MEMORIA TECNICA DESCRIPTIVA

MEMORIA TECNICA
DESCRIPTIVA DEL:
PROYECTO ELECTRICO DE MEDIA
Y BAJA TENSION DE LA
SUBESTACION ELECTRICA
TRIFASICA TIPO PEDESTAL
DE 112.5 KV- RELACION
13,200Y/7,621-220Y/127V
PROPIEDAD DE:
MOTEBURGER S.A. DE C.V,
UBICADO

Pgina 1
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

PLAZA NUEVO VERACRUZ, LOCAL


A07,AO8, KM 435.3 CARR.
MXICO-JALAPA VERACRUZ
S/N, COLONIA EL LAUREL DE
BUENAVISTA, VERACRUZ,
ESTADO DE VERACRUZ.
1. ANTECEDENTES
EL INMUEBLE DENOMINADO MOTEBURGER S.A. DE C.V, UBICADO
EN PLAZA NUEVO VERACRUZ, LOCAL A07,AO8, KM 435.3 CARR.
MXICO-JALAPA VERACRUZ S/N, COLONIA EL LAUREL DE
BUENAVISTA, VERACRUZ, ESTADO DE VERACRUZ. REQUIERE
DE
LA INSTALACIN ELCTRICA EN MEDIA Y BAJA TENSIN LA CUAL
DEBER CUMPLIR CON LA NOM-001 SEDE 2012 INSTALACIONES
ELCTRICAS (UTILIZACIN).
2. OBJETIVO
EL OBJETIVO DEL PRESENTE PROYECTO ES EL DE APLICAR LOS
CRITERIOS DEFINIDOS EN LA NOM-001 SEDE 2012 EN EL DISEO
DE
LA
INSTALACIN
ELCTRICA
DE
UTILIZACIN
PARA
GARANTIZAR LA SEGURIDAD DE LAS PERSONAS Y DEL INMUEBLE,
SATISFACIENDO PLENAMENTE LAS NECESIDADES DEL USUARIO CON
CALIDAD EN LA UTILIZACIN DE LA MISMA.

3. CONSIDERACIONES GENERALES
EL CUMPLIMIENTO DEL OBJETIVO SE GARANTIZA
APLICACIN DE LAS NORMATIVAS SIGUIENTES:
1. NOM-001

SEDE

2012

INSTALACIONES

CON

LA

ELCTRICAS

(UTILIZACIN).
Pgina 2
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

2. ESPECIFICACIONES

DE

LA

COMISIN

FEDERAL

DE

ELECTRICIDAD.

Pgina 3
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

4. SELECCIN DE LA CAPACIDAD DEL TRANSFORMADOR


CARGA TOTAL CONECTADA 70 KW A FACTOR DE POTENCIA DE 0.90, LO
QUE NOS DA UNA CARGA DE MANDADA DE 59.500 KW, CON ESTOS DATOS
PODEMOS DETERMINAR LA CAPACIDAD DEL TRANSFORMADOR:
KVA = CARGA CONECTADA / FACTOR DE POTENCIA
KVA = 70
KW / 0.90 = 77.7 KVA
POR LO TANTO EL TRANSFORMADOR INDICADO ES DE 112.5 KVA, EL
CUAL NOS DA UN FACTOR DE UTILIZACION DE 0.69 VALOR ACEPTABLE.
4.1. SELECCIN DE CONDUCTORES EN MEDIA TENSION
a) POR CAPACIDAD DE CONDUCCIN DE CORRIENTE.
EL TRANSFORMADOR TIENE UNA CAPACIDAD DE 112.5 KVA, A UNA
TENSIN NOMINAL DE 13,200 VCA,
CON ESTOS DATOS PODEMOS
DETERMINAR LA CORRIENTE DE CARGA EN EL ALIMENTADOR MEDIANTE
LA FORMULA SIGUIENTE:

