You are on page 1of 8

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

BASEMENT-1
1

FCU-B-01

LV ROOM

2056

75.3

63.0

57.7

56.3

40.50

38.90

8.10

50

0.2

0.45

230-1-50

42DC18

44.23

38.58

1800

8.85

70

70

75.3

63.0

55.7

54.7

1321.0

737.0

419.1

FCU-B-02

MDF-CCU ROOM

237

75.3

63.1

58.1

56.6

4.50

4.40

0.90

50

0.2

0.05

230-1-50

42CET03

7.76

5.49

220

1.55

25

25

75.3

63.1

52.6

50.7

770.0

557.0

241.4

FCU-B-03

CCMS-BMS ROOM

2300

75.2

63.1

58.2

56.8

43.40

42.10

8.68

50

0.2

0.50

230-1-50

40LM090

54.54

45.31

2063

10.91

62

62

75.2

63.1

55.1

54.1

1212.0

680.0

480.0

FCU-B-04

ENGG. WORKSHOP

1616

75.1

63.8

57.7

56.4

35.70

30.40

7.15

50

0.2

0.35

230-1-50

42DC16

40.05

32.98

1607

8.01

58

58

75.1

63.8

56.4

55.5

1194.0

737.0

419.1

FCU-B-05

ENGG. OFFICE

446

75.1

63.6

57.4

56.0

10.00

8.50

2.00

50

0.2

0.18

230-1-50

42CET08

16.09

11.24

483

3.22

51

51

75.1

63.6

53.9

52.1

1410.0

557.0

241.4

FCU-B-06

CHEMICAL STORE

100

75.2

64.4

58.6

57.4

2.10

1.80

0.42

50

0.2

0.02

230-1-50

42CET04

10.12

6.08

255

2.02

43

43

75.2

64.4

53.4

50.6

890.0

557.0

241.4

FCU-B-07

LOBBY

1060

75.2

63.2

58.0

56.6

20.70

19.60

4.14

50

0.2

0.23

230-1-50

42DC12

24.62

21.65

1045

4.92

51

51

75.2

63.2

56.3

55.3

997.0

762.4

416.3

FCU-B-08

SECURITY CONTROL ROOM

1002

75.3

63.2

57.9

56.5

20.00

18.80

4.00

50

0.2

0.22

230-1-50

42DC10

21.55

19.41

958

4.31

32

32

75.3

63.2

56.8

55.7

813.0

737.0

419.1

FCU-B-09

SECURITY MANAGER

485

75.3

63.4

58.1

56.7

9.60

9.00

1.92

50

0.2

0.11

230-1-50

42CET06

11.84

9.15

442

2.37

28

28

75.3

63.4

56.4

54.3

1170.0

557.0

241.4

10

FCU-B-10

SECURITY EQUIP. CCU ROOM

163

75.1

63.0

57.8

56.3

3.20

3.00

0.64

50

0.2

0.04

230-1-50

42CET03

7.70

5.44

220

1.54

25

25

75.1

63.0

52.6

50.7

770.0

557.0

241.4

11

FCU-B-11

PUMP ROOM

1677

75.2

64.0

58.1

37.3

31.00

31.00

6.20

50

0.2

0.36

230-1-50

42DC16

41.79

34.19

1687

8.36

25

25

75.2

64.0

56.7

55.8

1194.0

737.0

419.1

12

FCU-B-12

IRRIGATION PLANT ROOM

568

75.1

64.0

58.1

37.3

10.40

10.40

2.08

50

0.2

0.12

230-1-50

42CET08

17.99

12.67

570

3.60

25

25

75.1

64.0

54.8

53.3

1410.0

557.0

241.4

13

FCU-B-13

GREASE TRAP ROOM

1179

75.2

64.0

58.3

37.4

21.50

21.50

4.30

50

0.2

0.26

230-1-50

42DC12

27.39

22.86

1146

5.48

25

25

75.2

64.0

57.0

56.1

997.0

762.4

416.3

14

FCU-B-14

STORE ROOM-B30

929

75.2

63.3

57.8

56.4

18.90

17.40

3.78

50

0.2

0.20

230-1-50

42DC10

21.85

19.45

970

4.37

25

25

75.2

63.3

56.9

55.8

813.0

737.0

419.1

15

FCU-B-C1

SERVICE LIFT LOBBY

1263

75.2

62.8

57.6

56.1

24.60

24.00

4.92

50

0.2

0.27

230-1-50

42DC14

29.22

25.81

1193

5.84

85

85

75.2

62.8

55.5

54.5

1067.0

737.0

419.1

16

FCU-B-C2

GUEST LIFT LOBBY

294

75.2

63.2

58.3

56.9

5.50

5.40

1.10

50

0.2

0.06

230-1-50

42CET04

8.24

5.45

219

1.65

58

58

75.2

63.2

52.4

49.8

890.0

557.0

241.4

63.4

54.6

53.0

1410.0

557.0

241.4

GROUND FLOOR
1

FCU-G-01

DU MTR

1540

74.9

62.5

57.3

55.8

29.90

29.30

5.98

50

0.2

0.33

230-1-50

FCU-G-02

FCC ROOM

625

75.3

63.4

57.8

56.4

13.00

11.80

2.60

50

0.2

0.14

230-1-50

FCU-G-03

ETISALAT ROOM

2454

75.0

62.6

57.4

55.9

FCU-G-04

FCU-G-05

SOILED LINEN ROOM

118

75.3

64.6

58.1

56.8

SWITCH ROOM

900

75.4

63.4

58.3

56.8

FCU-G-06

ELECTRICAL ROOM

315

75.0

62.9

57.7

56.2

FCU-G-07

RECEIVING-GEN CASHIER

955

75.1

63.4

57.8

FCU-G-08

KITCHEN AREA

1639

75.2

63.3

FCU-G-09

GSM ROOM

808

74.9

10

FCU-G-10

SECURITY

1100

11

FCU-G-11

DISH-POT WASH

12

FCU-G-12

13

47.50

UNIT WITH DUAL FLUIID


COOLING OPTION
(CHIILED WATER AND
REFRIGERENT)

REFER DUAL COIL SUBMISSION


42CET08

17.36

12.93

570

3.47

UNIT WITH DUAL FLUIID


COOLING OPTION
(CHIILED WATER AND
REFRIGERENT)

