Professional Documents
Culture Documents
TABLE OF CONTENTS
GLOSSARY ............................................................................................................................ 5
1
INTRODUCTION ...................................................................................................... 7
1.1
1.2
1.3
Objective .................................................................................................................. 7
SCOPE ..................................................................................................................... 8
4.1
4.1.1
Air ........................................................................................................................... 12
4.1.2
4.1.3
Rainfall. .................................................................................................................. 12
4.1.4
4.2
4.3
DESIGN ................................................................................................................. 15
5.1
General .................................................................................................................. 15
5.2
Maintenance ........................................................................................................... 15
5.3
5.4
5.5
5.6
5.6.1
5.6.2
Reservoir ................................................................................................................ 16
5.6.3
5.6.4
5.6.5
Filters ..................................................................................................................... 17
5.6.6
Accumulation .......................................................................................................... 18
5.6.7
5.6.8
5.7
5.7.1
5.7.2
Genesis
File name:
Page 2 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
5.7.3
5.7.4
Wireline Valves....................................................................................................... 20
5.8
6.1
6.2
Radio ...................................................................................................................... 23
6.3
Antenna .................................................................................................................. 24
6.4
7.1
General .................................................................................................................. 26
7.2
Materials ................................................................................................................. 27
TESTING ................................................................................................................ 28
8.1
General .................................................................................................................. 28
8.2
8.3
8.4
PRESERVATION ................................................................................................... 30
10
DOCUMENTATION ............................................................................................... 31
11
PACKAGING ......................................................................................................... 32
12
REFERENCES ....................................................................................................... 33
Genesis
File name:
Page 3 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
HOLDS LIST
HOLD
Description
Section
5.6.1
6.2 & 6.3
REVISION HISTORY
REV.
Genesis
File name:
Description
Page 4 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
Section
March 13
GLOSSARY
AES
AISI
API
ATEX
Atmosphere EXplosibles
BS
British Standard
DIN
EGPC
EIA
EMC
EN
European Norm
ESD
Emergency Shutdown
FAT
FEED
F&G
HP
High Pressure
HPU
ICSS
IEC
IEEE
I/O
Input/Output
ISO
LP
Low Pressure
MV
Master Valve
NAS
Genesis
File name:
Page 5 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
NOSPCO
ONS
PoE
PUWER
QA
Quality Assurance
RTU
Rx
Reciever
SAT
SDRL
SOV
Solenoid Valve
SSSV
TCP
Tx
Transmitter
TIA
VHF
VSAT
WCP
WV
Wing Valve
Genesis
File name:
Page 6 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
1 INTRODUCTION
1.1
Project Description
This project covers the topside design of the Kamose platform from the tie-in to the
Christmas tree at the wellhead to the cottom of the export riser, as well as the design
of the platform itself. The rest of the ONS phase II project is outside of this project
Scope.
1.3
Objective
This document defines the minimum requirements for the design, fabrication,
inspection and testing of an electro / hydraulic wellhead control system designed for
two topside wells. Wellhead Control Panel (WCP) shall also contain a programmable
Remote Terminal Unit (RTU) and radio for transmitting signals between Tao &
Kamose platforms.
Genesis
File name:
Page 7 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
2 SCOPE
The Suppliers scope of work shall include the design, supply, inspection, Q.A.,
system testing, certification and documentation, including operational handbooks
necessary for good operation and maintenance of the specified system.
The Supplier will assume full responsibility; this means the Supplier shall guarantee
operability, quality of all components inclusive of all sub-suppliers and conformance
to authority and code requirements.
The unit design shall be based on a fit for purpose philosophy and shall utilise, as far
as possible, tried and tested designs, previously implemented in the European
offshore environment.
Supplier scope of work shall include design, fabrication, testing, calibration and
packing for shipment and supply of all materials and documentation necessary for
good operation and maintenance for the system.
Supplier shall provide nameplates for all instruments and equipment.