EL CONDUCTOR XLP CALIBRE 85.0 MM2, (3/0 AWG), DE ACUERDO A


LAS NORMAS DE DISTRIBUCION C.F.E., TIENE UNA CAPACIDAD DE
CONDUCCIN DE 200 AMP, POR LO CUAL, EL CONDUCTOR XLP-AL-15KVCAL. 3/0 AWG, SELECCIONADO ES EL ADECUADO PARA LA ACOMETIDA
EN MEDIA TENSION DE ESTE TRANSFORMADOR.
b) POR CADA DE TENSIN
SE CONSIDERAR UNA CADA DE TENSIN NO MAYOR DEL 1 % SEGN
NORMA
DE
DISTRIBUCION
C.F.E.2.2.2-A.4.
LA
LONGITUD
EQUIVALENTE DEL CIRCUITO ES DE 103 MTS. FORMULA:

POR LO TANTO EL CONDUCTOR XLP-AL-15KV CALIBRE 3/0 AWG


CON DICHA ESPECIFICACION.

CUMPLE

Pgina 4
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

4.2. SELECCIN DE LA PROTECCIN


DE ACUERDO A LO CALCULADO EN EL PUNTO ANTERIOR LA CORRIENTE
NOMINAL EN EL LADO DE ALTA TENSION DEL TRANSFORMADOR ES DE
6.56 AMP
EL FUSIBLE LO SELECCIONAMOS EN BASE AL 150% DE LA Inom,
DE ACUERDO AL ARTICULO 450-3 (a) (1).
I =

4.92

x 1.50 = 7.38 AMP,

POR LO TANTO ES DE 8 AMP

4.4. SELECCIN DEL CONDUCTOR DE PUESTA A TIERRA


EL CALIBRE DEL CONDUCTORES DE COBRE
TIERRA EN LA TRANSION AERO-SUBTERRANEA
SERA EL CALIBRE 53.5 MM2, (1/0 AWG).

PARA LA PUESTA
A
SEGN NORMA DE C.F.E

4.5. CANALIZACIN
PARA EL CLCULO Y LA SELECCIN DE LA CANALIZACIN ADECUADA DE
LOS CONDUCTORES SE TOMA COMO REFERENCIA EL CAPITULO 10 DE
LA NOM. TABLA 10-4. CALCULO DE TUBO CONDUIT:

COMO SON MS DE DOS CONDUCTORES ACTIVOS EL Fr ES DE 40% DEL


DIAMETRO DE LA TUBERIA

POR DISEO SE SELECCIONA TRES DE 78 mm, (3). YA QUE NOS DA


UN MEJOR MARGEN DE MANIOBRABILIDAD PARA LA INTRODUCCION Y
JALADO DE LOS CABLES.

Pgina 5
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

4.6 SELECCIN DE CONDUCTORES DEL ALIMENTADOR PRINCIPAL EN


BAJA TENSION
a) POR CAPACIDAD DE CONDUCCIN DE CORRIENTE.
LA CARGA TOTAL DEMANDADA DE 70 KW , A UNA TENSIN NOMINAL DE
220 VCA, 3 Y CONSIDERANDO UN F.P. DE 0.9, CON ESTOS DATOS
PODEMOS DETERMINAR LA CORRIENTE DE CARGA EN EL ALIMENTADOR
DERIVADO MEDIANTE LA FORMULA SIGUIENTE:

EL CONDUCTOR DE ALUMINIO CALIBRE 85 MM2, (3/0 AWG), SEGN LA


TABLA 310-16 DE LA NOM, TIENE UNA CAPACIDAD DE CONDUCCIN DE
200 AMP,
A UNA TEMPERATURA AMBIENTE
DE 25 C
Y
TEMPERATURA MXIMA DE OPERACIN DE 75 C.
UTILIZANDO EL FACTOR DE CORRECCIN POR TEMPERATURA (FCT), DE
0.88 PARA UNA TEMPERATURA AMBIENTE DE 36 40 C. LA
CAPACIDAD DE CONDUCCIN DE
CORRIENTE CORREGIDA
PARA DICHO
CONDUCTOR ES:

