INSTALLATION INSTRUCTIONS
APPLICATION
The TCONT800AS11AA Programmable Comfort Control provides electronic control of 24 Vac heating and cooling
systems. See Table 1 for a general description.
Changeover
Automatic or
manual
selectable
System Selection
Fan Selection
Heat-Off-Cool-Auto
On-Auto-Circ
Comments
System and Fan selection vary
based on system type
RECYCLE NOTICE
NO
NO
5 FEET
[1.5 METERS]
NO
INSTALLATION
When Installing this Product...
1.
2.
3.
Selecting Location
Install the comfort control about 5 ft. (1.5m) above the
floor in an area with good air circulation at average
temperature. See Fig. 1.
M19925
69-1787-1
Installing Wallplate
3.
4.
5.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power before wiring.
HEAT PUMP
HEAT/COOL
RC
RC
W1
S1
S1
S2
S2
SCREW TERMINALS
M22655
WALL
WIRES THROUGH WALL
AND WIRE SLOT
WALL ANCHORS (2)
System Type
MOUNTING
HOLES
MOUNTING
SCREWS (2)
Wallplate
Terminal
Identifications
Wiring
Diagram
Reference
Standard Heat/Cool
Heat/Cool
Fig. 5,
Fig. 6
Heat Pump
Fig.7
M19916
4.
5.
IMPORTANT
Use 18 gauge comfort control wire.
HEAT/COOL
HEAT/COOL
RC
R
W1
Y
G
B
RC
R
W1
Y
G
B
S1
S2
S1
S2
W1
W3
W2
AIR
HANDLER
B/C
B/C
OIL
FURNACE
INDOOR
OUTDOOR
ODT
COOLING UNIT
O.D. SECTION
(SINGLE STAGE)
(3 PH
ONLY)
TO POWER SUPPLY
PER LOCAL CODES
TO POWER SUPPLY
PER LOCAL CODES
COOLING UNIT
O.D. SECTION
(SINGLE STAGE)
(3 PH
ONLY)
M22657
HEAT PUMP
RC
R
O
Y
G
B
S1
S2
T
2
I-PF
W2
W1
W3
ODT-1
ODT-2
INDOOR
OUTDOOR
BR/X2
OR BK
PM-A
SUPPL. HTR.
CONTROL BOX
B/C
AIR
HANDLER
REQ.
FOR
TO POWER 3 PH
SUPPLY PER
LOCAL
CODES AND
AS DEFINED
IN FIELD
WIRING TABLE
BR(T)
TO POWER SUPPLY
PER LOCAL CODES
HEAT PUMP
O.D. SECTION
(SINGLE STAGE)
(3 PH
ONLY)
M22658
Fig. 7. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).
3
WALL
REMOVE DURING
INSTALLATION
CAUTION
M22643
REMOVE DURING
INSTALLATION
REMOVE DURING
INSTALLATION
M22644
M19918
OPERATION
SET CURRENT DAY
SET MONTH
MON
TUE
THU
FRI
RI
SAT
AT
SUN
SYSTEM Settings
Heat: controls heating system.
Off: both heating and cooling are off.
Cool: controls cooling system.
Auto: automatically changes between heating and
cooling systems, depending on indoor temperature. (See
Installer Setup section.)
DONE
FAN Settings
MON
WED
W
THU
FRI
SAT
AT
SUN
OK TO PICK MULTIPLE
U
DAYS SCREEN LOCKED
CHANGE FILTER
R UV LAMP HUMIDIFIER PAD
Preprogrammed Settings
Table 3 shows the default program settings. See Owners
Guide for complete instructions on changing the
program.
DONE
Schedule
Period
Setpoints
Time
Heat
Cool
Fan
Setting
Wake
6:00AM
70F
(21C)
78F
(25.5C)
Auto
Leave
8:00AM
62F
(16.5C)
85F
(29.5C)
Auto
Return
6:00PM
70F
(21C)
78F
(25.5C)
Auto
Sleep
10:00PM 62F
(16.5C)
82F
(28C)
Auto
INSTALLER SETUP
The comfort control works with many different system
types. To operate correctly, the comfort control must be
set up to operate the installed heating and/or cooling
system.
4.
THU
FAN
ON
DONE
Inside
Set To
AUTO
Following
Schedule
SYSTEM
EM HEAT
OFF
M22649
A
M
COOL
SCHED
HOLD
CLOCK SCREE
M22647
5.
3.
See screen below to review how the comfort control keys are used during Installer Setup. See Table
4 for Installer Setup Numbers and Settings.
ADVANCE TO NEXT
INSTALLER SETUP
INSTALLER
SETUP
NUMBER
MO
TU
Inside
WE
TH
FR
SA
SU
Set To
MON
SYSTE
M
EM
HEAT
CURRENT
SETTING
WED
THU
U
FRI
SAT
AT
SUN
Following
Schedule
OFF
DONE
CANC
DONE
O
PRESS TO EXIT
INSTALLER SETUP
M22648
6.
CHANGE THE
CURRENT
SETTING
M22650
Other Choices
Installer
Setup
Number
Option
Description
Options
Description
Comments
Not used.
1 thru 0099
Date (Year
Upper)
0120
20
Date (Year
Lower)
0130
05
Digit(s) represents
current calendar
month.
1-12
Date
(Day)
0150
15
Digit(s) represents
current calendar
date.