Genesis
File name:
Page 8 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
Title
American Petroleum Institute (API)
API Spec 6A
API RP 14C
API RP 500
Instrumentation
API RP 520
API RP 521
API RP 550
BS 5760
BS 6174
BS 6447
EIA/TIA (RS)
232
EIA/TIA (RS)
422
EIA/TIA (RS)
485
Genesis
File name:
Page 9 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
Reference
Title
International Electro-Technical Commission
IEC 60529
IEC 60079
IEC 60096-2
IEC 60227
IEC 60331
IEC 60332
IEC 60439
IEC 60584
Thermocouples
IEC 60751
IEC 60947
IEC 61131-1
IEC 61131-2
IEC 61131-3
IEC 61508
IEC 61511
Genesis
File name:
Page 10 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
Reference
Title
Institute of Electrical & Electonics Engineers
IEEE 802
IEEE C37.1
ISO 9001
EI 15
EN 61000-6-1:
2007
EN 61000-6-2:
2005
Miscellaneous
ATEX
Directive
94/9/EC
73/23/EEC
89/336/EEC
NAS 1638
SNT-TC-1 A
Genesis
File name:
Page 11 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
4 ENVIRONMENTAL DATA
The following data shall be used for design purposes. Should the Supplier consider
that other data is required for the design or supply of the equipment, or that the
omission of certain data could either affect the cost or compromise any safety aspect
of the design, this should be requested in writing prior to submission of the bid.
The equipment will be located on an offshore production platform in the
Mediterranean Sea, 50 km offshore from the North coast of Sinai and consequently
will be subjected to the effects of a highly saliferous atmosphere coupled with high
temperature and humidity.
All components and accessories inside the well head control package shall be
suitable for continuous operation under the outside environmental conditions stated
below.
4.1
Meteorological Data
4.1.1
Air
The air quality should be considered to be a highly corrosive marine climate with
high moisture and salt levels.
The dry bulb temperatures, for the design of offshore facilities above the splash
zone, are as follows:
Average
Design
Summer:
27 to 31C
40C
Winter:
11 to 24C
5C
4.1.2
Summer:
25C
Winter:
15C
4.1.3
Rainfall.
Maximum (winter):
Maximum (summer):
Annual average:
40 mm/year
Genesis
File name:
Page 12 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
4.1.4
Wind Data
The mean hourly wind speeds at 10m above sea level, indicating the directions from,
are shown below:
Table 3-1 Mean Hourly Wind Speeds
Direction
from North
1 Year
m/sec
10 Year
m/sec
100 Year
m/sec
9.2
10.8
12.3
30
9.6
11.7
13.5
60
10.2
13.1
15.6
90
8.6
11.5
14.2
120
8.0
11.0
13.8
150
7.1
9.6
11.9
180
7.9
10.7
13.2
210
12.1
16.9
21.3
240
14.3
18.4
22.1
270
14.1
17.2
20.0
300
12.1
14.0
15.8
330
12.0
14.2
16.1
OMNI
14.3
18.4
22.1
The omni-directional wind speeds in m/sec for other sample intervals are shown
below.
Table 3-2 Omni Directional Wind Speed
Omni directional
1 Year
m/sec
10 Year
m/sec
100 Year
m/sec
1 hour mean
14.3
18.4
22.1
10 minute mean
15.3
19.9
24.0
1 minute mean
16.6
21.7
26.4
3 second gust
18.3
24.1
29.6
Genesis
File name:
Page 13 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
4.2
Hazardous Area
All equipment located in the wellhead hydraulic unit shall be suitable for the following
hazardous area:
Electro-Magnetic Compatibility
Genesis
File name:
Page 14 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
5 DESIGN
5.1
General
The WCP shall consist of an integral skid mounted Hydraulic Power Unit (HPU),
Remote Terminal Unit (RTU), radio/modem and operator controls for two topside
wells.
The Hydraulic Power Unit shall provide hydraulic power for the well valves and
additional topsides ESD and HIPPS valves as defined in Section 5.6.1 of this
specification. The hydraulic fluid shall be Castrol Transaqua HT, cleaned to
NAS1638 class 6.