25

25

75.3

46.60

9.50

50

0.2

0.53

230-1-50

REFER DUAL COIL SUBMISSION

2.70

2.20

0.54

50

0.2

0.03

230-1-50

42CET04

9.87

5.77

238

1.97

50

50

75.3

64.6

53.1

50.1

890.0

557.0

241.4

17.40

16.70

3.48

50

0.2

0.20

230-1-50

42DC10

21.15

18.77

915

4.23

63

63

75.4

63.4

56.7

55.7

813.0

737.0

419.1

6.10

5.90

1.22

50

0.2

0.07

230-1-50

42CET05

8.99

6.57

271

1.80

60

60

75.0

62.9

52.9

51.3

970.0

557.0

241.4

56.4

19.70

17.80

3.94

50

0.2

0.21

230-1-50

42DC10

21.24

18.56

921

4.25

60

60

75.1

63.4

56.7

55.7

813.0

737.0

419.1

57.8

56.4

33.30

30.70

6.66

50

0.2

0.36

230-1-50

42DC16

37.92

32.55

1552

7.58

77

77

75.2

63.3

56.0

55.1

1194.0

737.0

419.1

64.0

57.1

36.7

15.40

15.40

3.08

50

0.2

0.18

230-1-50

42DC10

21.99

18.13

921

4.40

60

60

74.9

64.0

56.9

56.1

813.0

737.0

419.1

74.9

62.9

57.8

56.4

21.10

20.30

4.22

50

0.2

0.24

230-1-50

42DC12

24.31

21.52

1050

4.86

50

50

74.9

62.9

56.2

55.1

997.0

762.4

416.3

744

75.2

63.7

58.1

56.8

15.40

13.70

3.08

50

0.2

0.16

230-1-50

42DC10

21.46

18.40

911

4.29

65

65

75.2

63.7

56.8

55.9

813.0

737.0

419.1

GARBAGE ROOM

751

75.2

63.5

58.1

56.7

15.00

13.80

3.00

50

0.2

0.16

230-1-50

42DC10

21.44

18.70

926

4.29

57

57

75.2

63.5

56.8

55.8

813.0

737.0

419.1

FCU-G-13

CLEAN LINEN

989

75.1

63.3

57.8

56.4

20.00

18.50

4.00

50

0.2

0.21

230-1-50

42DC10

21.19

18.67

926

4.24

57

57

75.1

63.3

56.7

55.7

813.0

737.0

419.1

14

FCU-G-14

TOILET

436

75.2

63.6

58.2

56.8

8.80

8.00

1.76

50

0.2

0.09

230-1-50

42CET06

11.23

8.27

392

2.25

50

50

75.2

63.6

55.9

53.9

1170.0

557.0

241.4

15

FCU-G-15

FIRE ESCAPE

1057

75.2

63.2

58.1

56.7

20.20

19.50

4.04

50

0.2

0.23

230-1-50

42DC12

23.41

20.41

965

4.68

64

64

75.2

63.2

55.9

55.0

997.0

762.4

416.3

16

FCU-G-16

LOADING BAY

1611

75.1

63.4

57.9

56.5

32.90

29.90

6.58

50

0.2

0.35

230-1-50

42DC16

39.34

33.50

1626

7.87

50

50

75.1

63.4

56.3

55.3

1194.0

737.0

419.1

17

FCU-G-C1

SERVICE LIFT LOBBY

1543

75.1

63.1

57.7

56.3

31.00

29.00

6.20

50

0.2

0.34

230-1-50

42DC16

37.44

32.48

1552

7.49

77

77

75.1

63.1

56.0

55.0

1194.0

737.0

419.1

18

FCU-G-C2

GUEST LIFT LOBBY

185

75.3

64.7

58.2

57.0

4.30

3.40

0.86

50

0.2

0.04

230-1-50

42CET04

9.33

5.42

221

1.87

57

57

75.3

64.7

52.9

50.0

890.0

557.0

241.4

SERVICE MEZZANINE
1

FCU-M-01

S.POOL PLANT ROOM

728

75.1

63.2

57.8

56.4

14.70

13.60

2.94

50

0.2

0.16

230-1-50

42CET10

20.23

14.42

655

4.05

25

25

75.1

63.2

55.0

52.5

1530.0

557.0

241.4

FCU-M-C1

SERVICE LIFT LOBBY

848

75.2

63.2

57.5

56.1

17.80

16.20

3.56

50

0.2

0.18

230-1-50

42DC10

20.02

17.71

856

4.00

97

115

75.2

63.2

56.3

55.4

813.0

737.0

419.1

FCU-M-C2

GUEST LIFT LOBBY

201

75.3

64.5

58.1

56.9

4.60

3.70

0.92

50

0.2

0.04

230-1-50

42CET04

9.80

5.78

238

1.96

50

50

75.3

64.5

53.1

50.1

890.0

557.0

241.4

FIRST FLOOR
1

FCU-T1-01

IT OFFICE

1521

75.1

63.5

57.4

56.1

33.30

28.90

6.66

50

0.2

0.33

230-1-50

42DC16

39.38

33.23

1611

7.88

56

56

75.1

63.5

56.3

55.3

1194.0

737.0

419.1

2
3
4

FCU-T1-02
FCU-T1-03
FCU-T1-04

HOUSE KEEPING STORE


NURSE ROOM
MALE PRAYER ROOM

1010
151
165

75.2
75.0
75.2

64.2
62.9
64.5

58.2
57.8
57.9

56.9
56.7
56.6

22.10
4.10
3.90

18.60
2.90
3.10

4.43
0.82
0.78

50
50
50

0.2
0.2
0.2

0.22
0.03
0.04

230-1-50
230-1-50
230-1-50

1
1
1

42DC12
42CET04
42CET04

26.15
8.68
9.80

21.28
5.80
5.75

1050
238
238

5.23
1.74
1.96

50
50
50

50
50
50

75.2
75.0
75.2

64.2
62.9
64.5

56.7
52.7
53.1

56.0
49.9
50.1

997.0
890.0
890.0

762.4
557.0
557.0

416.3
241.4
241.4

FCU-T1-05

FEMALE PRAYER ROOM

160

75.3

64.8

58.4

57.2

3.70

2.90

0.74

50

0.2

0.74

230-1-50

42CET04

10.02

5.74

238

2.00

50

50

75.3

64.8

53.2

50.2

890.0

