Air System Sizing Summary for Santa Maria Business Park

Project Name: Santa Maria Business Park 62.1


Prepared by:

10/03/2014
09:46a.m.

Air System Information


Air System Name ........ Santa Maria Business Park
Equipment Class ......................................... UNDEF
Air System Type .......................................... SZCAV

Number of zones .......................................................... 1


Floor Area ......................................................... 66461.8 ft
Location .................................... Panama City, Panama

Sizing Calculation Information


Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated

Zone CFM Sizing .............. Sum of space airflow rates


Space CFM Sizing .......... Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load ................................................. 417.2
Total coil load ............................................... 5006.1
Sensible coil load .......................................... 4750.0
Coil CFM at Jul 0800 ................................... 212665
Max block CFM ............................................ 212665
Sum of peak zone CFM ............................... 212665
Sensible heat ratio .......................................... 0.949
ft/Ton ............................................................. 159.3
BTU/(hr-ft) ....................................................... 75.3
Water flow @ 10.0 F rise ........................... 1001.76

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at ................................................. Jul 0800


OA DB / WB .................................................. 81.7 / 72.4
Entering DB / WB .......................................... 78.3 / 64.2
Leaving DB / WB ........................................... 57.6 / 56.3
Coil ADP ................................................................. 55.3
Bypass Factor ....................................................... 0.100
Resulting RH .............................................................. 47
Design supply temp. ................................................ 60.0
Zone T-stat Check ................................................ 0 of 1
Max zone temperature deviation ............................... 3.0

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM .......................................... 212665 CFM
Standard CFM ............................................. 212266 CFM
Actual max CFM/ft ........................................... 3.20 CFM/ft

Fan motor BHP ................................................... 203.85 BHP


Fan motor kW ..................................................... 161.71 kW
Fan static ................................................................ 3.50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ......................................... 7909 CFM
CFM/ft ............................................................. 0.12 CFM/ft

Hourly Analysis Program v4.80

CFM/person .......................................................... 10.25 CFM/person

Page 1 of 8

Zone Sizing Summary for Santa Maria Business Park


Project Name: Santa Maria Business Park 62.1
Prepared by:

10/03/2014
09:46a.m.

Air System Information


Air System Name ........ Santa Maria Business Park
Equipment Class ......................................... UNDEF
Air System Type .......................................... SZCAV

Number of zones .......................................................... 1


Floor Area ......................................................... 66461.8 ft
Location .................................... Panama City, Panama

Sizing Calculation Information


Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated

Zone CFM Sizing .............. Sum of space airflow rates


Space CFM Sizing .......... Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
2821.6

Design
Airflow
(CFM)
212665

Minimum
Airflow
(CFM)
212665

Time of
Peak Load
Jul 1600

Maximum
Heating
Load
(MBH)
0.0

Zone
Floor
Area
(ft)
66461.8

Zone
CFM/ft
3.20

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
MEZZANINE
OFICINA A N400
OFICINA A N500
OFICINA A N600
OFICINA A N700
OFICINA A N800
OFICINA B N200
OFICINA B N300
OFICINA B N400
OFICINA B N500
OFICINA B N700
OFICINA B N800
OFICINA C N700
Oficina N000
VESTIBULO

Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

90.3
257.0
257.0
452.5
261.4
261.9
162.0
167.8
222.5
214.0
134.3
222.2
100.3
130.0
47.0

Jul 1500
Dec 1600
Dec 1600
Oct 1600
Dec 1600
Dec 1600
Jun 1600
Jun 1600
Jun 1600
Jun 1600
Jun 1600
Jun 1600
Mar 0900
Sep 0900
Jul 1500

6440
18341
18341
32290
18650
18692
11563
11975
15874
15270
9587
15855
7157
9276
3353

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

2190.5
5630.6
5630.6
10801.6
5530.5
5630.6
3382.0
3468.1
5630.6
5171.0
2560.7
5171.0
2712.5
2190.5
761.0

2.94
3.26
3.26
2.99
3.37
3.32
3.42
3.45
2.82
2.95
3.74
3.07
2.64
4.23
4.41

Page 2 of 8

Ventilation Sizing Summary for Santa Maria Business Park


Project Name: Santa Maria Business Park 62.1
Prepared by:

10/03/2014
09:46a.m.

1. Summary
Ventilation Sizing Method ...................................... ASHRAE Std 62.1-2007
Design Condition ........................................................... Cooling operation
Occupant Diversity .............................................................................. 1.000
Uncorrected Ventilation Airflow Rate .................................................... 7847 CFM
System Ventilation Efficiency .............................................................. 0.992
Design Ventilation Airflow Rate ............................................................ 7909 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
MEZZANINE
OFICINA A N400
OFICINA A N500
OFICINA A N600
OFICINA A N700
OFICINA A N800
OFICINA B N200
OFICINA B N300
OFICINA B N400
OFICINA B N500
OFICINA B N700
OFICINA B N800
OFICINA C N700
Oficina N000
VESTIBULO
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.80

Mult.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Supply
Air
(CFM)
6440
18341
18341
32290
18650
18692
11563
11975
15874
15270
9587
15855
7157
9276
3353
212665

Floor

Required

Area

Outdoor Air

(ft)

(CFM/ft)

2190.5
5630.6
5630.6
10801.6
5530.5
5630.6
3382.0
3468.1
5630.6
5171.0
2560.7
5171.0
2712.5
2190.5
761.0

0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06

Time

Required

Air

Required

Uncorrected

Space

Averaged

Outdoor Air

Distribution

Outdoor Air

Outdoor Air

Ventilation

Occupancy (CFM/person) Effectiveness

(CFM)

(CFM)

Efficiency

259
665
665
1275
653
665
399
409
665
611
302
611
320
259
90

259
665
665
1275
653
665
399
409
665
611
302
611
320
259
90
7847

0.997
1.001
1.001
0.997
1.002
1.001
1.002
1.003
0.995
0.997
1.005
0.998
0.992
1.009
1.010
0.992

25.4
65.4
65.4
125.4
64.2
65.4
39.3
40.3
65.4
60.1
29.7
60.1
31.5
25.4
8.8

5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

Page 3 of 8

Air System Design Load Summary for Santa Maria Business Park
Project Name: Santa Maria Business Park 62.1
Prepared by:

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

10/03/2014
09:46a.m.