The programmable Remote Terminal Unit shall provide the required minimum
automatic control and ESD/F&G shutdown functions required for the safe shutdown
of the platform.
The Platform power supply will be derived from a solar power package. The design
of the WCP shall minimize its electrical power usage whilst ensuring that the overall
system can be safely operated.
The design and controls must be kept as simple as possible, consistent with safe
and reliable operation. Failure of any part of the system / package shall be to the
safe or isolated condition.
The WCP shall be of the fully enclosed type and is to be lockable.
There is no instrument /plant air supply available on the platform.
An overview of the system is shown on Wellhead Typical Detail P&ID -Drawing No:
J08617A-P-DW-15420 / 15421.
5.2
Maintenance
The platform will be designed for infrequent maintenance visits. The WCP shall be
designed to ensure that the interval between periodic maintenance visits is
maximised. The Supplier shall advise, in his bid, the expected maintenance interval.
5.3
Structural Design
The structural design of the WCP shall, in addition to the normal static loads, take
account of transportation loads and include for acceleration to 1 g in any direction
and roll motions of 20 with a 10 Sec period.
Genesis
File name:
Page 15 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
The layout of equipment and instrument items shall allow ease of access for
maintenance.
The layout of equipment and instrument items shall be determined by supplier
subject to purchaser approval.
5.5
Standardisation of Sub-suppliers
The Purchaser will select the project supplier for electric motors, mechanical seals,
mechanical couplings, and general instrumentation and instrument fittings. Suppliers
shall define the manufacturers offered as sub-suppliers in these categories, in their
bids.
5.6
5.6.1
System Design
System Capacity
The system shall be sized to operate valves at capacities and pressures stated
below (HOLD 1)
Valve Type
Quantity
Min Op.
Press
(Barg)
Norm Op.
Press
(Barg)
Max Op.
Press
(Barg)
Approx.
Swept
Volume
(Litres)
150
200
207
1.6
150
200
207
0.4
250
310
345
0.1
5.6.2
Reservoir
A reservoir shall be provided for the supply and return fluid from the well valves.
The reservoir shall have sufficient capacity to supply and operate the maximum
system configuration referred to in this specification, including hydraulic accumulator
volume.
Genesis
File name:
Page 16 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
The supply reservoir shall be provided complete with drain valve, level gauge, & two
level transmitters (1 for ESD, 1 for monitoring) covering the full range of the reservoir
with isolation valves, clean out bulkhead plate, tank breather and magnetic particle
collector & sample points.
Fresh fill fluid shall be filtered before use.
5.6.3
Pumps shall generate one level of hydraulic pressure (LP), with intensifiers to
generate the HP supply:
LP
200 Barg for MVs, WVs and other platform valves. (HOLD 1)
HP
One electric driven pump shall be provided to deliver hydraulic fluid at the lower
pressure level. Dual (duty/standby) pressure intensifiers shall be provided to supply
fluid at the higher pressure level.
The pump shall be installed complete with suction block valve, discharge check
valve, discharge relief valve, discharge double block and bleed valve. Pump shall
have a discharge pressure gauge, a discharge pressure transmitter, inlet & outlet
filters as required.
Supplier to advise method of control & pressure settings for the pump start/stop
within the installation and operation manual.
Pump motor shall be provided with an emergency stop latching pushbutton unit.
A manually operated pump shall also be provided, in parallel with the above electric
pump, this pump shall also be supplied with suction block valve, discharge block
valve, discharge relief valve, discharge double block and bleed valve and discharge
pressure gauge.
5.6.4
Clean-up Loop
The system shall be provided with a clean up pump and filter system for cleaning of
the reservoir contents, the pump shall be manually operated. The clean up system
shall include valves to allow replacement of the filter elements before recirculation of
fluid from and to the storage reservoir. Valving shall also allow pump to be used to
fill/top-up supply reservoir using a quick connect coupling and barrel lance assembly.
