CT 08 FUTURE

STANDBY

CWS

CWS

CWR

CWR

CHWS

CHWS

CHWR

CHWR

CT 06 T0 CT 07 - FOR FUTURE

CT01 T0 CT05 - DUTY

- Cooling towers control by condensor water supply


temperature sensor (10).
- Modulating valve open/close state due to correlative chiller
start/stop command.
- Condensor water pumps and Primary chilled water pumps
running due to the numer of chiller running.
- Secondary chilled water pumps control by pressure sensor
(5, 6).
- Chillers control by chilled water supply/return temperature
sensor (7, 8) and flow meter (1) or Opertator.
- Make-up water pumps (MWP 1, MWP 2) only monitor.
- Conductivity, ORP, PH sensor use for monitoring purpose.
- Chilled water supply/return temperature (9, 15~26, 140,
141) and flow meter (2, 3, 4, 131) use for monitoring
purpose or calculate heat load.
- Differential pressure switch (44~49) use for chiller
protecting purpose.
- Water level switch (LVS) warn water low/high level in
cooling tower.

CWS

CWR

CWS

CWR

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWR

CWS
CWS

CWS

CWR

CWS

CWS

CWR

CWS

D
D

CWR

CWS
CWS

CWS

CWR

CWS

CWR

- General alarm:
+ Chillers trip.
+ Cooling towers trip.
+ Pumps trip.
+ Cooling tower water low/high level alarm.

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWS

CWR

CWS

CWS

CWS

CWR

CWS

CWR

CWS

CWR

CWR

CWS

- Time schedule control: The operator can set a weekly


schedule for Chiller system.

CWS

CWS

CWS

D
D

CWR

CWS

CWS

CHWR

CHWR

CHWR

CHWR

CHWS

CHWR

CHWR

CHWR

CWS
CWS
CWS
CWS
CWS
CWS

CWS
CWS
CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWR

CWS

CWS
CWS
CWS
CWS
CWS
CWS

CWS
CWS
CWS
CWS

CWS
CWS
CWS
CWS

CWR
CWR
CWR
CWR
CWR

125 MAKE-UP PIPE FROM BASEMENT

CWR

CWS
CWS
CWS
CWS

CHWR

CHWR

CHWR

CHWR

CHWR

CHWR

CHWR

PLUMBING
SERVICE MWP 1

MWP 2

MW-CP-01

CHWR
CHWR

CWS

CHWR

CHWR

CHWR

CHWS

CHWS

CHWS

CHWR

CHWS

CHWR

CHWS

CHWR

CWS

CHWR
CHWR
CHWR
CHWR
CHWR
CHWR

CWS

CHWR

CWR

CWR

CHWR
CHWR
CHWR

CHWS
CHWS
CHWS
CHWS
CHWS
CHWS

CHWR
CHWR
CHWR
CHWR

CHWR

CHWR

CWR

CWS

CHWR

CHWR
CHWR
CHWR

CHWS

CHWR
CHWR

CHWR
CHWR
CHWR
CHWR

CHWR
CHWR

CHWS
CHWS

CHWR

PLACE IN HOTEL

CWS

CHWR

CHWR

CHWS

CHWS

CHWS

CHWR
CHWR
CHWR

CHWS

CHWS

CHWS
CHWS
CHWS
CHWS
CHWS
CHWS
CHWS
CHWS

CHWR

CWR

CHWS

CHWS

CHWR
CHWR
CHWR
CHWR

CHWS
CHWS
CHWS
CHWS

CHWS
CHWS
CHWS

CHWS

CHWS

CHWS

CHWS

CHWS

CHWS

CHWS

CHWS

CWR

CWS

CHWS

MAKE-UP PIPE
FROM BASEMENT

125 MAKE-UP PIPE FROM BASEMENT

MW-CP-02

MAKE-UP PIPE
FROM BASEMENT

MW-CP-03

MAKE-UP PIPE
FROM BASEMENT

CHWR

MONITOR BY "AP-H-PAU-L1-02"
SENSOR SIGNAL SENT TO DDC IN CENTRAL PLANT OVER NETWORK

DOAN CONG THAC

MGM HO TRAM
SHINRYO CORPORATION

CHILLER SYSTEM CONTROL SCHEMATIC

HO PHUOC THAO
DAON CONG THUY

BAN MAI SYSTEM JSC


A JOHNSON CONTROLS ABCS
C-702 The Manor, 91 Nguyen Huu Canh, Binh Thanh Distr
Hochiminh city, Vietnam.
Tel: + 84 8 6258 6218
Fax: + 84 8 6258 6215

14/12/2012

You might also like