Reference Manual

Section 6: Troubleshooting

00809-0100-4100, Rev AA

March 2013

6.2.1

Warnings ( )
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the approvals section of the 3051 reference manual for any restrictions associated with a
safe installation.
Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions.

This device may not cause harmful interference. This device must accept any interference
received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 8 in. (20
cm) from all persons.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the o-ring designed to seal with the corresponding
flange adapter.
Electrical shock can result in death or serious injury.

Avoid contact with the leads and the terminals. High voltage that may be present on
leads can cause electrical shock.

Table 6-1. Rosemount 3051 Wireless Device Status Information


Device Status

Description

Electronics Failure

An electronics error that could


impact the device measurement
reading has occurred.

Radio Failure

The wireless radio has detected a


failure or stopped communicating.

Recommended Action
1.

Reset the device

2.

Reconfirm all configuration items in the device

3.

If the condition persists, replace the electronics

1.

Reset the device

2.

If the condition persists, replace the electronics

Supply Voltage
Failure

The supply voltage is too low for


the device to function properly.

1.

Replace the Power Module

Electronics Warning

The device has detected an


electronics error that does not
currently impact the device
measurement reading.

1.

Reset the device

2.

Reconfirm all configuration items in the device

3.

If the condition persists, replace the electronics

84

Troubleshooting