557.0

241.4

FCU-T1-06

HR MANAGER

331

75.3

64.2

57.8

56.5

7.60

6.20

1.52

50

0.2

0.07

230-1-50

42CET04

9.59

5.81

238

1.92

50

50

75.3

64.2

53.0

50.1

890.0

557.0

241.4

FCU-T1-07

GUEST LAUNDROMAT

136

75.3

65.0

58.4

57.2

3.20

2.50

0.64

50

0.2

0.03

230-1-50

42CET04

10.16

5.71

238

2.03

50

50

75.3

65.0

53.3

50.2

890.0

557.0

241.4

FCU-T1-08

OS & E STORE

491

75.3

64.5

58.6

57.3

10.70

8.90

2.14

50

0.2

0.11

230-1-50

42CET08

17.02

11.21

487

3.40

50

50

75.3

64.5

54.3

52.6

1410.0

557.0

241.4

FCU-T1-09

UNIFORM ISSUE

366

75.1

63.3

57.8

56.4

7.40

6.80

1.48

50

0.2

0.08

230-1-50

42CET05

9.81

6.95

291

1.96

50

50

75.1

63.3

53.2

51.5

970.0

557.0

241.4

10

FCU-T1-10

MEETING ROOM FURN STORE

957

75.1

63.3

57.7

56.3

19.70

18.00

3.94

50

0.2

0.21

230-1-50

42DC10

21.06

18.54

917

4.21

62

62

75.1

63.3

56.6

55.6

813.0

737.0

419.1

11

FCU-T1-11

STAFF CAF

1510

75.2

65.1

57.8

56.7

38.50

28.40

7.70

50

0.2

0.33

230-1-50

42DC16

43.30

32.36

1623

8.66

51

51

75.2

65.1

57.0

56.3

1194.0

737.0

419.1

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

12

FCU-T1-12

MALE LOCKERS

471

75.2

63.7

58.6

57.2

9.20

8.50

1.84

50

0.2

0.10

230-1-50

42CET06

11.30

8.25

392

2.26

50

50

75.2

63.7

56.0

53.9

1170.0

557.0

241.4

13

FCU-T1-13

FEMALE LOCKERS

412

75.1

63.7

58.4

57.0

8.20

7.40

1.64

50

0.2

0.09

230-1-50

42CET06

11.30

8.21

392

2.26

50

50

75.1

63.7

56.0

53.9

1170.0

557.0

241.4

14

FCU-T1-14

CHEMICAL ROOM

181

75.1

63.6

57.8

56.4

3.90

3.40

0.78

50

0.2

0.04

230-1-50

42CET03

8.07

5.42

220

1.61

25

25

75.1

63.6

52.6

50.8

770.0

557.0

241.4

15

FCU-T1-15

TOILET POOL AREA

717

75.1

63.2

58.0

56.6

13.90

13.20

2.78

50

0.2

0.16

230-1-50

42DC08

16.65

13.59

598

3.33

50

50

75.1

63.2

54.4

53.7

711.0

737.0

419.1

16

FCU-T1-16

SERVICE CORRIDOR

721

75.2

63.5

57.9

56.5

15.00

13.50

3.00

50

0.2

0.16

230-1-50

42DC10

21.15

18.41

907

4.23

67

67

75.2

63.5

56.7

55.7

813.0

737.0

419.1

17

FCU-T1-17

TOILET HEALTH CLUB

1329

75.4

63.8

59.0

57.6

24.60

23.50

4.92

50

0.2

0.29

230-1-50

42DC14

32.05

26.68

1260

6.41

58

58

75.4

63.8

56.1

55.3

1067.0

737.0

419.1

18

FCU-T1-18

CORRIDOR HEALTH CLUB

389

75.3

64.0

58.6

57.3

7.90

7.00

1.58

50

0.2

0.08

230-1-50

42CET06

11.41

8.16

386

2.28

52

52

75.3

64.0

56.0

54.0

1170.0

557.0

241.4

19

FCU-T1-19

CORRIDOR CREW LOUNGE

445

75.1

63.5

57.8

56.4

9.30

8.30

1.86

50

0.2

0.10

230-1-50

42CET06

11.12

8.19

389

2.22

53

53

75.1

63.5

55.9

53.8

1170.0

557.0

241.4

20

FCU-T1-20

HEALTH CLUB

2188

75.0

65.3

57.6

56.5

58.30

41.20

11.66

50

0.2

0.48

230-1-50

40LM090

63.06

44.09

2097

12.61

52

52

75.0

65.0

55.8

55.1

1212.0

680.0

480.0

21

FCU-T1-21

MEETING ROOM-2

1312

75.1

63.8

57.7

56.3

28.90

24.70

5.78

50

0.2

0.29

230-1-50

42DC14

32.41

26.62

1282

6.48

50

50

75.1

63.8

56.1

55.4

1067.0

737.0

419.1

22

FCU-T1-22

MEETING ROOM-1

790

75.2

64.4

57.5

56.3

19.20

15.00

3.84

50

0.2

0.17

230-1-50

42DC10

22.70

18.42

934

4.54

50

50

75.2

64.4

57.2

56.4

813.0

737.0

419.1

23

FCU-T1-23

BOARD ROOM

1084

75.1

64.0

57.7

56.4

24.50

20.30

4.90

50

0.2

0.24

230-1-50

42DC12

25.86

21.27

1050

5.17

50

50

75.1

64.0

56.6

55.9

997.0

762.4

416.3

24

FCU-T1-24

BREAKOUT AREA

1456

75.1

64.5

57.7

56.5

35.20

27.40

7.04

50

0.2

0.32

230-1-50

42DC16

41.58

32.25

1594

8.32

64

64

75.1

64.5

56.6

55.9

1194.0

737.0

419.1

25

FCU-T1-25

STAIR-2

1351

75.2

63.1

57.8

56.3

26.80

25.40

5.36

50

0.2

0..29

230-1-50

42DC14

30.58

26.61

1253

6.12

61

61

75.2

63.1

55.8

54.9

1067.0

737.0

419.1

26

FCU-T1-26

CREW LOUNGE

544

75.4

65.1

57.9

56.7

13.80

10.30

2.76

50

0.2

0.12

230-1-50

42CET08

17.50