POR LO QUE SELECCIONAMOS EL CONDUCTOR CALIBRE 85 MM2, (3/0


AWG),
PARA ALIMENTAR ESTE CIRCUITO.
b) POR CADA DE TENSIN
SE CONSIDERAR UNA CADA DE TENSIN NO MAYOR DEL 3 % SEGN
ART. 215-2, NOTA 1. LA LONGITUD EQUIVALENTE DEL CIRCUITO
ES DE 5.0 MTS.

EL
CONDUCTOR
CALIBRE 85 MM2, (3/0 AWG)
REQUERIDO POR ESTE ARTICULO.

CUMPLE CON LO

Pgina 6
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

4.7. SELECCIN DE LA PROTECCIN


SEGN EL ART. 240-3 LA PROTECCIN CONTRA SOBRE CORRIENTE
DE LOS CONDUCTORES SE DEBER SELECCIONAR DE ACUERDO CON SUS
CAPACIDADES DE CONDUCCIN ESPECIFICADAS EN LA TABLA 310-16
DE
LA
NOM-001SEDE-2005
INSTALACIONES
ELECTRICAS
(UTILIZACION).LA
PROTECCIN
SELECCIONADA
PARA
LOS
CONDUCTORES DE ESTE CIRCUITO
SER CON UN INTERRUPTOR TERMO
MAGNTICO
DE 3x300 AMP.
4.8. SELECCIN DEL CONDUCTOR DE PUESTA A TIERRA
EL CALIBRE DE LOS CONDUCTORES DE COBRE
PARA LA PUESTA
A
TIERRA DE EQUIPOS , SE SELECCIONA DE ACUERDO A LA TABLA
250-95
DE LA NOM.POR LO QUE EL CALIBRE DEL
CONDUCTOR
DE
PUESTA A TIERRA PARA ESTE CIRCUITO ES DEL CALIBRE 53.5
MM2, (1/0 AWG).
4.9. CANALIZACIN
PARA EL CLCULO Y
LA SELECCIN DE LA CANALIZACIN
ADECUADA DE LOS CONDUCTORES
SE TOMA COMO REFERENCIA
EL
CAPITULO 10 DE LA NOM. TABLA 10-4. CALCULO DE TUBO CONDUIT:

COMO SON MS DE DOS CONDUCTORES ACTIVOS EL Fr ES DE 40% DEL


DIAMETRO DE LA TUBERIA

POR DISEO SE SELECCIONA 2 DUCTOS DE 78 mm, (3). YA QUE NOS


DA UN MEJOR MARGEN DE MANIOBRABILIDAD PARA LA INTRODUCCION Y
JALADO DE LOS CABLES.

Pgina 7
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

5. CALCULO DE CORTO CIRCUITO


C.F.E
NOS INDICA UN VALOR DE CORTO CIRCUITO TRIFSICO DE
3000 AMP., PODEMOS OBSERVAR QUE ESTE VALOR ES MUY BAJO LO
CUAL NOS PERMITE DESPRECIAR LA IMPEDANCIA DEL CONDUCTOR XLP15 KV-AL CAL 3/0 YA QUE DE LO CONTRARIO EL VALOR QUE SE
OBTENDRA
EN
LAS
TERMINALES
DE
MEDIA
TENSIN
DEL
TRANSFORMADOR SERA LEVEMENTE MAS BAJO.
POR LO ANTERIOR TENEMOS:
POTENCIA BASE 1000 KVA
KV BASE 13.2 KV
LA CORRIENTE BASE LA OBTENEMOS DE
I BASE =
I BASE =

P BASE_____
1.732 X KV BASE
1000____
1.732 X 13.2

I BASE = 43.73 AMP


I CC P. U. = 3000 / 43.73 P.U.
I CC P.U. = 68.58 P.U.
AHORA CALCULAMOS LA IMPEDANCIA DE THEVENIN DEL SISTEMA
Zsth = 1 / Iff P.U.