5.6.5
Filters
Genesis
File name:
Page 17 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
5.6.6
Accumulation
Once a well has been opened, the system shall replenish the accumulators to their
normal pressures within 30 minutes.
5.6.7
The panel shall have the following front of panel controls and indications:
ESD pushbutton
Open / Close pushbuttons for all SSSVs, Master and Wing valves
Genesis
File name:
Page 18 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
NOTE:
To reduce number of signals sent to the Onshore Control room, low/high pressure
alarms shall be combined with the reservoir low/high level alarms to provide a
common status alarm signal.
Fusible loop header shall have one pressure transmitter for low low pressure
F&G/ESD function.
Transmitters shall be SMART type with integral indicators.
All process pressure gauges shall be fitted with snubbers.
Supplier shall provide sizing calculations for each relief valve.
5.6.8
Valve Connections
5.7.1
Each platform well control module shall have the following front of panel indication:
Pressure gauge for hydraulic supply to each of SSSV, MV & WV.
5.7.2
Equipment mounted back of panel on each topsides well control module shall
include:Pressure transmitters for remote indication of each SSSV position.
One solenoid valve for each MV, SSSV and WV (controlled by the RTU/ESD
system)
Wireline key lockable 2 position selector valves
Genesis
File name:
Page 19 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
5.7.3
Sequence of operation
Sequencing of well valve operation will be carried out by the RTU/ESD. Sequence
and time delay requirements are to be defined by Purchaser.
The hydraulic system shall include adjustable flow control valves to delay closure of
the SSSV until after the master and wing valves have closed. This is to prevent
premature SSSV closure in the event of loss of electrical power to the system
solenoid valves, or loss of hydraulic pressure.
Well Shutdown: The well valves will be closed in the following sequence wing,
master and then SSSV. There will be a 5 second delay between wing and master
closure initiation this will be implemented in the RTU/ESD. There will be a 15 second
delay between master and SSSV closure initiation this will be implemented in the
WHU.
Signal Failure or Hydraulic Loss: On loss of signal or hydraulic pressure there will be
a 15 second delay between master and SSSV closure initiation this will be achieved
by a hydraulic timer in the WHU.
System shall be designed to ensure closure of platform well valves within 30
seconds of demand.
5.7.4
Wireline Valves
During wire lining workover operations the MV & SSSV of the selected well shall be
under the control of the wireline or workover crew.
A well will be placed in wireline control by using the lockable valves on the
appropriate well control module.
The wireline connection from each of these valves shall be tubed to 12mm bulkhead
connectors on the exterior of the WHU.
5.8
Fusible Loop
The WCP shall be connected to a common process area hydraulic fusible loop
system with frangible bulbs and supply/return tubing. The unit shall include a
pressure transmitter which will be connected to the RTU/F&G system.
Supplier shall provide a pressure letdown system within the WHU to operate and
monitor the loop system at 6 barg. Supplier shall provide 30 off suitable frangible
bulb change-over valves for site installation by others.
Genesis
File name:
Page 20 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
All tubing, fittings, cables, junction box and hook-up material for complete installation
to be in Suppliers scope of work.
Genesis
File name:
Page 21 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
Suitable for use in a Zone 2 Gas Group IIA Temperature Class T3 hazardous
area.
Inherent reliability
Data logging
Time stamping
Extensive diagnostics
Genesis
File name:
Page 22 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
The F&G logic will interface directly with the platform ESD logic to initiate local
executive actions and activate audible and visual alarms. The F&G status will
be communicated to the onshore remote terminal
Inputs to the ESD logic will be from both analogue and digital devices with outputs
generally being fail safe, de-energise to trip.
The ESD status will be displayed in the jack-up drilling rig, when it is on-station.
The ESD system will be programmed in accordance with the requirements of the
Kamose platform F&G and ESD Cause & Effect Diagrams J08617A-J-CF-13460
The safety systems for Kamose will be configured as fail safe. Loss of power or
utilities or open circuit on inputs and/or outputs will result in external equipment going
to a safe condition.
