You are on page 1of 9

20000

AC-13 6000
14.1kW/15.2kW

AC-08
14.1kW/15.2kW

7000

AC-06
7000
AC-15
14.1kW/15.2kW
10.7kW/11.7kW

AC-14
10.7kW/11.7kW

AC-07
14.1kW/15.2kW

NOTE:
1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.
TRUNKING 250x100mm

TRUNKING 250x100mm

2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR


3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.
4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN PIPE.

9.5/19.1

9.5/19.1

SYMBOL AND LEGENDS:

9.5/19.1
uPVC 42

CEILING MOUNTED - VRV SYSTEM

uPVC 34

8000

uPVC 34

uPVC 34
AC-06
14.1kW/15.2kW

FLOOR STANDING TYPE - SPLIT TYPE


AC-07
14.1kW/15.2kW

AC-08
14.1kW/15.2kW

uPVC 42

AIR COOLED CONDENSING UNIT - SPLIT TYPE

AC-05
14.1kW/15.2kW
AIR COOLED CONDENSING UNIT - SPLIT TYPE

REFRIGERANT PIPE
PIPE DRAIN

uPVC 34
AC-09
10.7kW/11.7kW

AC-01
9.5/19.1

uPVC 42

8000

24000

NUMBERING
EQUIPMENT NAME

uPVC 34

9.5/19.1

uPVC 42

AC-04
14.1kW/15.2kW

CABINET
uPVC 34

AC-02
7.0kW/7.6kW
uPVC 42

9.5/19.1

TRUNKING 250x100mm
AC-04

AC-03
7.0kW/7.6kW

14.1kW/15.2kW

AC-05
14.1kW/15.2kW

9.5/15.9
uPVC 34
9.5/15.9/19.1

AC-16
uPVC 34

8000

9.5/15.9

uPVC 34

AC-17
10.7kW/11.7kW

9.5/15.9/19.1

9.5/19.1

10.7kW/11.7kW

AC-01
10.7kW/11.7kW

9.5/15.9/19.1

TRUNKING 250x100mm
AC-09
10.7kW/11.7kW

AC-11
AC-10/01
10.7kW/11.7kW 10.7kW/11.7kW
AC-02
7.0kW/7.6kW

AC-12
10.7kW/11.7kW
AC-03
7.0kW/7.6kW
2

HVAC EQUIPMENT LAY OUT

20000
6000

AC-08
14.1kW/15.2kW

7000

AC-13
14.1kW/15.2kW

AC-14
10.7kW/11.7kW

7000
AC-06
AC-15
14.1kW/15.2kW
10.7kW/11.7kW

AC-07
14.1kW/15.2kW

NOTE:
1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.
TRUNKING 250x100mm

2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR

TRUNKING 250x100mm

3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.


AC-13
10.7kW/11.7kW

AC-14
10.7kW/11.7kW

4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN PIPE.

AC-15
10.7kW/11.7kW

9.5/19.1

SYMBOL AND LEGENDS:


9.5/19.1

9.5/19.1

uPVC 34

8000

CEILING MOUNTED - SPLIT TYPE


uPVC 34

uPVC 34

uPVC 42
FLOOR STANDING TYPE - SPLIT TYPE

uPVC 42
9.5/19.1

AIR COOLED CONDENSING UNIT - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

uPVC 34
AC-16
10.7kW/11.7kW
9.5/19.1

REFRIGERANT PIPE
PIPE DRAIN

9.5/19.1

AC-01
9.5/19.1

uPVC 42

24000

8000

NUMBERING
EQUIPMENT NAME

uPVC 42

AC-12
10.7kW/11.7kW

AC-17
10.7kW/11.7kW

uPVC 34

9.5/19.1

9.5/19.1

uPVC 42

TRUNKING 250x100mm
AC-04
14.1kW/15.2kW
uPVC 42

uPVC 42

uPVC 34

9.5/19.1

AC-05
14.1kW/15.2kW

AC-16

AC-11
10.7kW/11.7kW

AC-10
10.7kW/11.7kW

9.5/19.1

10.7kW/11.7kW

8000

9.5/19.1

uPVC 34

9.5/19.1

AC-17
10.7kW/11.7kW

9.5/19.1
AC-09
10.7kW/11.7kW

AC-10/01
10.7kW/11.7kW

TRUNKING 250x100mm
AC-11
10.7kW/11.7kW
AC-02
7.0kW/7.6kW

AC-12
10.7kW/11.7kW
AC-03
7.0kW/7.6kW
2

HVAC EQUIPMENT LAY OUT

NOTE:
1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.
2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR
3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.
4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN

SYMBOL AND LEGENDS:

CEILING MOUNTED - VRV SYSTEM

FLOOR STANDING TYPE - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

REFRIGERANT PIPE
PIPE DRAIN

AC-01
NUMBERING
TRUNKING 250X100

TRUNKING 250X100
EQUIPMENT NAME

AC-15
AC-14
AC-06
AC-07
10.7kW/11.7kW 10.7kW/11.7kW 14.1kW/15.2kW 14.1kW/15.2kW
EL: +0.000
EL: +0.000
EL: +0.000
EL: +0.000

AC-13
10.7kW/11.7kW
EL: +0.000

AC-08
14.1kW/15.2kW
EL: +0.000

NOTE:
1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.
2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR
3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.
4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN PIPE.

SYMBOL AND LEGENDS:

CEILING MOUNTED - VRV SYSTEM

FLOOR STANDING TYPE - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

REFRIGERANT PIPE
PIPE DRAIN

AC-01

TRUNKING 250X100

NUMBERING
EQUIPMENT NAME

AC-04
AC-05
AC-16
AC-17
14.1kW/15.2kW 14.1kW/15.2kW 10.7kW/11.7kW 10.7kW/11.7kW
EL: +0.000
EL: +0.000
EL: +0.000
EL: +0.000

NOTE:
1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.
2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR
3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.
4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN

SYMBOL AND LEGENDS:

CEILING MOUNTED - VRV SYSTEM

FLOOR STANDING TYPE - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

REFRIGERANT PIPE
PIPE DRAIN

AC-01
NUMBERING
EQUIPMENT NAME
TRUNKING 250X100

AC-10~12
10.7kW/11.7kW
EL: +1.200

AC-09
AC-01
AC-02
AC-03
10.7kW/11.7kW 10.7kW/11.7kW 7.0kW/7.6kW 7.0kW/7.6kW
EL: +0.000
EL: +0.000
EL: +0.000
EL: +0.000

20000
6000

7000

7000

NOTE:
1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.
2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR
3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.
SAG-12
150x150

SAG-13
150x150

4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN PIPE.

SYMBOL AND LEGENDS:

