Flue Gas Temperature @ Eco inlet, TGin

Flue Gas Temperature @ Eco outlet TGout


Feed water Temperature @ Eco inlet TW in
Feed water Temperature @ Eco outlet
TWout
Flue gas volume flow rate @ 435 Deg C
Existing Heat Transfer Area

=
=
=

435
245
105

=
=
=

175
27.91
212.45

Flue Gas density @ 0 Deg C


Flue Gas density @ 435 Deg C
Flue Gas density @ 435 Deg C

=
=
=

Deg C
Deg C
Deg C
Deg C
m3/sec
m2

1.2 Kg/m3
(1.2 x 273) / (273 + 435)
0.46 Kg/m3

Tube OD
Straight length (Bend to Bend)
No of straight length segments
No of loop

50.8
3200
64
7

mm
mm
Nos
Nos

Casing Width
Casing Length (Excluding baffle plate)
Flue gas volume flow rate at Eco I/L (435 Deg C)
Available area for flue gas flow

1100
3277
27.91
2.44

mm
mm
m3/s
m2

In the modified Inline Design we can increase the Straight length (Bend to Bend)
up to the 4200 mm Max. We dont have the margin on Casing Width.