P.U.

Zsth = 1 / 68.58 P.U.


Zsth = 0.0145 P.U.
AHORA CALCULAMOS LA IMPEDANCIA DEL TRANSFORMADOR DE 112.5 KVA
Zt

= %Zt X (KVA BASE NUEVOS/KVA BASE DADOS)

Zt

= (2.8/100) X (1000/112.5)

Zt

= 0.2488 P.U.

AHORA BIEN LA IMPEDANCIA DE THEVENIN EN LAS TERMINALES DEL


BAJA TENSION DEL TRASFORMADOR
Pgina 8
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

Zth =

Zs + Ztr

P.U.

Zth =

0.0145+0.2488

Zth =

0.2633 P.U.

P.U.

AHORA CALCULAMOS EL VALOR DE CORTO CIRCUITO TRIFASICO EN BAJA


TENSION
I ff 3 = 1/0.2633 P.U.
I ff 3 = 3.7966
I BASE =

1000____
1.732 X 0.22

IBASE = 2,624 A
I ff 3 REAL = 3.7966 X 2,624 AMP
I ff 3 REAL = 9,962 AMP.
AHORA CALCULAMOS EL VALOR DE CORTO CIRCUITO MONOFASICO EN
BAJA TENSION
I ff 1 = 1/ 0.2488 P.U.
I ff 1 = 4.0192 P.U.
I BASE =

1000___
1.732 X 0.22

IBASE = 2,624 A
I ff 1 REAL = 4.0192 X 2,624 AMP
I ff 1 REAL = 10.54

AMP.

CON ESTE VALOR PODEMOS DECIR QUE LA CAPACIDAD INTERRUPTIVA DE


LOS EQUIPOS INSTALADOS ESTAN POR ARRIBA DEL VALOR OBTENIDO,
YA QUE EL FABRICANTE POR DISEO LOS PROPORCIONA CON UN VALOR
DE 42 KA.

Pgina 9
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

6. CLCULO DEL SISTEMA DE TIERRAS


6.1 CALIBRE MINIMO DEL CONDUCTOR DE LA RED DE
TIERRAS.
EL CLCULO DEL CALIBRE MNIMO DEL CONDUCTOR QUE
CONSTITUYE LA RED DE TIERRA SE DETERMINA CON LA EXPRESIN
SIGUIENTE:
Icc
A

Tm
234

log

Ta
Ta

33s
DONDE:
A
=
Icc =
S
=
Tm

Ta

SECCIN TRANSVERSAL DEL CONDUCTOR EN CIRCULAR KCM


CORRIENTE DE CORTO CIRCUITO EN AMPERES
TIEMPO EN SEGUNDOS, DURANTE EL CUAL CIRCULA LA
CORRIENTE CORTO CIRCUITO
TEMPERATURA MXIMA PERMISIBLE EN EL CONECTOR, EN
GRADOS CENTGRADOS
TEMPERATURA AMBIENTE, EN GRADOS CENTGRADOS.

LA TEMPERATURA MXIMA PERMISIBLE EN CONECTORES ES:


Tm
Tm

=
=

450
250

C
C

(PARA CONECTORES SOLDABLES)


(PARA CONECTORES MECNICOS)

