WIND LOAD ANALYSIS
1. V = 150 kph, zone 3A (Palawan; table 207-11)
2. Kd = 0.85; Building (Main wind force resisting system) Table 207 -2
Iw = 1.15; Essential Occupancy (commercial bldg. more than 1 storey );
Table 207 3
3.
4.
5.
6.
3 2
8.71
126
14.6984
2
36
126
12.3564
1
17.5000
10.0625
2
3 2
54
29.2651
40.0000
47.3 10 6
9. Velocity pressure qz = (
) (0.81 )(1)(0.85)(150)2(1.15)
Qz = 0.84265 kPa
10.
Low-Rise Buildings and Buildings with h < 18 m; Components
and Cladding. Design wind load p=
p qz (GC p ) (GC pi )
kPa
Zone 1, 2 & 3
P13=0.84265 ((+0.3) (0.18)) =+.101, +.404
(kpa)
Zone 1
P1 = 0.84265((-0.8) (0.18)) = -.8256, -0.5224
(kpa)
Zone 2
P =0.84265((-1.2) (0.18)) = -1.1629, -0.86
(kpa)
Zone 3
P3 = 0.84265((-2.0) (0.18)) = -1.837, -1.5336
(kpa)