11.11

487

3.50

50

50

75.4

65.0

54.5

52.9

1410.0

557.0

241.4

27

FCU-T1-C1

SERVICE LIFT LOBBY

1248

75.2

63.1

57.5

56.1

25.70

23.80

5.14

50

0.2

0.27

230-1-50

42DC14

30.96

26.99

1277

6.19

52

52

75.2

63.1

55.9

54.9

1067.0

737.0

419.1

28

FCU-T1-C2

GUEST LIFT LOBBY

223

75.2

64.6

58.1

56.9

5.10

4.10

1.02

50

0.2

0.05

230-1-50

42CET04

9.87

5.74

238

1.97

50

50

75.2

64.6

53.1

50.1

890.0

557.0

241.4

2nd FLOOR
1

FCU-T2-01

RM-01

367

75.1

63.2

57.4

55.9

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

FCU-T2-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T2-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T2-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T2-05

RM-05

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T2-06

RM-06

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T2-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T2-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T2-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T2-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T2-11

RM-11

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

12

FCU-T2-12

RM-12

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

13

FCU-T2-13

RM-13

448

75.5

63.6

58.2

56.8

9.00

8.40

1.80

50

0.2

1.81

230-1-50

LOW STATIC UNIT

42CET05

11.00

7.97

339

2.20

25

25

75.5

63.6

54.0

52.4

970.0

557.0

241.4

14

FCU-T2-14

RM-14

393

75.5

63.7

58.2

56.8

8.10

7.30

1.62

50

0.2

1.61

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

15

FCU-T2-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T2-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T2-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T2-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T2-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T2-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T2-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T2-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T2-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T2-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T2-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T2-26

RM-26

386

75.1

63.2

57.4

56.0

8.10

7.40

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

27

FCU-T2-27

RM-27

386

75.1

63.2

57.4

56.0

8.10

7.40

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

28

FCU-T2-28

RM-28

392

75.2

63.4

57.7

56.3

8.20

7.40

1.64

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

29

FCU-T2-29

RM-29

371

75.2

63.3

57.6

56.2

7.80

7.10

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.87

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

30

FCU-T2-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T2-C1

SERVICE LIFT LOBBY

1161

75.2

64.0

57.4

36.9

22.30

22.30

4.46

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T2-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

3rd FLOOR-TA
1

FCU-T3-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T3-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T3-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T3-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T3-05

RM-05

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T3-06

RM-06

320

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

FCU-T3-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T3-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T3-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T3-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T3-11

RM-11

440

75.2

63.4

58.0

56.6

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

12

FCU-T3-12

RM-12

448

75.5

63.6

58.2

56.8

9.00

8.30

1.80

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

11.00

7.97

339

2.20

25

25

75.5

63.6

54.0

52.4

970.0

557.0

241.4

13

FCU-T3-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T3-14

RM-14

393

75.5

63.7