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 0800
HEATING DATA AT DES HTG
COOLING OA DB / WB 81.7 F / 72.4 F
HEATING OA DB / WB 73.0 F / 60.9 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
38360 ft
988169
38360 ft
4191 ft
8115
4191 ft
0
10802 ft
6640
10802 ft
0
38360 ft
152060
38360 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
5032 ft
5032
5032 ft
0
1930 ft
1930
1930 ft
0
132924 W
271384
0
0
0W
0
0
0
132924 W
412089
0
0
772
140709
158222
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
198613
15822
0%
0
0
2184741
174044
0
0
4013253
174044
0
0
30%
21569
0
0
70%
15494
0
0
30%
136061
0
0
212665 CFM
0
212665 CFM
0
7909 CFM
11822
82227
7909 CFM
-10231
-1035
212665 CFM
551781
212665 CFM
-551781
0
0
0%
0
0%
0
4749979
256271
-562011
-1035
4749978
256161
-562012
0
4749978
256161
-562012
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 4 of 8

Zone Design Load Summary for Santa Maria Business Park


Project Name: Santa Maria Business Park 62.1
Prepared by:

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.80

10/03/2014
09:46a.m.

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 94.5 F / 75.9 F
HEATING OA DB / WB 73.0 F / 60.9 F
OCCUPIED T-STAT 73.0 F
OCCUPIED T-STAT 70.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
38360 ft
1347008
38360 ft
4191 ft
14293
4191 ft
0
10802 ft
12529
10802 ft
0
38360 ft
303092
38360 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
5032 ft
5032
5032 ft
0
1930 ft
1930
1930 ft
0
132924 W
290715
0
0
0W
0
0
0
132924 W
429472
0
0
772
161003
158222
0
0
0
0
0
0
0
0
0
0
0
10% / 10%
256508
15822
0%
0
0
2821583
174044
0
0

Page 5 of 8

System Psychrometrics for Santa Maria Business Park


Project Name: Santa Maria Business Park 62.1
Prepared by:

10/03/2014
09:46a.m.

July DESIGN COOLING DAY, 0800


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Ventilation Reclaim
Vent - Return Mixing
Central Cooling Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
81.7
79.6
78.3
57.6
60.0
60.0
77.5
78.3

Specific
Humidity
(lb/lb)
0.01499
0.01170
0.00959
0.00933
0.00933
0.00933
0.00951
0.00951

Airflow
(CFM)
7909
7909
212665
212665
212665
212665
212665
212665

CO2 Level
(ppm)
400
400
1186
1186
1186
1186
1217
1217

Sensible
Heat
(BTU/hr)
11822
17732
4749978
551781
4013253
173123

Latent
Heat
(BTU/hr)
82227
123168
256161
174044
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4737.7 BTU/(hr-CFM)
Site Altitude = 52.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
2184741

Zone
T-stat
Cond
Mode (BTU/hr)
Cooling 4013253

Zone
Temp
(F)
77.5

Zone
Airflow
(CFM)
212665

CO2
Level
(ppm)
1217

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 6 of 8

System Psychrometrics for Santa Maria Business Park


Project Name: Santa Maria Business Park 62.1
Prepared by:

10/03/2014
09:46a.m.

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Ventilation Reclaim
Vent - Return Mixing
Central Cooling Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
73.0
71.2
70.0
67.6
70.0
70.0
70.0
70.0

Specific
Humidity
(lb/lb)
0.00864
0.00859
0.00857
0.00857
0.00857
0.00857
0.00857
0.00857

Airflow
(CFM)
7909
7909
212665
212665
212665
212665
212665
212665

CO2 Level
(ppm)
400
400
654
654
654
654
664
664

Sensible
Heat
(BTU/hr)
10231
15346
562012
551781
0
0

Latent
Heat
(BTU/hr)
1035
1550
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4737.7 BTU/(hr-CFM)
Site Altitude = 52.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.80

Zone
Sensible
Load
(BTU/hr)
0

Zone
T-stat
Cond
Mode (BTU/hr)
Deadband
0

Zone
Temp
(F)
70.0

Zone
Airflow
(CFM)
212665

CO2
Level
(ppm)
664

Terminal
Heating
Coil
(BTU/hr)
0

Zone
Heating
Unit
(BTU/hr)
0

Page 7 of 8

Psychrometric Analysis for Santa Maria Business Park


Project Name: Santa Maria Business Park 62.1
Prepared by:

10/03/2014
09:46a.m.

Location: Panama City, Panama


Altitude: 52.0 ft.
Data for: July DESIGN COOLING DAY, 0800
0.020

1. Outdoor Air
2. Ventilation ReclaimOutlet
3. Mixed Air
4. Central Cooling Coil Outlet
5. SupplyFan Outlet
6. RoomAir
7. Return PlenumOutlet

0.018
0.016

2
4

0.012

63

0.010

0.008
0.006

Specific Humidity ( lb/lb )

0.014

0.004
0.002
0.000
30

Hourly Analysis Program v4.80

40

50

60
70
Temperature ( F )

80

90

100

Page 8 of 8