8000

100x100

150x150

CEILING MOUNTED - VRV SYSTEM

FLOOR STANDING TYPE - SPLIT TYPE

VCD-04
200x200
200x200
100x100

100x100

100x100

150x150

SAG-14
150x150

SAG-10
150x150

SAG-11
150x150

AIR COOLED CONDENSING UNIT - SPLIT TYPE

200x200

AIR COOLED CONDENSING UNIT - SPLIT TYPE

SAG-08
150x150

REFRIGERANT PIPE
PIPE DRAIN

100x100

AC-01
SAG-07
150x150
8000

150x100

100x100

250x200

SAG-09
150x150

100x100

SAG-06
150x150

CABINET
100x100
SAG-02
150x150
SAG-03
150x150
100x100

100x100

VCD-03
250x200

VCD-02
150x100

250x200

EAG-04
200x200

200x200

150x150
200x200

150x150

EAG-03
200x200
AL-02
450x400

300x200

VCD-05
100x100
150x150

200x200

200x200

SF-01
Q=406L/s, 150Pa
AF-01

150x150

150x150

EF-01
Q=222L/s, 50Pa

150x150

SAG-05
150x150

EAG-06
150x150
EF-02
Q=210L/s

HVAC DUCTING LAY OUT

600x550
AL-01

EAG-05
150x150

EAG-02
200x200

8000

200x200

300x250

SAG-01
150x150

100x100

VCD-01
200x200

200x200
100x100

SAG-04
150x150

100x100

150x150

EAG-01
200x200

24000

NUMBERING
EQUIPMENT NAME

20000
6000

7000

7000

NOTE:
SAG-26
150x150

SAG-24
150x150

1. ALL DIMENSION ARE MILIMETER (MM) UNLESS OTHERWISE NOTED.

SAG-23
150x150

SAG-24
150x150

2. ALL EQUIPMENT SIZE SHALL BE RECONFIRMED BY VENDOR


3. ALL OPENING ELEVATION IS BASE ON THE BOTTOM OF OPENING.
4. CONDENSER PIPE OF AIR CONDITIONING SHALL BE CONNECTED TO NEAREST DRAIN PIPE.

100x100

100x100

100x100

100x100

SYMBOL AND LEGENDS:

CEILING MOUNTED - VRV SYSTEM

100x100

150x150

150x150

8000

VCD-08
150x150
100x100

150x200

FLOOR STANDING TYPE - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

AIR COOLED CONDENSING UNIT - SPLIT TYPE

REFRIGERANT PIPE
SAG-22
150x150

SAG-21
150x150

SAG-19
150x150

SAG-20
150x150

PIPE DRAIN

AC-01

100x100

8000

100x100

200x200

150x150

100x100

SAG-18
150x150

100x100

100x100

SAG-17
150x150

VCD-06
100x100

VCD-07
200x200

VCD-05
200x200

200x200

200x200

250x200

150x150

250x250

AF-02

8000

150x150

150x150

150x150
SF-02
Q=348L/s, 150Pa

EAG-08
150x150

EAG-10
150x150

150x150

100x100

4341

100x100

250x250

EAG-12
200x200

AL-04
450x400

300x200
EF-03
Q=200L/S, 50 Pa

150x150

100x100

EAG-11
200x200
SAG-16
150x150

SAG-15
150x150

EAG-09
150x150

AL-03
600x500

HVAC DUCTING LAY OUT

EAG-07
150x150

24000

NUMBERING
100x100

EQUIPMENT NAME

PIPE DRAIN INSULATED THICKNESS


(MM)
(MM)

CONCRETE

D=<42

DENSITY HANGER
(MM)

10

SIZE
ROD THREAD
M8

1200

ExPANSION BOLT

MAxIMUM DISTANCE BETWEEN SUPPORT

ROD THREAD M8

50x50

ExPANSION BOLT

NUT & WASHER


DUCT
NUT & WASHER
STEEL ANGLE

HANGER ROD

75x50
CONTROL WIRE/ POWER WIRE FOR INDOOR UNIT

LARGER SIZE

ARMOURING TAPE

WITH INSULATION

DUCT HANGERS MINIMUM SIZE


GREATER SIDE
DUCT DIMENSION

DENSITY HANGER

COPPER DIAMETER
(MM)

UP TO 305
306 TO 762

HANGER RING

763 TO 1372
1373 TO 2134
REFRIGERANT PIPE FOR OFFICE BUILDING INSTALLATION DETAIL

OVER 2135

(UNIT : MM)
SUPPORT INTERVAL
3000
2400
1500
ANGLE ROD
ANGLE ROD
ANGLE ROD
25 x 25 x 3t
8 25 x 25 x 3t 8
25 x 25 x 3t 8
25 x 25 x 3t
8 25 x 25 x 3t 8
25 x 25 x 3t 8
25 x 25 x 3t
8 25 x 25 x 3t 8
25 x 25 x 3t 8

1200
ANGLE
25 x 25 x 3t
25 x 25 x 3t
25 x 25 x 3t

40 x 40 x 3t

10

25 x 25 x 3t

10

25 x 25 x 3t

10

25 x 25 x 3t

8
10

40 x 40 x 3t

10

40 x 40 x 3t

10

25 x 25 x 3t

10

25 x 25 x 3t

10

ROD
8
8

REMARKS

ExPANSION BOLT

1. REFERENCE : SMACNA STANDARD 2ND EDITION-1995, FIG.4-4, TABLE 4-1M


DUCT SUPPORT TYPICAL

REMARKS

CONCRETE

1. REFERENCE : ASTM B280 SEAMLESS COPPER TUBE FOR AIR CONDITIONING AND REFRIGERATION FILED SERVICE
2. REFERENCE : ASHARE 2010 TABLE 13-SUGGESTED PIPE SUPPORT SPACING FOR STRAIGHT HORIZONTAL RUNS
ROD THREAD M8
DRAIN PIPE uPVC

