PROJECT : 1.

5 MTPA EXPANSION OF Pb-Zn BENIFICIATION PLANT AT RAMPURA AGUCHA (4TH STREAM)


OWNER : HINDUSTAN ZINC LIMITED
CONSULTANT :DEVOLOPMENT CONSULTANTS PVT. LTD.

11 KV & 6.6 KV SIZE CABLE SELECTION CRITERIA


11KV (UE) GRADE CABLE XLPE TYPE WITH STRANDED & COMPECTED AL. CONDUCTOR OF GR H2 7 CL. 2
DESIGN AMBIENT TEMPERATURE = 50 Deg. Cent

SL. NO.

CABLE FROM

132/11 KV, 12.5/16


MVA TRANS.
11KV EXISTING
PANEL(TIE FDR.).
11KV SW. BOARD
(PANEL-4)
11KV SW. BOARD
(PANEL-5)
11KV SW. BOARD
(PANEL-6)
11KV SW. BOARD
(PANEL-7)
11KV SW. BOARD
(PANEL-8)
11KV SW. BOARD
(PANEL-9)
11KV SW. BOARD
(PANEL-10)
11KV SW. BOARD
(PANEL-11)
11KV SW. BOARD
(PANEL-12)
11KV SW. BOARD
(PANEL-13)
11KV SW. BOARD
(PANEL-17)
11KV SW. BOARD
(PANEL-18)
11KV SW. BOARD
(PANEL-20)

2
3
4
5
6
7
8
9
10
11
12
13
14
15

POWER
HANDLING
KW/KVA
/KVAR

LOAD
CURRENT
(AMP.)

RATING
FACTOR
FOR 50 0 C
AMBIENT

RATING
FACTOR
FOR SIDE
BY SIDE
LAYING

REQD.
CURRENT
RATING
(AMP.)

NO. OF
RUNS

CABLE
SIZE
SELECTED

CURRENT
RATING OF
CABLE IN
AIR
(AMP)

FAULT
CLEARING
DURATION
(MILLI
SEC)

SYSTEM
FAULT
LEVEL
(KA) FOR
1 SEC.

EFFECTIVE
SHORT CKT
RATING
REQUIRED
(KA for 0.4 S)

TOTAL
CURRENT
CARRYING
CAPACITY
(AMP)

SEL.SHORT
CKT
RATING
OF CABLE
(KA for 0.4S)

11KV SW. BOARD (PANEL-1)

16000

839.81

0.88

0.68

1403.42

3C X 300

440

400

26

10.4

1760

70.5

11KV SW. BOARD (PANEL-2)

16000

839.81

0.88

0.68

1403.42

3C X 300

440

400

26

10.4

1760

70.5

CAPACITOR BANK

2500

131.22

0.88

0.68

219.28

3C X 120

255

400

26

10.4

255

28.25

DISTR. TRANFO
(INC#1)
DISTR. TRANFO
(INC#2)
DISTR. TRANFO
(INC#3)
DISTR. TRANFO
(INC#4)
11/6.6 KV TRAFO.

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

10000

524.88

0.88

0.68

877.14

3C X 300

440

400

26

10.4

880

70.5

BALL MILL MOTOR

3500

183.71

0.88

0.68

307.00

3C X 300

440

400

26

10.4

440

70.5

LIGHTING TRAFO

500

26.24

0.88

0.68

43.86

3C X 70

180

400

26

10.4

180

16.45

CONV. TRAFO

3500

183.71

0.88

0.68

307.00

3C X 300

440

400

26

10.4

440

70.5

DISTR. TRANFO
(INC TO AUX. PMCC)
DISTR. TRANFO
(INC#5)
DISTR. TRANFO
(INC#6)
CAPACITOR BANK

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

2000

104.98

0.88

0.68

175.43

3C X 120

255

400

26

10.4

255

28.25

2500

131.22

0.88

0.68

219.28

3C X 120

255

400

26

10.4

255

28.25

CABLE TO

1 OF 4

\\vboxsrv\conversion_tmp\scratch_1\255770790.xls.ms_office

PROJECT : 1.5 MTPA EXPANSION OF Pb-Zn BENIFICIATION PLANT AT RAMPURA AGUCHA (4TH STREAM)
OWNER : HINDUSTAN ZINC LIMITED
CONSULTANT :DEVOLOPMENT CONSULTANTS PVT. LTD.