The F&G logic will interface with various types of field devices used for F&G
detection, the F&G element of the RTU shall have standard interfaces for all
commonly used detector systems.
Fire and Gas detectors that require occasional maintenance will be provided with an
override function accessed via the RTU interface, these provide inhibit and enabling
functions thus permitting routine work.
The F&G system will be programmed in accordance with the requirements of the
Kamose platform F&G and ESD Cause & Effect Diagrams J08617A-J-CF-13460.
Selected data shall be transmitted to the onshore remote terminal via a VHF radio
link between Kamose and Tao platforms and a line of sight microwave radio system
and VSAT between Tao platform and onshore. For details of data to be transmitted
between Kamose platform and onshore refer to J08617A-J-AE-13470 Kamose
Offshore Instrument Index.
A laptop shall be provided loaded with all the relevant software to enable operator to
interface with the RTU. Laptop will allow operator to connect to the RTU to setup/configure controllers and display data during a platform visit.
6.2
Radio
A high speed digital data VHF radio shall be mounted in the WCP and shall be
connected to the RTU using an Ethernet link.
Radio requirements to be, but not limited to the following:
Genesis
File name:
Page 23 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
Frequency range:
Operational modes:
Configuration:
Diagnostics:
Transmission:
Ethernet Protocol:
Modbus/TCP
Encryption:
Connections:
Power supply:
24VDC
Housing:
Rugged enclosure
Mounting:
DIN rail
Handset:
Yes
Vendor to ensure that selected frequency channels comply with Egyptian regulatory
standards.
6.3
Antenna
Antenna shall be a Yagi type with a narrow beam width suitable for point to point
communication. It shall have a high front to back ratio to help minimize potential
interference to and from other radio systems.
Antenna shall be constructed of heavy duty stainless steel and be suitable for use in
an offshore environment as stated in Section 3.1.
Antenna requirements to be, but not limited to the following:
Frequency range:
Polarisation:
Number of elements:
Genesis
File name:
Page 24 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
Construction:
Stainless steel.
Mounting:
Antenna Cable
Vendor to supply suitable antenna cable complete with connectors. Cable will be
required to have galvanized steel wire braid and flame retardant outer sheath.
Cable run will be approximately 50m, Vendor to confirm that this cable length is
acceptable and will not have a detrimental effect on the radio performance.
If cable run is to long consider Power over Ethernet (PoE) as this enables radio
placement near antenna to improve wireless network performance.
Genesis
File name:
Page 25 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
7.1
General
Solenoid valves shall consume low power, be continuously powered and fail safe.
All WCP instrumentation and pushbuttons that interface with the RTU shall be cabled
directly to the RTU I/O terminals via a gland plate in the RTU enclosure.
Field cables (by others) carrying signals between the RTU and field devices shall
enter the WCP via a gland plate in the side of the panel, glands shall be through type
to provide environmental seal. Cables shall enter RTU enclosure via a gland plate,
glands shall be Ex type suitable for use in specified hazardous area.
Motor start, stop and emergency stop pushbuttons and motors will be cabled, by
supplier, directly to the motor starters. Motor starters will be by supplier and located
in the WHU.
All instruments shall be tagged with stainless steel labels bearing Purchasers tag
numbers (to be advised later).
All unit cabling shall be flame retardant in accordance with lEC 332 part 1 & 3
Standard ships wiring cable to BS6883 with braid wire armour shall be used for
routes external to the cabinet, with unarmoured cable within cabinet. Nylon sealing
washers shall be used on glands to maintain enclosure IP ratings where applicable.
Junction boxes etc. shall be earthed to skid by means of star washers. WHU shall be
fitted with M10 earth bosses on diagonally opposite corners of the skid.
There will be no power available for internal cabinet lighting. The design of the
cabinet shall make provision for ambient light to be available for maintenance
purposes (removable panel/window). If this is not possible, Supplier shall state this in
his bid so that Client can ensure maintenance crews visit the platform with necessary
portable lighting.