58.2

56.8

8.10

7.30

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

15

FCU-T3-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T3-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T3-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T3-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T3-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T3-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T3-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T3-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T3-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T3-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T3-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T3-26

RM-26

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

27

FCU-T3-27

RM-27

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

28

FCU-T3-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T3-29

RM-29

372

75.0

63.1

57.3

55.9

7.90

7.10

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.81

339

2.12

25

25

75.0

63.1

54.0

52.3

970.0

557.0

241.4

30

FCU-T3-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T3-C1

SERVICE LIFT LOBBY

1168

75.2

64.0

57.4

36.9

22.40

22.40

4.48

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T3-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

4th FLOOR-TA
1

FCU-T4-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T4-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T4-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T4-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T4-05

RM-05

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T4-06

RM-06

320

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T4-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T4-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T4-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T4-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T4-11

RM-11

440

75.2

63.4

58.0

56.6

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

12

FCU-T4-12

RM-12

448

75.5

63.6

58.2

56.8

9.00

8.30

1.80

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

11.00

7.97

339

2.20

25

25

75.5

63.6

54.0

52.4

970.0

557.0

241.4

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

13

FCU-T4-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T4-14

RM-14

393

75.5

63.7

58.2

56.8

8.10

7.30

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

15

FCU-T4-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T4-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T4-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T4-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T4-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T4-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T4-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T4-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T4-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T4-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T4-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T4-26

RM-26

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

27

FCU-T4-27

RM-27

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

28

FCU-T4-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T4-29

RM-29

372

75.0

63.1

57.3

55.9

7.90

7.10

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.81

339

2.12

25

25

75.0

63.1

54.0

52.3

970.0

557.0

241.4

30

FCU-T4-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T4-C1

SERVICE LIFT LOBBY

1168

75.2

64.0

57.4

36.9

22.40

22.40

4.48

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T4-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

5th FLOOR-TB
1

FCU-T5-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T5-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T5-03

RM-03

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T5-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T5-05