14,062
A

=
lo
g

450
234

40
40

33(0.083
3)
A =

14,062

/ 0.2523 = 55,735

Pgina 10
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

EL VALOR APROXIMADO ES EL 105,500 QUE CORRESPONDE AL 1/0 AWG,


PERO POR RAZONES DE SEGURIDAD SE SELECCIONA EL CALIBRE 4/0
AWG

Pgina 11
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

6.2 DISEO PREMILIMINAR DE LA RED DE TIERRAS


4/0
AWG

2.00
MTS

4/0
AWG

4/0
AWG

4/0
AWG

2.00
MTS

Ar = 4 M2
N = 4
D = 2.0 MTS
LONGITUD DEL CONDUCTOR:
CONDUCTORES HORIZONTALES =
CONDUCTORES VERTICALES
TOTAL

4 mts
4 mts
=

8 mts

6.3 NUMEROS DE ELECTRODOS REQUERIDOS.


LA UNIN DEL CONDUCTOR DE LA RED DE TIERRAS AL ELECTRODO SE
DEBER HACER CON CONECTORES DEL TIPO MECNICO O PROCESO DE
SOLDADURA.
EL NMERO DE ELECTRODOS EN LA RED DE TIERRAS SE DETERMINA POR
LA EXPRESIN:
Nv = 0.6 Ar
DONDE:
Nv = NUMERO DE VARILLAS
Ar = REA TOTAL DE LA MALLA PROPUESTA EN M2
____
Nv = 0.6 (4)= 1.2
6.4 LONGITUD MINIMA DEL CONDUCTOR REQUERIDO EN LA RED DE
TIERRAS.
PARA DETERMINAR LA LONGITUD MNIMA DEL CONDUCTOR REQUERIDO EN
LA RED DE TIERRAS DESARROLLAR LA FORMULA SIGUIENTE:
L =

Km

x Ki

x
116

p
+

x
0.17

Icc
x

x
ps

DONDE:
Pgina 12
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

L
=
Km=

LONGITUD MNIMA REQUERIDA EN LA RED DE TIERRAS, EN


METROS.
COEFICIENTE
QUE TOMA EN CUENTA EL NMERO DE
CONDUCTORES
PARALELOS
N,
SU
DIMETRO
d,
PROFUNDIDAD DE INSTALACIONES H Y ESPACIAMIENTO
ENTRE LOS MISMOS D.

LA CANTIDAD DE FACTORES ENTRE PARNTESIS EN EL 2. TERMINO ES


EL NUMERO DE CONDUCTORES EN PARALELO N MENOS DOS.
Km

l
n

D2

2
Km

1
2

16

l
n
16 x 0.
4

x h

+
x d

l
n

107.2x10-

3
4

ln

Km= 0.2805 0.0915 = 0.1890


Ki

FACTOR DE CORRECCIN POR IRREGULARIDAD


Ki = 0.65+0.17n = 0.65+0.17(4)= 1.33

N =
P
t
PS
LA

NUMERO DE CONDUCTORES EN PARALELO EN UNA DIRECCIN


QUE FORMAN LA MALLA
= RESISTIVIDAD PROMEDIO DEL TERRENO EN /M
= MXIMA DURACIN
DEL CHOQUE EN SEGUNDOS. PARA
EFECTOS DE CLCULO EN ESTE PROCEDIMIENTO CONSIDERE t
= S
= RESISTIVIDAD SUPERFICIAL DEL TERRENO EN /M
RESISTIVIDAD PROMEDIO DEL TERRENO ES DE:
P =

2.00

/MT2

Y LA RESISTIVIDAD SUPERFICIAL, EN ESTE CASO LA DEL CONCRETO


ES DE:
PS

3000

/MT2

POR LO TANTO
L

= 0.1890

x 1.33

L=

x
116

2.0
+

x
0.17

14,06
2
X

x
3000

0.0833

6,452/626 =10.30 mts


Pgina 13

ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780


CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

PARA PODER CONTINUAR CON EL CLCULO DE LA RED ES NECESARIO


QUE SE CUMPLA LA SIGUIENTE COMPROBACIN.
L < LPROP
DONDE:
LPROP = LONGITUD DEL CONDUCTOR DE LA MALLA PROPUESTA
L
= LONGITUD MNIMA REQUERIDA EN LA RED DE TIERRAS
LPROP = (No
COND.
VERTICALES*LONG)
+
(No
COND.
HORIZONTALES * LONG) + (Nv * LONG)
LPROP = ( 2 x 2 ) + ( 2 x 2 ) + (3.05 x 4 ) = 20.2
10.30 < 20.2
6.5