All DC motors shall be standard products in accordance with IEC. DC motors shall
be 24 VDC. Motor datasheets are to be submitted with bidders offer. The electrical
installation shall meet IEC requirements.
A single, 4 x 50mm2, cable (by others) shall supply the 24vdc power to the WHU for
the RTU.
Genesis
File name:
Page 26 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
A single, 4 x 120mm2, cable (by others) shall supply the 24vdc power to the WHU for
the pump.
The RTU on the Kamose platform shall be supplied from a dedicated power supply
with 96 hour battery backup (By others). This shall be fed from the general platform
electrical supply in normal operation.
7.2
Materials
Base frame, panel and wellhead control modules shall be 316 SS, as a minimum.
Tubing shall be metric AISI 316L stainless steel, as a minimum.
Tube fittings shall be Parker Hannifin metric double ferrule type, AISI 316 stainless
steel, as a minimum.
Cable tray/supports shall be 316L SS
System shall be supplied complete with sufficient hydraulic fluid for topsides system
first fill.
Genesis
File name:
Page 27 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
8 TESTING
8.1
General
8.2
The Factory Acceptance Test shall include the Combined System Test. This will
incorporate the WCP, RTU, radio link and field I/O. This test will be carried out at the
WCP Suppliers works. Field I/O shall be achieved using a test simulator.
The test shall be designed to demonstrate that the WCP & RTU will perform their
specified functions. The test shall demonstrate the performance and accuracy
required.
Vendor shall be responsible for providing a test simulator and all temporary
hardware to allow for full function testing.
Witness testing shall only be carried out after the Test Procedure has been
submitted and approved by the Purchaser.
Test procedure to be detailed and include all components to be used for the Test rig.
Genesis
File name:
Page 28 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
The software configuration and any hardware being supplied shall be fully tested.
The Supplier shall demonstrate the operation of all diagnostic and maintenance tests
provided with the system. Errors shall be simulated to demonstrate the capability of
the system to detect and report errors.
8.3
The Seller shall provide commissioning support during a full functional test.
Genesis
File name:
Page 29 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
9 PRESERVATION
After successful testing and approval received for shipping, Wellhead Control Panel
preservation should be, as a minimum, carried out as follows:
Drain down all hydraulic fluid from accumulators, reservoirs, filters etc.
Place silica gel sacks within all junction boxes and electrical enclosures to
prevent condensation forming.
Genesis
File name:
Page 30 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
10 DOCUMENTATION
The wellhead control and hydraulic power documentation shall be developed and be
user friendly with respect to design, installation, operational and maintenance
requirements.
The Purchaser shall initially develop a Suppliers Document Requirements List
(SDRL) and SDRL Instruction Specification that shall accompany the Enquiry
Material Requisition. The SDRL instructions shall define precise document
requirements, the means of document approval, the quantity of soft/hard copies
required from initial enquiry through to final issue, and the dates by which documents
should be transferred back and forth throughout documentation development. Prior
to commitment of Purchase Order the selected Supplier shall complete the SDRL
with additional documentation pertaining to the wellhead control and hydraulic power
that enhanced design, installation, operational and maintenance requirements
developed during the enquiry.
Genesis
File name:
Page 31 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
11 PACKAGING
The Supplier shall be responsible for ensuring that the Wellhead control panel is
packed securely, and in such a manner as to prevent damage and dirt ingress whilst
being transported, or stored, under the most severe environmental conditions likely
to be encountered throughout the entire route from source to construction yard.
The WHU shall be accompanied by a Packing List that shall include the following
information as a minimum:
Genesis
File name:
Page 32 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13
12 REFERENCES
J08617A-J-SP-13000
J08617A-J-BD-13093
J08617A-J-BD-13402
J08617A-J-BD-13451
J08617A-J-CF-13460
J08617A-J-PH-13465
J08617A-J-AE-13470
J08617A-P-RD-15000
Genesis
File name:
Page 33 of 33
Date:
J08617A-J-SP-13482 Rev D1 Kamose Wellhead Control Panel Specification
March 13