RM-05

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T5-06

RM-06

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T5-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T5-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T5-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T5-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T5-11

RM-11

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

12

FCU-T5-12

RM-12

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

13

FCU-T5-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T5-14

RM-14

394

75.2

63.4

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

15

FCU-T5-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T5-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T5-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T5-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T5-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T5-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T5-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T5-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T5-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T5-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T5-25

RM-25

391

75.2

63.4

57.7

56.3

8.20

7.40

1.64

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

26

FCU-T5-26

RM-26

385

75.2

63.4

57.7

56.3

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

27

FCU-T5-27

RM-27

385

75.2

63.4

57.7

56.3

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

28

FCU-T5-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T5-29

RM-29

371

75.2

63.3

57.6

56.2

7.80

7.10

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.87

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

30

FCU-T5-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T5-C1

SERVICE LIFT LOBBY

1164

75.2

64.0

57.3

36.8

22.50

22.50

4.50

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T5-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

6th FLOOR-TA
1

FCU-T6-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T6-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T6-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T6-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T6-05

RM-05

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T6-06

RM-06

320

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T6-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T6-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T6-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T6-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T6-11

RM-11

440

75.2

63.4

58.0

56.6

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

12

FCU-T6-12

RM-12

448

75.5

63.6

58.2

56.8

9.00

8.30

1.80

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

11.00

7.97

339

2.20

25

25

75.5

63.6

54.0

52.4

970.0

557.0

241.4

13

FCU-T6-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T6-14

RM-14

393

75.5

63.7

58.2

56.8

8.10

7.30

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

15

FCU-T6-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T6-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T6-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T6-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T6-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T6-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T6-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T6-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T6-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T6-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T6-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T6-26

RM-26

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

27

FCU-T6-27

RM-27

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

28

FCU-T6-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T6-29

RM-29

372

75.0

63.1

57.3

55.9

7.90

7.10

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.81

339

2.12

25

25

75.0

63.1

54.0

52.3

970.0

557.0

241.4

30

FCU-T6-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T6-C1

SERVICE LIFT LOBBY

1168

75.2

64.0

57.4

36.9

22.40

22.40

4.48

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T6-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

7th FLOOR-TC
1

FCU-T7-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T7-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T7-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T7-04

RM-04

302

75.2

63.4

57.5

56.1

6.50

5.80

1.30

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T7-05

RM-05

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T7-06

RM-06

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T7-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T7-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T7-09

RM-09

368

75.1

63.3

57.6

56.2

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

10

FCU-T7-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T7-11

RM-11

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

12

FCU-T7-12

RM-12

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

13

FCU-T7-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T7-14

RM-14

394

75.5

63.7

58.2

56.8

8.10

7.30

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

15

FCU-T7-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T7-16

RM-16

409

75.1

63.3

57.7

56.3

8.50

7.70

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

17

FCU-T7-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T7-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T7-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T7-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T7-21

RM-21

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

22

FCU-T7-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T7-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

24

FCU-T7-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T7-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T7-26

RM-26

385

75.2

63.4

57.7

56.3

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

27

FCU-T7-27

RM-27

385

75.2

63.4

57.7

56.3

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

28

FCU-T7-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T7-29

RM-29

371

75.0

63.1

57.3

55.9

7.80

7.10

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.81

339

2.12

25

25

75.0

63.1

54.0

52.3

970.0

557.0

241.4

30

FCU-T7-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T7-C1

SERVICE LIFT LOBBY

737

75.3

64.0

57.7

37.1

14.00

14.00

2.80

50

0.2

0.16

230-1-50

LOW STATIC UNIT

42DC10

21.77

18.31

907

4.35

67

67

75.3

64.0

56.9

56.1

813.0

737.0

419.1

32

FCU-T7-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

33

FCU-T7-C3

GSM ROOM

1348

75.5

64.0

57.8

37.1

25.80

25.80

5.16

72

0.29

0.10

230-1-50

LOW STATIC UNIT

42DC14

37.00

26.75

1263

6.50

57

57

75.5

64.0

56.2

55.5

1067.0

737.0

419.1

8th FLOOR-TA
1

FCU-T8-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T8-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T8-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T8-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T8-05

RM-05

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T8-06

RM-06

320

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T8-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T8-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T8-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T8-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T8-11

RM-11

440

75.2

63.4

58.0

56.6

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

12

FCU-T8-12

RM-12

448

75.5

63.6

58.2

56.8

9.00

8.30

1.80

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

11.00

7.97

339

2.20

25

25

75.5

63.6

54.0

52.4

970.0

557.0

241.4

13

FCU-T8-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T8-14

RM-14

393

75.5

63.7

58.2

56.8

8.10

7.30

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

15

FCU-T8-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T8-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T8-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T8-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T8-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T8-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T8-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T8-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T8-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T8-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T8-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T8-26

