00809-0100-4100, Rev AA
March 2013
Note
Use a pressure input source that is at least four times more accurate than the transmitter, and
allow the input pressure to stabilize for ten seconds before entering any values.
3, 5, 1, 1
Assemble and power the entire calibration system including the 3051, Field
Communicator/AMS, power supply, pressure input source, and readout device.
2.
3.
Select 5: Maintenance
4.
Select 1: Calibration.
5.
6.
Select 2: Lower Sensor Trim. The lower sensor trim value should be the sensor trim
point that is closest to zero.
Note
Select pressure points so that lower and upper values are equal to or outside the expected
process operation range.
7.
Follow the on-screen instructions to complete the adjustment of the lower value.
8.
Repeat the procedure for the upper value. Select 1: Upper Sensor Trim and follow the
on-screen instructions to complete the adjustment of the upper value.
Follow the screen prompts to perform a Sensor Trim using AMS Device Manager.
2.
If desired right click on the device and under the Method drop down menu, move cursor
over Calibrate and under Sensor Trim and select Upper Sensor Trim