NOTES:1. ALL DIMENSIONS & COORDINETS ARE IN METERS.

2. HIGH FLOOD LEVEL(HFL) = 237.37 M ABOVE MSL


3. THIS DRAWING SHALL BE REFERED ONLY FOR INSTRUMENT DUCT/TRENCH LAYOUT.
4. WHEREVER INST. & ELECTRICAL TRENCH IS RUNNING IN PARALLEL 1000mm DISTANCE
SHALL BE MAINTAINED BETWEEN ADJOINING FACES.
5. FOR CO-ORDINATES OF INST. TRENCH REFER RESPECTIVE GENERAL CIVIL/ PIPING
AREA DRAWINGS.
6. INST. CABLE DUCT AS SHOWN SHALL BE SUPPLIED, FABRICATED AND INSTALLED BY
INST. CONTRACTOR.
7. SUPPORTS AS REQUIRED FOR INST. CABLE DUCTS SHALL BE PROVIDED BY
STRUCTURAL DEPARTMENT, BASED ON LOAD OF CABLES AND DUCTS. SUPPORTS AT
REGULAR INTERVALS OR CONTINUOUS SUPPORTS SHALL BE PROVIDED AND SAGGING
OF INST.CABLE DUCT IS NOT PERMITTED. CONTINUOUS HORIZONTAL SUPPORTS SHALL
BE PROVIDED ALONG THE PIPE RACK FOR CABLE DUCTS SHOWN IN THE DRAWING
DETAIL GIVEN BELOW.
8. RUNNING/ CROSSING OF HOT PIPES/ STEAM LINES ABOVE OR BELOW INST. CABLE
DUCT IS NOT PERMITTED.
9. INSTRUMENT DUCT FABRICATION SHALL BE AS PER STD NO. 6907-7-52-0254 (31SHT)
10. ESTIMATED WEIGHT OF DUCTS INCLUDING CABLES GIVEN IN TABLE.
11. THE PARTITIONS IN THE CABLE DUCT FOR VARIOUS CABLES LIKE SIGNAL/ ALARM
CABLES AND POWER/ CONTROL CABLES SHALL BE PROVIDED IN SUCH A WAY THAT
THEY SHALL MATCH THE SIMILAR PARTITIONS PROVIDED IN THE INST.CABLE TRENCH.
THIS MEANS THAT WHEN THE DUCT JOINS THE TRENCH THE SIMILAR PARTITIONS OF
DUCT & TRENCH SHALL MATCH IN ORIENTATION.
12. BATTERY LIMIT FOR SUPPLY, FABRICATION AND ERECTION/ LAYING OF INSTRUMENT
CABLE DUCT/ TRENCH SHALL BE AS MARKED IN THIS DRAWING.
13. THICKNESS OF CONCRETE FOR TRENCHES AS WELL AS SUPPORT FOR REMOVABLE
COVER SHALL BE DECIDED BY STRUCTURAL DEPARTMENT BASED ON THE LOAD.
14.ALL REQUIRED SUPPORTS FOR INSTRUMENT TRAYS FROM INDIVIDUAL INST./JN.
BOXES/LOCAL PANEL TO INST. CABLE DUCT SHALL BE PROVIDED BY INST. CONTRACTOR
WITH THE APPROVAL OF SITE ENGINEER INCHARGE.

PARTITION WALL
150W (TYP)

RCC COVER

SIZE OF INST. RCC TRANCH (ICT)

TABLE FOR DUCT DETAIL CABLES ONLY

D1-101

1200

400

300

750

150

D1-102

1000

400

250

600

150

650Kg/Mt

D1-103

800

300

200

450

150

400Kg/Mt

D1-104

600

300

150

300

150

300Kg/Mt

D1-105

400

200

100

150

150

120Kg/Mt

(*-AT GRADE ELEVATION .


NECESSARY SUPPORTS BY
STRUCTURAL DEPT.)

ICT NO.
WELD

MC 100

WIDTH (mm) DEPTH (mm) P1(mm) P2(mm)

ICT-1

400

600

150

100

ICT-2

600

800

300

150

MS INSERT P/L
100 mm Sq. 6mm Thk.
AT EVERY 1.5 METER INTERVAL

TYP. SECTION OF
INST. RCC CABLE TRENCH
(ICT)

TYP.CROSSING DETAIL
OF INST. AND EXISTING TRENCH
DETAIL -Y

Hkkjr Lkjdkj dk mIkde


z

(A Govt. of India Undertaking)

Page 3425 of 3574

DUCT
DETAIL NO.

MAX.WEIGHT
OF DUCT
INCLUDING
CABLES
800Kg/Mt

NEW DELHI

Page 3426 of 3574

The drawing, design and details given on this format are the property of ENGINEERS INDIA LIMITED. They are merely loaned on the borrower's express agreement that they
will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.