RM-26

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

27

FCU-T8-27

RM-27

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

28

FCU-T8-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T8-29

RM-29

372

75.0

63.1

57.3

55.9

7.90

7.10

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.81

339

2.12

25

25

75.0

63.1

54.0

52.3

970.0

557.0

241.4

30

FCU-T8-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T8-C1

SERVICE LIFT LOBBY

1168

75.2

64.0

57.4

36.9

22.40

22.40

4.48

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T8-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

9th FLOOR-TB
1

FCU-T9-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T9-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T9-03

RM-03

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T9-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T9-05

RM-05

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T9-06

RM-06

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T9-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T9-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T9-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T9-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T9-11

RM-11

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

12

FCU-T9-12

RM-12

440

75.2

63.3

57.9

56.5

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

13

FCU-T9-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY

REMARKS

V-PH-HZ
CFM

DBT F WBT F

DBT F WBT F

TMBH

SMBH

GPM

Pa

IN. WG

kW

MODEL

TMBH

SMBH

Air
Flow
CFM

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM

AIR ON COIL

AIR OFF COIL

DIMENSION DETAILS
(MM)

DBT
F

WBT
F

DBT
F

WBT
F

14

FCU-T9-14

RM-14

394

75.2

63.4

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

15

FCU-T9-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T9-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T9-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T9-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T9-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T9-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T9-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T9-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T9-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T9-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T9-25

RM-25

391

75.2

63.4

57.7

56.3

8.20

7.40

1.64

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

26

FCU-T9-26

RM-26

385

75.2

63.4

57.7

56.3

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

27

FCU-T9-27

RM-27

385

75.2

63.4

57.7

56.3

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

28

FCU-T9-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T9-29

RM-29

371

75.2

63.3

57.6

56.2

7.80

7.10

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.87

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

30

FCU-T9-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T9-C1

SERVICE LIFT LOBBY

1164

75.2

64.0

57.3

36.8

22.50

22.50

4.50

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

25.97

1239

6.42

67

67

75.2

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T9-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

