Current (A)
53 Generator Reactive Output Current (A)
54 Generator Real Current (A)
55 Exciter Field Current (A)
56 Three Phase Kilowatts (KE and later) (kW)
57 Power Factor (PF)
58 Three Phase KVAR (KE and later)
60 Hours (h)
70 Voltage Adjust
71 PF/KVAR Adjust
90 Password
91 Software ID
92 Latest Fault
93 Previous Fault
94 Fault Clear
95 Alarm Fault
96 Shutdown Fault Reset