REV.
DATE
REVISION
BY
CHECKED
APPD.

A
16.06.2014
ISSUED FOR BIDS
Ravinder
NA
RK

ENGINEERS INDIA LIMITED

APPD.

DRAWING NO.

REV.

A535-068-16-51-SK-1001
000

1-1641-0504 REV.0 A4-210x297

Page 3427 of 3574

CONTROL ROOM LAYOUT - SRR#6

A535-000-16-51-SK-1005
DWG.NO.:
A535-068-16-51-SK-1005
000

Page 3428 of 3574

SYSTEM CONFIGURATION FOR EXISTING ESD SYSTEM IN SRR#6


DWG NO. A535-000-16-51-SK-1008
A535-068-16-51-SK-1008 SHEET 1

Page 3429 of 3574

SYSTEM CONFIGURATION FOR EXISTING FGS SYSTEM IN SRR#6


DWG NO. A535-068-16-51-SK-1008 SHEET 2

Page 3430 of 3574

SYSTEM CONFIGURATION FOR EXISTING DCS SYSTEM IN SRR#6


DWG NO. A535-068-16-51-SK-1008 SHEET 3

03.07.14

A535-000-16-51-SK-1002

Page 3431 of 3574

03.07.14

ISSUED WITH TENDER

A535-000-16-51-SK-1003
Page 3432 of 3574

DISTRIBUTED CONTROL SYSTEM


C4 Mis storage facilities

A535-000-00-IOF-01
Page 1 of 4

TABLE - I: I/O SUMMARY (DCS)


CLOSED LOOPS
OUTPUT

INPUT
Unit

OPEN LOOPS

4-20mA

4-20mA

4-20mA

4-20mA

WB

WOB

WB

WOB

P&F

L&T

P&F

Format No. EIL-1641-1924 Rev.1


Page 3433 of 3574

L&T

P&F

L&T

P&F

L&T

Control
Blocks
To
Consider
ed

INPUT
Calcul
ation
Blocks

4-20mA
WB

WO
B

RTD/
TC
WB

OUTPUT
Contacts

Switche
s (WB)

Switches
(WOB)

Proximity
Switches
(WB)

MCC
(WOB
)

420mA
(WB)

Copyright EIL All rights reserved

420mA
(WOB
)

Cont
act
(WO
B)

DISTRIBUTED CONTROL SYSTEM


C4 Mis storage facilities

A535-000-00-IOF-01
Page 2 of 4

TABLE - II: I/O SUMMARY (ESD - PLC)


INPUT

Unit

4-20mA
(NOTE-4)

WB

CONTACTS
PROXI
MITY
SWITCHES
SWITC
HES
WOB
WB

OUTPUT
CONTACTS

MCC

SOV

MCC

OTHER

WOB

WB

WOB

WOB

RELAYS
(NOTE-1)

PBs, HS
AND
SELECT.
SW
(NOTE-2)

EMER.
SW
(NOTE -2)

STATUS
LAMP
(NOTE -3)

ANN. WIN
(NOTE -3)

TIMERS

NOTES:
Note-1: Relays required for multiplication of contacts. Interposing relays wherever required shall be provided as per I/O count for MCC points.
Note-2: Pushbutton/ selector switches/ emergency switches are taken in the input count. This column is for counting hardware in Hardwired console.
Note-3: This column is for counting hardware in Hardwired Console. Outputs are included in output count
Format No. EIL-1641-1924 Rev.1
Page 3434 of 3574

Copyright EIL All rights reserved

DISTRIBUTED CONTROL SYSTEM


C4 Mis storage facilities

A535-000-00-IOF-01
Page 3 of 4

TABLE - III: I/O SUMMARY (PLC-GAS DETECTION SYSTEM)


ANALOG INPUT
UNIT

Format No. EIL-1641-1924 Rev.1


Page 3435 of 3574

4-20mA
(2-wire, WB)

4-20mA
(3-wire, WOB)

DIGITAL INPUT
WB

WOB

DIGITAL OUTPUT
WOB

Copyright EIL All rights reserved

DISTRIBUTED CONTROL SYSTEM


C4 Mis storage facilities

A535-000-00-IOF-01
Page 4 of 4

TABLE-I V : SERIAL LINK TO DCS

Sr. No
A

From System

Location

Type of Serial Link

No. of Serial links

Single/ Dual

Foreign Device Interfaces through DCS Serial Interface Card

1.
2.
3.
4.

Format No. EIL-1641-1924 Rev.1


Page 3436 of 3574

Copyright EIL All rights reserved

000

Page 3437 of 3574