10th FLOOR
1

FCU-T10-01

RM-01

371

75.1

63.3

57.6

56.2

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.84

339

2.15

25

25

75.1

63.3

54.0

52.3

970.0

557.0

241.4

FCU-T10-02

RM-02

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T10-03

RM-03

321

75.2

63.5

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.88

294

2.04

25

25

75.2

63.5

53.8

51.4

890.0

557.0

241.4

FCU-T10-04

RM-04

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T10-05

RM-05

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T10-06

RM-06

320

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T10-07

RM-07

322

75.2

63.4

57.6

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T10-08

RM-08

321

75.2

63.4

57.5

56.2

6.80

6.10

1.36

50

0.2

0.07

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

FCU-T10-09

RM-09

367

75.1

63.2

57.5

56.1

7.70

7.00

1.54

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

10

FCU-T10-10

RM-10

463

75.2

63.3

57.9

56.5

9.30

8.60

1.86

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.76

7.88

339

2.15

25

25

75.2

63.3

54.0

52.3

970.0

557.0

241.4

11

FCU-T10-11

RM-11

440

75.2

63.4

58.0

56.6

8.90

8.20

1.78

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.84

7.87

339

2.17

25

25

75.2

63.4

54.0

52.4

970.0

557.0

241.4

12

FCU-T10-12

RM-12

448

75.5

63.6

58.2

56.8

9.00

8.30

1.80

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

11.00

7.97

339

2.20

25

25

75.5

63.6

54.0

52.4

970.0

557.0

241.4

13

FCU-T10-13

RM-13

447

75.0

63.0

57.5

56.0

9.20

8.50

1.84

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET05

10.52

7.81

339

2.10

25

25

75.0

63.0

53.9

52.2

970.0

557.0

241.4

14

FCU-T10-14

RM-14

372

75.3

63.5

57.9

56.5

7.80

7.00

1.56

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.22

6.91

294

2.04

25

25

75.3

63.5

53.8

51.4

890.0

557.0

241.4

15

FCU-T10-15

RM-15

377

75.1

63.2

57.4

56.0

7.90

7.20

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

16

FCU-T10-16

RM-16

411

75.5

63.7

58.2

56.8

8.40

7.70

1.68

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.09

7.96

339

2.22

25

25

75.5

63.7

54.0

52.5

970.0

557.0

241.4

17

FCU-T10-17

RM-17

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

18

FCU-T10-18

RM-18

346

75.2

63.4

57.7

56.3

7.30

6.50

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

19

FCU-T10-19

RM-19

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

20

FCU-T10-20

RM-20

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

21

FCU-T10-21

RM-21

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

22

FCU-T10-22

RM-22

347

75.2

63.4

57.7

56.3

7.30

6.60

1.46

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.14

6.88

294

2.03

25

25

75.2

63.4

53.8

51.4

890.0

557.0

241.4

23

FCU-T10-23

RM-23

346

75.4

63.7

58.1

56.7

7.20

6.50

1.44

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET04

10.38

6.93

294

2.08

25

25

75.4

63.7

53.9

51.5

890.0

557.0

241.4

24

FCU-T10-24

RM-24

420

75.6

63.8

58.4

57.0

8.50

7.80

1.70

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

11.17

7.99

339

2.23

25

25

75.6

63.8

54.1

52.5

970.0

557.0

241.4

25

FCU-T10-25

RM-25

390

75.1

63.1

57.3

55.9

8.20

7.50

1.64

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.85

339

2.12

25

25

75.1

63.1

5.39

52.3

970.0

557.0

241.4

26

FCU-T10-26

RM-26

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

27

FCU-T10-27

RM-27

385

75.1

63.2

57.5

56.1

8.10

7.30

1.62

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

28

FCU-T10-28

RM-28

392

75.3

63.5

57.8

56.4

8.10

7.40

1.62

50

0.2

0.09

230-1-50

LOW STATIC UNIT

42CET05

10.92

7.90

339

2.18

25

25

75.3

63.5

54.0

52.4

970.0

557.0

241.4

29

FCU-T10-29

RM-29

372

75.0

63.1

57.3

55.9

7.90

7.10

1.58

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.60

7.81

339

2.12

25

25

75.0

63.1

54.0

52.3

970.0

557.0

241.4

30

FCU-T10-30

RM-30

356

75.1

63.2

57.3

55.9

7.60

6.80

1.52

50

0.2

0.08

230-1-50

LOW STATIC UNIT

42CET05

10.68

7.84

339

2.14

25

25

75.1

63.2

54.0

52.3

970.0

557.0

241.4

31

FCU-T10-C1

SERVICE LIFT LOBBY

1161

75.3

64.0

57.7

37.1

22.10

22.10

4.42

50

0.2

0.25

230-1-50

LOW STATIC UNIT

42DC14

32.09

26.10

1239

6.42

67

67

75.3

64.0

56.1

55.4

1067.0

737.0

419.1

32

FCU-T10-C2

GUEST LIFT LOBBY

459

75.3

64.0

59.0

37.8

8.00

8.00

1.60

50

0.2

0.10

230-1-50

LOW STATIC UNIT

42CET08

13.06

9.04

370

2.61

78

78

75.3

64.0

53.0

51.8

1410.0

557.0

241.4

SERVICE ROOF
1

FCU-SR-C1

SERVICE LIFT LOBBY

2240

75.0

62.9

57.9

56.5

42.40

41.30

8.48

50

0.2

0.49

230-1-50

40LM090

50.93

42.18

1889

10.19

115

115

75.0

62.9

54.6

53.7

1212.0

680.0

480.0

FCU-SR-C2

GUEST LIFT LOBBY

551

75.2

63.9

58.2

56.8

11.60

10.10

2.32

50

0.2

0.12

230-1-50

42CET08

16.45

11.30

487

3.29

50

50

75.2

63.9

54.0

52.3

1410.0

557.0

241.4

ROOF
7

PROJECT

: DUBAI INN - PORT SAEED

CLIENT

: M/S EMAAR

CONSULTANT

: M/S ARCH GROUP

CONTRACTOR

: M/S SHAPOORJI PALLONJI

MEP CONTRACTOR

: M/S NASCON ENGINEERING LTD.


SCHEDULE OF FAN COIL UNIT
SPECIFIED

PROPOSED

COOLING COIL
SUPPLY AIR
FLOW
SR NO.

UNIT REF.

AREA SERVED

AIR ON COIL

AIR OFF COIL

ELECTRICAL DATA

CAPACITY CAPACITY
TOTAL
SENSIBLE

CHW FLOW
RATE

EXTERNAL EXTERNAL
STATIC
STATIC
PRESSURE PRESSURE

POWER
INPUT

QTY
V-PH-HZ

CFM
1

FCU-R-C1

SERVICE LIFT LOBBY

2500

DBT F WBT F
75.1

62.9

DBT F WBT F
57.9

56.4

TMBH

SMBH

GPM

Pa

IN. WG

kW

47.40

46.50

9.48

50

0.2

0.54

230-1-50

REMARKS
MODEL

40LM100

TMBH

59.46

SMBH

52.96

Air
Flow
CFM

2759

AIR ON COIL

DBT
F

WBT
F

DBT
F

WBT
F

11.89

75.1

62.9

57.6

55.7

1610.0

680.0

480.0

115

115

AIR OFF COIL

DIMENSION DETAILS
(MM)

CH.
Water ESP PA
ESP PA
Flow OFFERED (CALCULATED)
GPM