WIND LOAD ANALYSIS
1. V = 150 kph, zone 3A (Palawan; table 207-11)
2. Kd = 0.85; Building (Main wind force resisting system) Table 207 -2
Iw = 1.15; Essential Occupancy (commercial bldg. more than 1 storey );
Table 207 3
3.
4.
5.
6.

Kz = 0.89; z (21m); (Exposure B); Case 1


Kzt = 1; Section 207.5.7
G=0.85
Enclosed Building; Section 207.5.9.
7. Internal pressure coefficient GCpi = 0.18; Fig. 207-5
8. External pressure coefficients GCp ; Components and Cladding; Figure
207 -11c

3 2

8.71

126

14.6984

2
36

126

12.3564

1
17.5000

10.0625

2
3 2

54

29.2651

40.0000

Zone 3 = 2.75 x 2.75 = 7.5625 x 4 = 30.25m ; GCp = +3, -2


Zone 2 = (445.63-221.19) x 2 + (174.38-36) x 2 = 725.64m ; GCp= +3, -1.2
Zone 1 = (221.19 + 36) x 2 = 514.38m ; GCp = +3, -0.8

47.3 10 6

9. Velocity pressure qz = (
) (0.81 )(1)(0.85)(150)2(1.15)
Qz = 0.84265 kPa
10.
Low-Rise Buildings and Buildings with h < 18 m; Components
and Cladding. Design wind load p=
p qz (GC p ) (GC pi )

kPa

Zone 1, 2 & 3
P13=0.84265 ((+0.3) (0.18)) =+.101, +.404

(kpa)

Zone 1
P1 = 0.84265((-0.8) (0.18)) = -.8256, -0.5224

(kpa)

Zone 2
P =0.84265((-1.2) (0.18)) = -1.1629, -0.86

(kpa)

Zone 3
P3 = 0.84265((-2.0) (0.18)) = -1.837, -1.5336

(kpa)

2.7500
10.0000

Zone 3 = 2.75 x 2.75 = 7.5625 x 8 = 60.5m ; GCp = +3, -2


Zone 2 = (10 x 2.75) x 4 + (34.5 x 2.75) x 4 = 489.5m ; GCp= +3, -1.2
Zone 1 = (34.5 x 10) x 2 = 690.m ; GCp = +3, -0.8