FLExIBLE DUCT

T
IN
JO
SE F)
R
R
E
SV D O
AN C ,
TR (A ,

LO

NG
(V ITU
OR DI
A A NA L
)
SE

DRAIN PIPE INSTALLATION DETAIL


DRAIN PIPE INSTALLATION SLOPE 1%
DRAIN PIPE UNDER THE CEILING HAVE INSULATION LAYER
DRAIN PIPE OUTSIDE BUILDING DON'T HAVE INSULATION LAYER
CEILING

CONCRETE FLOOR
ExPANSION BOLT
HANGER ROD M6

AM

DRAIN PIPE
SLOPE: MIN 1/100

ExHAUST AIR GRILL

VENDOR TO ADVICE

FALSE CEILING
INSTALLATON FOR ExHAUST GRILL

L-1 PITTSBURGH LOCK

REINFORCEMENT ANGLE SIZE


NO REINFORCEMENT
REQUIRED

A, C, D or F

>=300

PIPE HANGER FOR REFRIDGERANT PIPE


OUTSIDE THE BUILDING

<=500

TRANSVERSE JOINT TYPE

0.55mm

200

GREATER SIDE DUCT DIMENSION DUCT THICKNESS


UP TO 305

1m ~1.5m

>=300

INSULATION

INSTALLATION CASSETLE TYPE INDOOR UNIT DETAIL


INTERMEDIATE
REINFORCEMENT

150
150

0MM

0MM

MA
x.

A
0M
90

0M
90

Ax

SEE DETAIL

T-1 DRIVE SLIP


T-3 REINFORCED
(A)
L-1 PITTSBURGH LOCK

MA
x.

MAx. SAG 42MM


PER METER OF
SUPPORT SPACING

1
3

JO

S1
NT

.
Ax
0M
80

T-5 PLAIN"S"SLIP

SEE DETAIL "B"

RUBBER
SEE DETAIL "A"

BOLT M10
NO REINFORCEMENT
ANGLE ATTACH
UNDER 305

25BAND CLAMP
WITH WIRE IS
OPTIONAL.
REMARKS
1. REFERENCE : SMACNA STANDARD 2ND EDITION-1995, FIG.3-9
2. DUCT SHOULD ExTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING.

WASHER

MAx.

NO REINFORCEMENT
ANGLE ATTACH
UNDER 305

25MM MIN.

NUT M10

(C)
TRANSVERSE JOINT

T-6 HEMMED"S"SLIP
T-6a REINFORCED
(D)
DETAIL

ANGLE STEEL SUPPORT

DETAIL "A"

1
3

REMARKS
1. REFERENCE : SMACNA STANDARD 2ND EDITION-1995, FIG.1-10
2. TRANSVERSE JOINT TYPE T-24, T-25 AND SLIP-ON FLANGE MUST BE ATTACHED
INTERNAL TIE LOAD INTO EACH DUCT SECTION ON JOINT (REFER TO FIG. 1-2, 1-3
AND TABLE 1-14M IN SMACNA STANDARD 2ND EDITION-1995)

T-8 DOUBLE"S"SLIP
(T-8a REINFORCED)

INSTALLATION OUTDOOR UNIT DETAIL

FLEXIBLE DUCT SUPPORTS

CAULKING COMPOUND (SILICON)

ExPANTION ANCHOR

DUCT SLEEVE
AIR DUCT
INSULATION
HANG BOLT
VIBRATION
ISOLATION SPRING
CAULKING COMPOUND (SILICON)
WALL

PIPE SLEEVE

GLASS FIBRE

INSULATION

PIPE
WALL

AIR DUCT THROUGH WALL


CANVAS CONNECT

ANGLE DUCT IN-LINE FAN

GLASS FIBRE

PIPE THROUGH WALL

DUCT IN-LINE FAN INSTALLATION

DUCT