6.6KV (UE) GRADE CABLE XLPE TYPE WITH STRANDED & COMPECTED AL. CONDUCTOR OF GR H2 7 CL. 2
DESIGN AMBIENT TEMPERATURE = 50 Deg. Cent

SL. NO. CABLE FROM

1
2
3
4
5
6
7

CABLE TO

11/6.6 KV, 8/10 MVA6.6KV SW. BOARD


TRANS.
(PANEL-1)
6.6KV EXISTING PANEL
6.6KV SW. BOARD
(TIE FDR.).
(PANEL-2)
6.6KV SW. BOARD DRYING COMPR.
(PANEL-4)
NO-1
6.6KV SW. BOARD DRYING COMPR.
(PANEL-5)
NO-2
6.6KV SW. BOARD FLOAT.AIR BLOWER
(PANEL-6)
(WORKING)
6.6KV SW. BOARD FLOAT.AIR BLOWER
(PANEL-7)
(STANDBY)
6.6KV SW. BOARD ZINC. REGRIND MILL
(PANEL-8)

POWER
HANDLING
KW/KVA
/KVAR

LOAD
CURRENT
(AMP.)

RATING
FACTOR
FOR 50 0 C
AMBIENT

RATING
FACTOR
FOR SIDE
BY SIDE
LAYING

REQD.
CURRENT
RATING
(AMP.)

NO. OF
RUNS

CABLE
SIZE
SELECTED

CURRENT
RATING OF
CABLE IN
AIR
(AMP)

FAULT
CLEARING
DURATION
(MILLI
SEC)

SYSTEM
FAULT
LEVEL
(KA) FOR
1 SEC.

EFFECTIVE
SHORT CKT
RATING
REQUIRED
(KA for 0.4 S)

TOTAL
CURRENT
CARRYING
CAPACITY
(AMP)

SEL.SHORT
CKT
RATING
OF CABLE
(KA for 0.4S)

10000

874.80

0.88

0.68

1461.90

3C X 300

440

400

26

10.4

1760

70.5

10000

874.80

0.88

0.68

1461.90

3C X 300

440

400

26

10.4

1760

70.5

300

26.24

0.88

0.68

43.86

3C X 70

180

400

26

10.4

180

16.45

300

26.24

0.88

0.68

43.86

3C X 70

180

400

26

10.4

180

16.45

450

39.37

0.88

0.68

65.79

3C X 70

180

400

26

10.4

180

16.45

450

39.37

0.88

0.68

65.79

3C X 70

180

400

26

10.4

180

16.45

350

30.62

0.88

0.68

51.17

3C X 70

180

400

26

10.4

180

16.45

3.3KV (UE) GRADE CABLE XLPE TYPE WITH STRANDED & COMPECTED AL. CONDUCTOR OF GR H2 7 CL. 2
DESIGN AMBIENT TEMPERATURE = 50 Deg. Cent

SL. NO. CABLE FROM

CABLE TO

POWER
HANDLING
KW/KVA
/KVAR

LOAD
CURRENT
(AMP.)

RATING
FACTOR
FOR 50 0 C
AMBIENT

RATING
FACTOR
FOR SIDE
BY SIDE
LAYING

REQD.
CURRENT
RATING
(AMP.)

NO. OF
RUNS

CABLE
SIZE
SELECTED

CURRENT
RATING OF
CABLE IN
AIR
(AMP)

FAULT
CLEARING
DURATION
(MILLI
SEC)

SYSTEM
FAULT
LEVEL
(KA) FOR
1 SEC.

EFFECTIVE
SHORT CKT
RATING
REQUIRED
(KA for 0.4 S)

TOTAL
CURRENT
CARRYING
CAPACITY
(AMP)

SEL.SHORT
CKT
RATING
OF CABLE
(KA for 0.4S)

11/3.3 KV, 3.5 MVA 3.3KV ACS 1000


CONV.TRANS.
DRIVE PANEL

3500

918.5387361

0.88

0.68

1534.991203

3C X 300

440

400

26

10.4

1760

70.5

3.3KV ACS 1000


DRIVE PANEL

2800

734.8309889

0.88

0.68

1227.992963

3C X 300

440

400

26

10.4

1320

70.5

3.3KV SAG MILL


MOTOR

2 OF 4

\\vboxsrv\conversion_tmp\scratch_1\255770790.xls.ms_office