CW PUMPS
FOR CIRULATING WATER PUMPS
THE CAPACITY TO BE HANDLED IS
LARGE
THE HEAD TO BE DEVELOPED IS
LOW
THE SCHEME
THE Q OUT
FOR A 210 MW POWER PLANT THE Q
OUT IS ARROUND 248325000 KILO
CALORIES PER HOUR
CONSIDERING A T OF 9 C THE FLOW
REQUIRED IS 27591666.66 Kgs/Hr ie
27591.6 M3/Hr
WITH A 10 % MARGIN IT IS ARROUND
30500 M3/Hr
THIS IS THE CAPACITY WE HAVE
THE T
THE T IS THE RANGE OF COOLING
CONSIDERED IN COOLING TOWER
FOR A LESSER RANGE MORE WATER HAS
TO FLOW
FOR MORE WATER FLOW MORE SHOULD
BE THE SIZE OF CONDENSER
HENCE OPTIMAL VALUE HAS TO BE
CHOSEN
THE APPROACH
THE RANGE IS ALSO DEPENDING ON
THE APPROACH
ie APPROACH TO THE WET BULB
TEMPERATURE
WET BULB TEMPERATURE IS
DECIDED BY NATURE FOR A GIVEN
AREA
THE CW PUMP
THE CAPCITY IS HIGH AND THE HEAD
IS LOW
FOR THIS TWO TYPES OF PUMPS CAN
BE SELECTED
THE MIXED FLOW PUMP OR
THE AXIAL FLOW PUMP
THE CHOICE
AMONG THE TWO THE MIXED FLOW
IMPELLER IS THE PREFERED CHOICE
FROM THE H-Q CURVE IT IS
OBSERVED THAT POWER
CONSUMPTION OPTIMAL AT THE
OPERATING POINT FOR THE MIXED
FLOW PUMPS
PUMP CONSTRUCTION
DEPENDING ON THE QUALITY OF
WATER THE PUMP CAN BE
PULL OUT TYPE OR NON PULL OUT
TYPE
IN CASE OF PULL OUT TYPE THE LINE
SHAFT BEARINGS ARE LUBRICATED
WITH SEPARATE CLEAN WATER
OTHER CHOICES
WHEN THE CAPACITY TO BE
HANDLED IS LARGE ANOTHER
OPTION AVAILABLE IS CONCRETE
VOLUITE PUMPS
THE 500 MW SETS USE CONCRETE
VOLUTE PUMPS