Professional Documents
Culture Documents
Sr. No.
Contents
1.
2.
Principle of Operation
3.
Construction
4.
Operation Procedure
5.
Drain Discharge
6.
7.
Application
8.
Life of Collectors
9.
Replacement of Collectors
10.
Warranty
11.
12.
Electric Circuit
13.
14.
15.
Setting Parameters
16.
17
Trouble Shooting
Page No.
11
OPERATION MANUAL
1.
SPECIFICATIONS:
ELC-8 LP / 25 A / 50 C / 100 LP
Power Consumption
Power Source
Pump Capacity
8 LP
25 A, 25 D
ELC 8 LP
ELC 25A
ELC 50C
ELC 100LP
610 mm
380 mm
540 mm
805 mm
480 mm
720 mm
805 mm
480 mm
920 mm
870 mm
620 mm
940 mm
Weight (Approx)
70 kgs.
100 kgs
140 kgs
180 kgs
12
12
16
Collector (pcs/set)
2. PRINCIPLE OF OPERATION:
The ELC system uses the principle of electrostatics to collect fluid contaminants. FERROCARE
ELC's unique design permits it to take advantage of the natural charge of each contaminant.
Contaminants that have a positive charge are drawn towards the negative electrode plate and
those with a negative charge are drawn towards the positive plate. Neutral contaminants are drawn
and deposited by gradient force to the edge of the collectors where the intensity of the deformed
electric field is the strongest.
As the fluid flows freely through the system, the ELC removes contaminants - submicronic particles
even smaller than 0.01 micron, dust, dirt and products of oxidation such as tars or sludge and
varnishes. Contaminants are trapped on cellulose collectors for easy disposal. The ELC does not
affect soluble additives.
3. CONSTRUCTION:
A) The ELC consists of the electrical panel (A) and the condenser unit (B). The latter works as the
Cleaning Cell of the ELC unit.
B) The condenser (cleaning tank) is designed for pressure 1.5 kg/cm2.
The total head of oil between the oil reservoir to be cleaned and the ELC 8LP / 25A / 50C / 100LP
unit should not exceed 3 meters. In case the head exceeds 3 meters, use our D type machine.
ELC 100LP
HV-1
mA
mA
HV-2
KV
KV
WAIT
WAIT
FWR
REV
FWR
REV
START
STOP
START
STOP
PMP FWR
PMP FWR
PMP REV
PMP REV
HV
FERROCARE
LV
HV
LV
FERROCARE
This on delay timer switches off the pump every time the float switch is operated after the machine is
started, even after a power failure or shutdown. This ensures that the contaminants from the collector,
which may have been dislodged into the oil in the ELC tank during power failure or shut down are
redeposited on the collectors before the oil flow is restarted.
4b. STOPPING THE MACHINE: Press the Stop button (START/ STOP) to stop the machine. The
LED will switch off to indicate pump stoppage.
5. DRAIN DlSCHARGE When the ELC is continuously operated for a long time, it is advisable
to discharge about 1 litre of the oil from the drain valve (E) at an interval of 50 hours. This
ensures discharge of heavy contaminants from the drain.
6. DRAINING/ REMOVING CLEANED OIL FROM THE TANK
a)
b)
c)
d)
e)
f)
g)
h)
PRECAUTION: Do not pump out all the oil, care has to be taken to switch off the pump if dirty oil
starts flowing out of the machine.
i)
The oil at the bottom should be drained into the oil pan from the drain valve.
NOTE: If final oil is required to be NAS grade 7 (ISO code16/13) and better, do not drain oil from
the cleaning tank back to the reservoir.
j)
IMPORTANT: The oil pump can only be reversed by pressing the push button inside the
panel and the FWR/REV button on the control panel together, after opening the panel.
7. APPLICATION
The Electrostatic Liquid Cleaner "ELC" unit can be used for cleaning hydraulic and lubricating
oils of the following general specifications.
Temperature - below 60 degrees C and Moisture - below 500 ppm
The ELC unit cannot be used for cleaning of:
a) Oils with moisture in excess of 500 ppm
b) Oils with detergent dispersant additives
c) Some synthetic oils
d) Conductive oils
8. LIFE OF COLLECTORS
The life of collectors depends on the contamination level in the oil.
If contamination level is 7 to 10 mg/100 ml., a new collector set can clean about 5,000 litres
(ELC-50C) of oil. The average life of a collector is 2,000 hours.
A rough indication of collector life is as follows:
Type of ELC
ELC-8 LP
7.0-10.0mg
10-15mg
ELC-50 C
7.0-10mg
10-15mg
ELC-100LP
Contaminant
Level/ 100ml
7.0-10.0mg
Life of
Collectors
10-15mg
ELC-25 A
7.0-10mg
10-15mg
C
B
A
Fig. 5
Seal
Nut
Fig. 6
Hi-Volt
Cable
HV-1
mA
mA
HV-2
KV
KV
WAIT
WAIT
FWR
REV
FWR
REV
START
STOP
START
STOP
PMP FWR
PMP FWR
PMP REV
PMP REV
HV
LV
FERROCARE
100LP
HV
LV
FERROCARE
The panel displayed indicates that High Voltage is 10.6 kV and that machine is running with pump
in forward mode for ELC 100LP (fig. on left).