1-31
Schedule
Options
0160
7-day programming 0
0 nonprogrammable
System Type
Selection
0170
1 Heat/1 Cool
System
11 heat/1 cool
2single-stage heat pump
(no aux. heat)
3heat only (no fan)
4 heat only (with fan)
5hot water Series 20
(3-wire or normally open
zone valves)
6cool only
Available options
and defaults vary
by comfort
control. System
selection
automatically
modifies some
default settings
and/or hides other
Installer Setup
options.
Heat/cool appli1
cations where
equipment controls
fan operation in
heat mode.
Only shown if
heat/cool system
is selected. If heat
pump is chosen,
fan defaults to
electric.
Cycles per
0220
hour (cph) for
1st Stage
Compressor
Compressor Stage
1 cycles per hour
(cph)
1-6
1-6 available;
3 is recommended.
Cycles per
0240
hour (cph) for
Heater
Stage 1
Heater Stage 1
cycles per hour
(cph).
1-12
Select
1-6
2000 -2178
available
Not shown if
system selection
is heat pump.
Selection in this
stage changes
default cph for
2nd stage heat.
Select
Installer
Setup
Number
Option
Description
Other Choices
Options
Description
Comments
Continuous
Backlight
0280
Backlight not on
continuously.
Comfort control
backlight comes
on with each key
press.
Changeover
0300
Manual changeover 1
1auto changeover
Deadband
0310
Temperature
Indication
Scale
0320
Temperature is
displayed in F.
Temperature is displayed
in C.
Daylight
Savings
0330
Daylight savings
enabled (United
States).
0daylight savings is
disabled.
Set to 0 in areas
that do not follow
daylight savings.
Remote
Temperature
Sensor
(Outdoor or
Indoor)
0340
No remote
1,3
temperature sensor
1outdoor temperature
sensor for display only.
3indoor temperature
sensor.
Defaults and
Options depend
on System Type
selected. Indoor
Temperature
Sensor uses an
averaging
network and does
not include onboard sensor.
Furnace filter
1-6
change reminder off
Humidifier
0510
Pad
Replacement
Reminder
Humidifier pad
replacement
reminder off
1-3
Backlight is on continuously
(comfort control must have a
common wire attached for
this function).
Option is always
shown; however,
continuously on
backlight works
only if comfort
control is wired
with 24 Vac
Common.
Shown only if
automatic
changeover is
selected.
Select
Installer
Setup
Number
Option
Description
Other Choices
Options
Description
Comments
Adaptive
Intelligent
Recovery
0530
Adaptive Intelligent 0
Recovery control
is activated (system
starts early so
setpoint is reached
by start of program
period).
0conventional recovery
(system starts recovery at
programmed time)
Number of
Periods
0540
Four periods
available (Wake,
Leave, Return,
Sleep)
Minimum
Compressor
Off Time
0580
Five-minute
minimum off time
for compressor
Heat
Temperature
Range Stop
0600
90
Highest heating
setpoint.
40 to 89
Shown in 1/2 C.
Cool
Temperature
Range Stop
0610
50
Lowest cooling
setpoint.
51 to 99
Shown in 1/2 C.
12
12-hour clock
format
24
No extended fan
operation after call
for heat ends
90
No extended fan
operation after call
for cool ends
90
Keypad
Lockout
Unlocked keypad
1, 2
1partially locked
keypad
2fully locked keypad
0670
Unlockedall
functions are
available.
Partially locked
only temperature
up and down keys
and ability to
enter and modify
Installer Setup
mode are
available.
Fully locked
only ability to
enter and modify
Installer Setup
mode are
available.
Select
Temperature
Control in
Heat
Installer
Setup
Number
0680
Option
2
Description
Other Choices
Options
Standard
1, 3
temperature control
in heating
Description
1less aggressive
temperature control (could
cause temperature
undershoot)
3more aggressive
temperature control (could
cause temperature
overshoot)
Comments
Applies to
recovery ramp
and use of
auxiliary heat
during recovery.
Choose 1 if
getting
temperature
overshoot.
Choose 3 if
getting
temperature
undershoot.
Temperature
Control in
Cool
0690
Standard
1, 3
temperature control
in cooling
1less aggressive
temperature control (could
cause temperature
undershoot)
3more aggressive
temperature control (could
cause temperature
overshoot)
Applies to
recovery ramp.
Choose 1 if
getting
temperature
overshoot.
Choose 3 if
getting
temperature
undershoot.
Temperature 0700
Display Offset
No difference in
displayed
temperature and
actual room
temperature
Reset
Comfort
Control
No comfort control
reset.
0710
10
Only calendar
settings and time
are retained.
SYSTEM CHECKOUT
ADVANCED FEATURES
CAUTION
Select
Installer
Setup
Number
Factory Setting
Options
Description
Other Choices
Options
Description
Comments
Installer Test
Cool
Test 1
Cool is off
0cool off
1cool stage 1
turns on
Installer Test
Fan
Test 2
Fan is off
0fan off
1fan turns on
Installer Test
Heat
Test 3
Heat is off
0heat off
1stage 1heat on
11
Possible Cause
Action
Heating or cooling
equipment is not operating.
Check wiring.
Check Installer Setup Number 0170; verify correct
system type is chosen.
Verify equipment operation in System Test mode.