Transformer Name:

Full-load rating, kVA: 315. kVA


SNL Standard Impedance, % 4.70% %
Line-to-line primary voltage: 480 volts
Line-to-line secondary voltage: 208 volts
Primary current, FLA: 379 amps
Secondary current, FLA: 874 amps
Primary fuse, max of 300% 1,137 amps
Primary fuse, min of 125% 474 amps
Secondary breaker, 125% 1,093 amps
Fault duty, primary 8,062 amps
Fault duty, secondary 18,604 amps
K-Factor FHL-Factor
Fundamental current: 100 amps 874
Third Harmonic current: amps 0
Fifth Harmonic current: amps 0
Seventh Harmonic current: amps 0
Ninth Harmonic current: amps 0
Eleventh Harmonic current: amps 0
Thirteenth Harmonic current: amps 0
Fifteenth Harmonic current: amps 0
Calculated RMS current, FLA: 100 amps 874
Calculated Harmonic Factors: 1.00 1.00
Template dated 25Jan99 by HOE Printed: 13-Apr-12