The panel displayed (fig. on right) indicates that current is 0.6 mA and the machine is running with
pump in forward mode for ELC 8LP / 25A / 50C .
For 100LP - indicator for HV-1 is green and display is V for Voltage. The 100LP machine uses
TWO High Voltage transformers, hence the LEDs are divided as HV-1 and HV-2.
For other ELCs - Indicator for milliamps is green and current is 0.6 mA. Since the machines have
only one transformer, the LED lights are separate for mA and kV.
The Pump Switch LED is ON, meaning pump is running forward.
The display will scroll across four parameters, namely, mA, kV (milliampere current and Voltage
across the electrodes), temperature and running hours in sequence. Each parameter will be
displayed for the duration set in Scroll Time setting
15 a. SETTING PARAMETERS:
Pressing the "SETTING" button
will select the
next parameter
for display.
16 b. SAFETY SETTINGS:
There is a push button inside the panel which allows the programming functions, so that the set
parameters cannot be disturbed by anyone playing with the push buttons.
Display of different parameters can still be selected, but settings cannot be changed until the
internal switch is activated after opening the panel cover.
2. Set Temperature:
3. L. V. Setting:
LV Setting: 05
(1 to 10)
This the setting for the Low Voltage operation of the ELC.
This sets the tripping current for the transformer when ELC
is operating on low voltage of 5 KV. In the particular case
above, the ELC will trip at 2 mA (for 25 A/ 8LP, 5mA for
50C/100 LP). This setting ensures safety of the
transformer.
4. L.V. Skip:
This sets the "Low" mode of the HVT.
If this parameter is set to "n" the transformer will change to
"Low" mode after the current set for Hi mode i.e., 10 mA is
exceeded (with a delay of 1 sec.)
If the current exceeds the "Low" (5 mA) also, the machine
will trip.
If this parameter is set to "y", the machine will trip directly
when "High" current is exceeded.
Scroll Time 03
(0 to 10)
SErv - Service
If Op. Hrs. = 1, then 250 Hrs.
Controller Trip on "SERV"
Recommended Settings:
50C . . . . . . . . 06 hrs.
100LP . . . . . . 06 hrs.
25A . . . . . . . . 05 hrs.
8LP . . . . . . . . 03 hrs.
LS - Limit Switch
FS - Float Switch
This error display means that the ELC tank cover is open.
When properly secured the cover operates a limit switch
and switches off this error message.
Trouble Shooting:
! Put back the top cover, if not in place and tighten all the
bolts securely.
! Check that the limit switch is OK.
There is a float switch which does not allow the
electrodes to be charged. If not totally immersed in oil.
When the float switch is activated, the motor will trip for
a five minute interval and restart. It will now run
continuously. This interruption is provided so that
contaminants from previous operation do not flow out
with the new oil, and are redeposited on the collectors. if
the pump does not start, or the float switch is faulty, then
also this error signal will appear. This error means that
there is insufficient oil in the tank. One reason is that oil
is not available to the pump. This alarm will come due to
Hi-volt fuse blown out.
Trouble Shooting:
! Check that the oil pump is running.
! Check if oil is available and the suction hose is properly
Trouble Shooting:
! Check that there is no obstruction to the discharge.
! Check the pump / motor are aligned and secured to the
foundation.
! Check the pump motor windings electrically.
! Check capacitor overload relay and contactors.
Trouble Shooting:
! Check whether there is moisture in the oil.
! Check if oil contains an excess of metal particles
If low switch over is "y" the machine will now switch to low
and if the current exceeds even the low setting the
machine will trip.
This indicates that the tripping current of the HVT is
reached in "Lo" mode.
L-oL - Current Over Load
in "Lo" mode
Trouble Shooting:
! Check whether there is moisture in the oil.
! Check if oil contains an excess of metal particles.
Temperature overload :
This indicates that the temperature of the oil flowing
through the machine is too high and the machine will stop.
10
Trouble Shooting:
! Check the setting is not too low.
! Check the oil cooler in the equipment.
! Heavy moisture in oil.
PROBLEM
CHECK
SOLUTIONS
1.
2.
ELC B + MCB
trips earth leakage
1. Rectify
2. Overhaul motor
3. Replace if faulty
3.
4.
4. Replace if faulty
5. Tighten properly
4. Readjust properly
5. Open and clean the
Rotor, and strainer mesh
6. Replace if faulty
7. Replace if capacitor
faulty rectify connection
8. Replace if faulty
5.
1. Open valve
2. Clean if choked
6.
7.
1. Replace if necessary
2. Tighten properly
11
NO. PROBLEM
CHECK
SOLUTIONS
8.
1. Thermal OLR
2. Y- strainer
3. Motor pump alignment
4. Motor winding weak
5. Power supply voltage (230/415)
6. Loose contact of contactor
power contact and OLR
9.
Fuse-1 blows
repeatedly.
10.
11.
12.
12