RESISTENCIA DE LA RED DE TIERRAS

LA RESISTENCIA DE LA RED DE TIERRAS SE DETERMINA POR LA


FORMULA SIGUIENTE:
R= _p_ + _p_
4r
L
DONDE:
R
P
R

=
=
=

RESISTENCIA DE LA RED DE TIERRAS, EN


RESISTIVIDAD OHMICA DEL TERRENO, EN -METRO
RADIO DE UNA PLACA CIRCULAR EQUIVALENTE, CUYA
REA ES LA MISMA QUE LA OCUPADA POR LA MALLA REAL
DE TIERRAS, EN METROS.
LONGITUD TOTAL DE LOS CONDUCTORES DEL SISTEMA DE
TIERRAS, EN METROS.

r =

Ar

r =

2.
0
4 x

0.7978
+

0.797
8

2.0

1.5358

2.2

Pgina 14
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

6.6 CALCULO DEL MAXIMO AUMENTO DE POTENCIAL EN LA RED DE


TIERRAS.
DESARROLLAR LA FORMULA SIGUIENTE:
E = Icc x R (VOLTS)
DONDE:
E

MXIMO AUMENTO DE POTENCIAL EN LA RED, EN VOLTS


E = 14,062

6.7

x 1.5358 = 21,596 V

CALCULO DE POTENCIALES TOLERABLES.


Ep

116

0.7 x

ps

t
DONDE:
Ep
Ec

=
=

POTENCIAL DE PASO TOLERABLE EN VOLTS.


POTENCIAL DE CONTACTO TOLERABLE EN VOLTS.
Ep

116

0.7

3000

7,677 V

3000

2,169 V

0.083
3
Ec

116

0.17
0.083
3

6.8

CALCULO DE POTENCIALES PROBABLES.


Epr

Ks

x Ki x p x

Icc
Lprp

Em

Km

x Ki x p x

Icc
Lprp

DONDE:
Epr = POTENCIAL DE PASO EN LA RED, EN VOLTS.
Em = POTENCIAL DE MALLA
Ks = COEFICIENTE QUE TOMA EN CUENTA LA GEOMETRA DE LA
RED, DIMETRO DEL CONDUCTOR d, PROFUNDIDAD DE
INSTALACIN H Y EL ESPACIAMIENTO ENTRE LOS MISMOS
D.
Pgina 15
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.

MEMORIA TECNICA DESCRIPTIVA

Ks

1
2h

1
+

1
2D

1
3D

EL TOTAL DE TRMINOS DENTRO DEL PARNTESIS ES IGUAL AL NMERO


DE CONDUCTORES EN PARALELO DE LA MALLA.
Ks =

1
2x0.
4

+
107.2x10

1
+ 0.4

+ 1
2x1

1
3x1

-3

Ks = 0.0784
Ep
r

= 0.078
4

1.3
3

2.
0

14,06
2
20.2

14,06
2
20.2

Epr = 145 Volts


Em

0.189
0

Em =

1.3
3

2.
0

349 Volts

6.9 CONDICIONES DE SEGURIDAD.


PARA QUE LA MALLA PROPUESTA SEA ACEPTADA DEBE CUMPLIR CON LA
SIGUIENTE COMPARACIN.
Epr < Ep
145 < 7,678

Em < Ec
349 < 2,169

Pgina 16
ING. DAVID GUSTAVO DE LA O GOMEZ; CEDULA PROFESIONAL: 5713780
CARR. A BOSQUES DE SALOYA KM 2; R/A EMILIANO ZAPATA, CENTRO, TAB.